SAG588820100 SAG588820200 System Application Guide Spec No. 588820100 (Model 48BA1200-19) Spec No. 588820200 (Model 48BA1200-23) Issue AA, September 8, 2010 Home SYSTEM OVERVIEW Description: Front Access Battery Rack System consisting of a nominal 19” or 23” wide 7’ tall relay rack, battery trays, and busbar termination assembly. The battery trays accommodate a variety of front terminal -48V valve regulated lead acid (VRLA) batteries. Includes factory routed and lugged cabling from each battery tray to the termination assembly. May also be equipped with optional left or right side mounted battery disconnect circuit breakers. When equipped with battery disconnect circuit breakers, factory CB alarm wiring is provided to an alarm card. The alarm card provides external relay contacts and resistive battery for connection to customer external alarm circuits. Application: For use with -48VDC NetSure™ Power Systems and other -48VDC Power Systems. Spec. Nos.: 588820100 (19”). 588820200 (23”). Models: 48BA1200-19 (19”). 48BA1200-23 (23”). Output Voltage: -48VDC. Capacity: 960A, maximum, when equipped with six (6) battery trays. Agency Approval: UL Listed, Seismic Zone 4, NEBS (pending). Framework Type: Relay Rack. Mounting Width: 19” or 23” Wide (Nominal) Relay Rack (part of system). Mounting Depth: 588820100: Determined by battery trays ordered. A 16.5” deep and 21” deep battery tray is available. 588820200: Determined by battery trays ordered. A 24.4” deep battery tray is available. Access: Front for Installation and Maintenance. Color: Gray. List Options: Common Equipment (19” Mounting), Common Equipment (23” Mounting), Battery Tray (19” Mounting, 17” Deep), Battery Tray (19” Mounting, 21” Deep), Battery Tray (23” Mounting, 21” Deep). Accessory Options: Batteries, Optional Battery Disconnect Circuit Breaker Kits. Environment: 0°C to +50°C (+32°F to +122°F). Page 1 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home 588820100 and 588820200 Battery Termination Busbars (Battery and GND/RTN) (P/O List 1) 588820100 List 1 (Common Equipment, 19” Mounting) 588820200 List 1 (Common Equipment, 23” Mounting) 588820100 List 10 (Battery Tray, 19” Mounting, 16.5” Deep) 588820100 List 11 (Battery Tray, 19” Mounting, 21” Deep) 588820200 List 11 (Battery Tray, 23” Mounting, 24.4” Deep) 19” x 7’ Relay Rack (P/O List 1) 23” x 7’ Relay Rack (P/O List 1) SEE ALSO System Overview Accessory Descriptions Table of Contents Specifications Ordering Information Physical Size Information List Descriptions Related Documentation Page 2 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 TABLE OF CONTENTS Ordering Information System Overview Picture List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation SYSTEM OVERVIEW.................................................................................................................................................1 TABLE OF CONTENTS.............................................................................................................................................3 ORDERING INFORMATION......................................................................................................................................4 List Options..........................................................................................................................................................4 Accessory Options..............................................................................................................................................5 LIST DESCRIPTIONS ................................................................................................................................................6 588820100 List 1: Common Equipment, -48V, 19" Battery Rack System......................................................6 588820100 List 10: Battery Tray, 19" Mount, 16.5" Deep (547555) ...............................................................6 588820100 List 11: Battery Tray, 19" Mount, 21" Deep (547550) ..................................................................7 588820200 List 1: Common Equipment, -48V, 23" Battery Rack System......................................................7 588820200 List 11: Battery Tray, 23" Mount, 24.4" Deep (547560) ...............................................................8 ACCESSORY DESCRIPTIONS.................................................................................................................................9 Batteries ...............................................................................................................................................................9 19” Battery Shelf...............................................................................................................................................9 23” Battery Shelf.............................................................................................................................................10 Optional Battery Disconnect Circuit Breaker Kits .........................................................................................11 SPECIFICATIONS....................................................................................................................................................12 1.1 Environmental Ratings .............................................................................................................................12 1.2 Compliance Information ...........................................................................................................................12 PHYSICAL SIZE INFORMATION ............................................................................................................................13 Overall Dimensions – 588820100 List 1 with List 10 or List 11 ....................................................................13 Overall Dimensions – 588820200 List 1 with List 11......................................................................................14 Floor Mounting Dimensions – 588820100.......................................................................................................15 Floor Mounting Dimensions – 588820200.......................................................................................................15 Battery Lug Landing Dimensions – 588820100 and 588820200 ...................................................................16 Circuit Breaker Alarms .....................................................................................................................................17 BATTERY MANUFACTURER INFORMATION ......................................................................................................18 RELATED DOCUMENTATION................................................................................................................................18 Page 3 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home ORDERING INFORMATION List Options Order the following by the items Part Number as specified in the following table. When viewing electronically, click on the Link to jump to the detailed description page. List No. Part Number 1 58882010001 10 58882010010 11 58882010011 1 58882020001 11 58882020011 Description Common Equipment, -48V, 19" Battery Rack System Includes (1) relay rack, (2) vertical tray mounting brackets, (1) busbar kit with covers, (12) cable lacing brackets, (1) instruction manual, and packaging. Battery Tray, 19" Mount, 16.5" Deep Includes tray, hardware, cable cut to length, lugs. Battery Tray, 19" Mount, 21" Deep Includes tray, hardware, cable cut to length, lugs. Common Equipment, -48V, 23" Battery Rack System Includes (1) relay rack, (2) vertical tray mounting brackets, (1) busbar kit with covers, (12) cable lacing brackets, (1) instruction manual, and packaging. Battery Tray, 23" Mount, 24.4" Deep Includes tray, hardware, cable cut to length, lugs. Notes: 1) 588820100: Vertical tray spacing is automatically determined by battery tray selection; 7RU for List 10 and 6RU for List 11. 588820200: Vertical tray spacing is automatically determined by battery selection; 6RU, 7RU, or 8RU. If no battery is selected, spacing is 8RU. 2) 588820100: The locations of the cable lacing brackets is determined by the tray spacing, total of six (6) per side. 588820200: The locations of the cable lacing brackets is determined by the tray spacing, total of six (6) per side for 6RU or 7RU and five (5) per side for 8RU. 3) Cable size for each tray is 2AWG for optional battery disconnect circuit breakers selected up to 100A and 1/0AWG for circuit breakers selected over 100A or for systems without battery disconnects. 4) If a battery type is not selected, battery terminal lugs are provided and shipped loose for all batteries listed for use with the battery tray ordered and for the cable size determined in Note 3). Page 4 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Home Accessory Options Order the following by the items Part Number as specified in the following table. When viewing electronically, click on the link to jump to the detailed description page. Description Batteries Optional Battery Disconnect Circuit Breaker Kits Part Number See ACCESSORY DESCRIPTIONS Section Page 5 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home LIST DESCRIPTIONS 588820100 List 1: Common Equipment, -48V, 19" Battery Rack System Features ♦ Provides the following equipment: (1) nominal 19” wide by 7’ tall relay rack, (2) vertical tray mounting brackets, (1) busbar kit with covers, (12) cable lacing brackets, (1) instruction manual, and packaging. ♦ Factory assembled per battery trays and optional battery disconnect circuit breakers ordered. Restrictions The relay rack accommodates up to six (6) battery trays (spaced 6RU or 7RU apart, as determined by the battery tray ordered). Ordering Notes 1) Order as required. 588820100 List 10: Battery Tray, 19" Mount, 16.5" Deep (547555) Features ♦ Provides a 16.5” deep battery tray for the nominal 19” wide relay rack provided as part of List 1. The battery tray holds four (4) 12V front terminal valve regulated lead acid (VRLA) batteries. Battery cabling is factory provided and connected to the system’s main busbars. Batteries are configured as one (1) 48V string per tray. ♦ Trays can be ordered with or without a battery disconnect circuit breaker. When circuit breakers are ordered, one is provided in the –48V lead of each battery string (1 circuit breaker per tray). ♦ Refer to the “Physical Size Information” section for dimensions. Restrictions Designed to accommodate the batteries listed under Batteries in the ACCESSORY DESCRIPTIONS section. A single battery tray must mount at bottom of relay rack. Multiple battery trays must mount starting at bottom of relay rack and working upward. Factory spaces battery trays 7RU apart. Cable size for each tray is 2AWG for optional battery disconnect circuit breakers selected up to 100A and 1/0AWG for circuit breakers selected over 100A or if circuit breakers are not selected. Ordering Notes 1) Order up to six (6) battery trays per relay rack, as required. 2) Order batteries separately. See Batteries in the ACCESSORY DESCRIPTIONS section. Battery cables and lugs factory provided and connected. 3) If an optional battery disconnect circuit breaker is desired, order per Optional Battery Disconnect Circuit Breaker Kits in the ACCESSORY DESCRIPTIONS section. Page 6 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 588820100 List 11: Battery Tray, 19" Mount, 21" Deep (547550) Home Features ♦ Provides a 21” deep battery tray for the nominal 19” wide relay rack provided as part of List 1. The battery tray holds four (4) 12V front terminal valve regulated lead acid (VRLA) batteries. Battery cabling is factory provided and connected to the system’s main busbars. Batteries are configured as one (1) 48V string per tray. ♦ Trays can be ordered with or without a battery disconnect circuit breaker. When circuit breakers are ordered, one is provided in the –48V lead of each battery string (1 circuit breaker per tray). ♦ Refer to the “Physical Size Information” section for dimensions. Restrictions Designed to accommodate the batteries listed under Batteries in the ACCESSORY DESCRIPTIONS section. A single battery tray must mount at bottom of relay rack. Multiple battery trays must mount starting at bottom of relay rack and working upward. Factory spaces battery trays 6RU apart. Cable size for each tray is 2AWG for optional battery disconnect circuit breakers selected up to 100A and 1/0AWG for circuit breakers selected over 100A or if circuit breakers are not selected. Ordering Notes 1) Order up to six (6) battery trays per relay rack, as required. 2) Order batteries separately. See Batteries in the ACCESSORY DESCRIPTIONS section. Battery cables and lugs factory provided and connected. 3) If an optional battery disconnect circuit breaker is desired, order per Optional Battery Disconnect Circuit Breaker Kits in the ACCESSORY DESCRIPTIONS section. 588820200 List 1: Common Equipment, -48V, 23" Battery Rack System Features ♦ Provides the following equipment: (1) nominal 23” wide by 7’ tall relay rack, (2) vertical tray mounting brackets, (1) busbar kit with covers, (12) cable lacing brackets, (1) instruction manual, and packaging. ♦ Factory assembled per battery trays and optional battery disconnect circuit breakers ordered. Restrictions The relay rack accommodates up to six (6) battery trays when spaced 6RU or 7RU apart and five (5) battery trays when spaced 8RU apart. Battery selection determines tray spacing. Ordering Notes 1) Order as required. Page 7 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) 588820200 List 11: Battery Tray, 23" Mount, 24.4" Deep (547560) Home Features ♦ Provides a 24.4” deep battery tray for the nominal 23” wide relay rack provided as part of List 1. The battery tray holds four (4) 12V front terminal valve regulated lead acid (VRLA) batteries. Battery cabling is factory provided and connected to the system’s main busbars. Batteries are configured as one (1) 48V string per tray. ♦ Trays can be ordered with or without a battery disconnect circuit breaker. When circuit breakers are ordered, one is provided in the –48V lead of each battery string (1 circuit breaker per tray). ♦ Refer to the “Physical Size Information” section for dimensions. Restrictions Designed to accommodate the batteries listed under Batteries in the ACCESSORY DESCRIPTIONS section. A single battery tray must mount at bottom of relay rack. Multiple battery trays must mount starting at bottom of relay rack and working upward. Factory spaces battery trays 6RU, 7RU, or 8RU apart as determined by battery selected. If no battery selected, factory spaces battery trays 8RU apart. Cable size for each tray is 2AWG for optional battery disconnect circuit breakers selected up to 100A and 1/0AWG for circuit breakers selected over 100A or if circuit breakers are not selected. Ordering Notes 1) Order up to six (6) battery trays per relay rack when spaced 6RU or 7RU apart or five (5) battery trays per relay rack when spaced 8RU apart, as required. 2) Order batteries separately. See Batteries in the ACCESSORY DESCRIPTIONS section. Battery cables and lugs factory provided and connected. 3) If an optional battery disconnect circuit breaker is desired, order per Optional Battery Disconnect Circuit Breaker Kits in the ACCESSORY DESCRIPTIONS section. Page 8 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Home ACCESSORY DESCRIPTIONS Batteries 19” Battery Shelf Manufacturer* Manufacturer P/N Emerson P/N (12V Module) Capacity (A-Hr) Dimension WxLxH (Inches) (per 12V Module) Min Tray Spacing (RU) Weight (lb) (per 12V Module) Lug Kit 2AWG Lug Kit 1/0AWG 528235 Deka 12AVR100ET 104264 96 4.33 x 20.13 x 9.38 6 75 528234 Douglas DSN12-100F -- 100 4.24 x 15.59 x 11.30 7 77.7 528234 528235 Douglas DSN12-90F -- 88 4.24 x 15.59 x 10.04 7 70.6 528234 528235 Enersys 12V92F 122005 92 4.10 x 16.40 x 10.10 7 61.7 528234 528235 Enersys 12VE115F -- 101 4.33 x 20.10 x 9.25 6 80.5 528234 528235 Enersys SBS 100F -- 100 4.30 x 15.60 x 11.30 7 71.9 528234 528235 Enersys SBS C11F -- 91 4.10 x 16.40 x 10.10 7 61.6 528234 528235 FIAMM 12UMTX100/19FT -- 100 4.25 x 15.55 x 10.83 7 74.8 528234 528235 GNB M12V105FT 103715 100 4.33 x 20.12 x 9.37 6 78.8 528234 528235 GNB M12V90FT 524858 86 4.13 x 15.55 x 10.63 7 68.2 528234 528235 Northstar NSB100FT -- 100.5 4.24 x 15.59 x 11.30 7 78.5 528234 528235 Northstar NSB12-330FT -- (330W) 4.20 x 15.60 x 10.00 7 70.6 528234 528235 Northstar NSB12-380FT -- (380W) 4.20 x 15.60 x 11.30 7 78.3 528234 528235 Northstar NSB90FT -- 87.8 4.24 x 15.59 x 10.04 7 70.6 528234 528235 * See Battery Manufacturer Information Page 9 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home 23” Battery Shelf Capacity (A-Hr) Dimension WxLxH (Inches) (per 12V Module) Min Tray Spacing (RU) Weight (lb) (per 12V Module) Lug Kit 2AWG Lug Kit 1/0AWG Manufacturer* Manufacturer P/N Emerson P/N (12V Module) C&D TEL12-105F 514368 100 4.94 x 22.51 x 9.00 6 84.9 528234 528235 C&D TEL12-160F 140456 157 4.95 x 22.01 x 11.14 7 115 528234 528235 C&D TEL12-180F -- 181 4.95 x 22.01 x 12.60 8 131 528234 528235 Deka 12AVR-150ET 122018 150 4.90 x 22.00 x 11.75 8 115 528234 528235 Deka 12AVR-170ET 541381 170 4.91 x 22.16 x 12.60 8 120 528234 528235 528235 Deka HR5500ET -- 152 4.90 x 22.00 x 11.75 8 120 528234 Douglas DSN12-110F -- 110 4.92 x 22.05 x 8.94 6 86.4 528234 528235 Douglas DSN12-170F 127691 171 4.92 x 22.05 x 12.60 8 129.6 528234 528235 Douglas DST12-170F -- 170 4.96 x 21.97 x 12.64 8 132 528234 528235 Enersys 12TX105F -- 100 4.90 x 22.10 x 9.30 6 105.8 528234 528235 Enersys 12V100F -- 100 4.90 x 22.00 x 9.00 6 104.7 528234 528235 Enersys 12V155FS 122010 155 4.90 x 22.10 x 11.10 7 125.6 528234 528235 Enersys 12V170F -- 170 4.90 x 22.10 x 12.40 8 147.7 528234 528235 Enersys 12VF105F -- 107 4.90 x 22.10 x 9.30 6 101.4 528234 528235 Enersys 12VX100F -- 100 4.90 x 22.00 x 9.00 6 104.7 528234 528235 Enersys SBS 170F -- 170 4.90 x 22.10 x 11.10 7 115.7 528234 528235 Enersys SBS 190F -- 190 4.90 x 22.10 x 12.40 8 132.3 528234 528235 FIAMM 12FAT100 -- 100 4.96 x 21.97 x 9.06 6 90.39 528234 528235 FIAMM 12FAT125 -- 125 4.96 x 21.97 x 10.67 7 110.23 528234 528235 FIAMM 12FAT155 -- 155 4.96 x 21.97 x 12.64 8 132.28 528234 528235 FIAMM 12UMTX100FT -- 100 4.96 x 21.97 x 9.06 6 83.6 528234 528235 FIAMM 12UMTX110FT -- 110 4.96 x 21.97 x 9.06 6 90.39 528234 528235 FIAMM 12UMTX140FT -- 140 4.96 x 21.97 x 10.67 7 110 528234 528235 FIAMM 12UMTX155FT -- 155 4.96 x 21.97 x 12.64 8 129.8 528234 528235 FIAMM 12UMTX170FT -- 170 4.96 x 21.97 x 12.64 8 132 528234 528235 FIAMM 12UMTX180FT -- 180 4.96 x 21.97 x 12.64 8 134 528234 528235 GNB M12V125FT 123617 125 4.88 x 22.01 x 11.14 7 104.7 528234 528235 GNB M12V155FT 112795 155 4.88 x 22.01 x 11.14 7 118.4 528234 528235 GNB M12V180FT -- 180 4.88 x 22.01 x 12.50 8 133 528234 528235 Northstar NSB110FT -- 110 4.92 x 22.05 x 8.94 6 91.3 528234 528235 Northstar NSB12-600FT -- (600W) 4.90 x 22.10 x 12.60 8 131.2 528234 528235 Northstar NSB155FT -- 148 4.92 x 22.05 x 11.14 7 131.2 528234 528235 Northstar NSB170FT 126111 171 4.92 x 22.05 x 12.60 8 131.2 528234 528235 * See Battery Manufacturer Information Page 10 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Optional Battery Disconnect Circuit Breaker Kits Home Features ♦ Provides a battery disconnect circuit breaker housing mounted on the left or right side of the battery tray. Selected circuit breaker factory installed and wired. Restrictions Factory wires Battery Rack System with 2AWG cables for battery disconnect circuit breakers selected up to 100A and 1/0AWG cables for circuit breakers selected over 100A. Ordering Notes 1) Order one (1) kit per tray, as required, from the following table. Part Number 528500 528501 528502 528503 Description Single Pole, Right Side Mounted Single Pole, Left Side Mounted Double Pole, Right Side Mounted Double Pole, Left Side Mounted 2) Order one (1) circuit breaker per tray from the following table. Ampere Rating P/N Electrical/Mechanical Trip1 (Black Handle) No. of Poles 30 256693100 35 256693500 40 256693900 50 256694300 1-Pole 60 256694700 70 256695100 75 256695500 100 256695900 125 100765 2-Pole 150 100763 200 121810 Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical or manual trip condition. Page 11 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home SPECIFICATIONS 1.1 Environmental Ratings 1.1.1 Operating Ambient Temperature Range: 0°C to +50°C (+32°F to +122°F). 1.1.2 Storage Ambient Temperature Range: -40°C to +85°C (-40°F to +185°F). 1.1.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to 95%, non-condensing. 1.1.4 Altitude: (A) Operating: -200 feet (-61 meters) to 10,000 feet (3048 meters). Derate operating ambient temperature range by 2°C per 1000 feet (305 meters) above 5000 feet (1524 meters). (B) Storage and Transportation: -1,000 feet (-305 meters) to 50,000 feet (15,241 meters). 1.1.5 1.2 Aisle Space Clearance: Recommended minimum aisle space clearance is 2'6" for the front of the Battery Rack System and 4” for the rear of the Battery Rack System. Compliance Information 1.2.1 Safety Compliance: This power board is UL Listed as a DC Power Distribution Center for Communications Equipment. This unit meets the requirements of CSA 22.2, No. 225 and is tested and Certified by UL ("c UL") as a Custom Built Power Distribution Center for Communications Equipment. (pending) 1.2.2 Seismic Compliance: NEBS Zone 4 Earthquake compliant when equipped with four (4) or fewer battery trays. (pending) 1.2.3 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS compliance reports. (pending) Page 12 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Home PHYSICAL SIZE INFORMATION Overall Dimensions – 588820100 List 1 with List 10 or List 11 Notes: 1. Dimensions are in inches. 2. P/N 547550 battery tray shown, P/N 547555 similar. 3. W eight (LB S ) List N o . T ra y P /N T ra y O verall D im ensions 5888 201 00 List 1 0 5475 55 5888 201 00 List 1 1 5475 50 w/ C ircuit B reak er O ptio n w /out C ircuit B reak er O ptio n D im ensions C A B 19” M o unting 16.5” D ee p 16.5 7.29 7RU 19” M o unting 21” D ee p 21.0 7.29 6RU 4. Finish: Gray 5. Maximum trays available per rack is six (6). Optional battery disconnect circuit breakers mount on left or right side of battery tray. Top View B (see Note 3) 84.00 C (see Note 3) Left Side View 21.80 Front View A (see Note 3) Right Side View Page 13 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home Overall Dimensions – 588820200 List 1 with List 11 Notes: 1. Dimensions are in inches. 2. W eight (LB S ) List N o . T ra y P /N T ra y O verall D im ensions 5888 202 00 List 1 1 5475 60 23” M o unting 4.4” D ee p 24.4” w/ C ircuit B reak er O ptio n w /out C ircuit B reak er O ptio n D im ensions A 24.4 B 9.78 C 6RU, 7RU, or 8RU 3. Finish: Gray 4. Maximum trays available per rack is six (6) with 6RU or 7RU spacing, and five (5) with 8RU spacing. Optional battery disconnect circuit breakers mount on left or right side of battery tray. Top View B (see Note 2) 84.00 C (see Note 2) Left Side View 25.80 Front View A (see Note 2) Right Side View Page 14 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Floor Mounting Dimensions – 588820100 Home Floor Mounting Dimensions – 588820200 Page 15 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) Home Battery Lug Landing Dimensions – 588820100 and 588820200 588820100 Top of Relay Rack (some components removed for clarity) GND/RTN Busbar -48V Battery Busbar -48V Battery and GND/RTN Busbars Customer Battery Cable Connections to Pwr. Sys. Customer Battery Cable Connections to Pwr. Sys. Factory Battery Cable Connections Front Factory Battery Cable Connections 588820200 Top of Relay Rack (some components removed for clarity) GND/RTN Busbar -48V Battery and GND/RTN Busbars -48V Battery Busbar Customer Battery Cable Connections to Pwr. Sys. Customer Battery Cable Connections to Pwr. Sys. Factory Battery Cable Connections Front Factory Battery Cable Connections Page 16 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Home Circuit Breaker Alarms Top of Relay Rack Alarm Card Front Notes: Relay shown in deenergized state. Relay energizes during alarm condition. N.O. (Normally Open Contact) Com. (Common) N.C. (Normally Close Contact) J3 4 N.O. 3 2 N.C. Terminal Block (J3) accepts a wire size in the range of 26AWG to 14AWG (solid or stranded). Recommended Torque (J3): 0.5 to 0.6 Nm. 1 Resistive Battery Com. Page 17 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG588820100 SAG588820200 Issue AA, September 8, 2010 System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) BATTERY MANUFACTURER INFORMATION Home The Battery Rack Systems described in this System Application Guide are designed to accommodate batteries from various manufacturers. The following are referenced in this document. C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858 Deka®: East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147 Douglas®: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159 Fiamm: FIAMM T.I, 23880 Industrial Park Drive, Farmington Hills, Detroit, MI 48335 GNB MarathonTM: GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543 Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803 PowerSafe EnersysTM: EnerSys Inc., Reading, PA, 196212-4145 RELATED DOCUMENTATION Schematic Diagram: SD588820100/SD588820200 Wiring Diagram: T588820100/T588820200 Instructions: Section 6045 Page 18 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 588820100 (Model 48BA1200-19) Spec. No. 588820200 (Model 48BA1200-23) SAG588820100 SAG588820200 Issue AA, September 8, 2010 Home REVISION RECORD Issue Change Number (ECO) AA LLP213933 Description of Change New Date Approved 9/8/2010 John Jasko Rich Trifiletti Oct 5, 2010 John Jasko Sep 28, 2010 Emerson Network Power, Energy Systems, North America, Inc. 4350 Weaver Parkway, Warrenville, IL 60555 Toll Free: 800-800-1280 (USA and Canada) Telephone: 440-246-6999 Fax: 440-246-4876 Web: EmersonNetworkPower.com/EnergySystems EnergyNet: Secure.EmersonNetworkPower.com Page 19 of 19 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.