SAG582140001 SYSTEM OVERVIEW

SAG582140001
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Issue AF, July 14, 2010
Home
SYSTEM OVERVIEW
Description:
-48V DC @ up to 16,800 amperes Power System.
This power system is designed to power a load while charging a positive grounded
battery. This power system is capable of operating in a batteryless installation or off
battery for maintenance purposes. This power system is designed for operation with the
positive output grounded.
The NETSURE™ 801NLDB (208V Input Power Bay), 801NLEB (380V/480V Input Power
Bay), and 801NL-B (Distribution Bay) DC Power System is a complete integrated power
system containing rectifiers, intelligent control, metering, monitoring, and distribution.
This power system consists of the following components.

Power Bays
The system consists of one (1) Primary
Power Bay and up to six (6) Secondary
Power Bays.
Each Power Bay can be equipped with up
to twenty-four (24) Rectifier Modules.
Each Power Bay contains a Monitor and
Control Panel. In the Primary Power Bay,
this panel houses the Meter-ControlAlarm (MCA) assembly. This panel in the
Primary Power Bay also houses the
optional LMS Main CPU circuit card of the
integrated LMS Monitoring System. In a
Secondary Power Bay, this panel can be
equipped with an optional LMS Expansion
CPU circuit card. (The optional LMS
Monitoring System provides a higher level
of monitoring and controlling capabilities
to the power system.)
The Monitor and Control Panel in both
Primary and Secondary Power Bays
contain a seven-slot card cage to house
MCA alarm relay circuit cards, MCA
input/output (I/O) circuit cards, and
optional LMS I/O circuit cards. (If a
Secondary Power Bay is to be equipped
with optional LMS I/O circuit cards, it must
also be equipped with the LMS Expansion
CPU circuit card.)

Distribution Bays
The system consists of one (1) to eight (8)
Distribution Bays.
Each Distribution Bay provides four (4)
distribution buses.
Each distribution bus accepts a choice of
218-type circuit breakers and TPL-type
fuses.
Power Bay
Page 1 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
A Distribution Bay may also be equipped with an optional distribution panel
which accepts a choice of TPS/TLS-type fuseholders or Bullet Nose-type
circuit breakers.

Home
Rectifier Modules
The Rectifier Modules provide load power, battery float current, and battery recharge
current during normal operating conditions.

MCA (Meter-Control-Alarm)
The MCA controls the operation of the Rectifier Modules and provides power system
control, metering, monitoring, and alarm functions.
MCA Local Control Panel: This panel is located on the front of the Primary Power
Bay and contains a keypad, display,
and indicators for local MCA user
interface.
MCA Relay Circuit Card: Each MCA
relay circuit card provides six (6) sets
of Form-C relay contacts for customer
external alarms. These relays are user
programmable for various power
system alarms. Up to sixteen (16)
MCA relay circuit cards can be
installed in the Primary and Secondary
Power Bays. The Primary Power Bay
is factory equipped with two (2) MCA
relay circuit cards.
MCA I/O Circuit Cards: The MCA I/O
circuit cards provide analog
inputs/outputs and binary inputs. Up to
sixteen (16) MCA I/O circuit cards can
be installed in the Primary and
Secondary Power Bays.

Optional Integrated
LMS Monitoring System
The LMS Monitoring System consists
of an LMS Main CPU circuit card,
optional LMS Expansion CPU circuit
cards, optional LMS I/O circuit cards,
optional LMS Expansion Cabinet, and
optional LMS Expansion Assemblies.
The LMS Main CPU circuit card is
mounted in the Primary Power Bay.
Each Secondary Power Bay that is to
be equipped with optional LMS I/O
circuit cards must contain an LMS
Expansion CPU circuit card. LMS
Expansion Cabinets and LMS
Expansion Assemblies are available
that mount into customer racks and
equipment.
The LMS Monitoring System is factory
integrated within each Power Bay, and
Distribution Bay
Page 2 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
requires no additional customer interconnections within the Power Bay.
Simple cable connections between Power and Distribution Bays complete
the interbay connections required. Separate analog, binary, and relay circuit cards
do not have to be supplied for power system monitoring. Analog, binary, relay, and
temperature circuit cards can be provided to monitor equipment external to the power
system.
The LMS input circuit cards monitor a variety of analog, binary, and temperature
points external to the system. An LMS relay output circuit card is also available
which provides programmable relays. These relays may be used for external alarms,
or to control other equipment.
The LMS Monitoring System can be accessed via a local port, a modem port (when
optional modem is ordered), an optional TL1 port, and an Ethernet port (for Telnet
access, optional Web access, optional SNMP access, optional TL1 access, and
Email alarm reporting).
The LMS Monitoring System collects data from the power system and the input circuit
cards monitoring external points. The data collected is used for alarm processing
and reporting, and to provide statistics.
The LMS Monitoring System is capable of reporting alarm conditions to a remote
terminal, pager, Email address, via SNMP traps over Ethernet when the SNMP
option is ordered, or via TL1 (over Ethernet) when the 'TL1 over Ethernet' option is
ordered. TL1 is also available via a serial connection in 'direct mode'. For remote
terminal or pager notification, the LMS Main CPU circuit card must be equipped with
the optional modem. Two types of alarm reporting mechanisms are provided,
System Alarm Reporting and Individual User Alarm Reporting.
Refer to SAG586505000 for further LMS information. The SAG can be accessed via
the CD (Electronic Documentation Package) furnished with your system.

Applications
The NETSURE™ 801NLDB and 801NLEB is capable of interfacing with Vortex® Power
Systems (VPS).
The NETSURE™ 801NLDB and 801NLEB is capable of interfacing with legacy power
systems.
Refer to the wiring diagrams in the Installation Instructions (Section 6016). Refer
also to Lists 64, 65, 66, and 67.
Page 3 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Family:
NETSURE™
Spec. No.:
582140001
Model:
801NLDB (208V Input Power Bay)
801NLEB (380V/480V Input Power Bay)
801NL-B (Distribution Bay)
Input Voltage
Nominal 380/480 volts AC, three phase, 50/60 Hz, with an operating
range of 260 to 530 volts. Acceptable input frequency range is 45 to 65
Hz.
or
Nominal 208 volts AC, three phase, 50/60 Hz, with an operating range of
176 to 264 volts. Acceptable input frequency range is 45 to 65 Hz.
Output Voltage:
-48 Volts DC
Output Capacity:
System:
16,800 Amperes, maximum
(Other configurations are available. For higher amperage configurations,
contact Emerson Network Power.)
2400 Amperes, nominal
100A / -48V
6000 Amperes, maximum
1500 Amperes, maximum
Power Bay:
Rectifier Module:
Distribution Bay:
Distribution Bus:
(four Distribution Buses
per Distribution Bay)
Optional Distribution Panel: 500 Amperes, maximum
(Bullet Nose Circuit
Breakers and/or TLS/TPS
Fuses) (one optional
Distribution Panel per
Distribution Bay)
Agency Approval:
Model 801NL-B (Distribution Bay):
Listed UL 1801, NEBS
Model 801NLEB (Power Bay):
Listed UL 1950, NEBS
Model 801NLDB (Power Bay):
Lists (All):
Lists (0B, 05, 13, 21, 50,
63, 64, 65, 66, 67, 70, 71):
Framework Type:
Power Bay:
Width:
Depth:
Height:
Access:
Distribution Bay:
Width:
Depth:
Height:
Listed UL 1950
NEBS
Seismic Rated (Zone 4) Box Framework
24.375 Inches
30 Inches
84 Inches
Front and Rear Access for Installation and Maintenance, Front for
Operation.
31.375 Inches
30 Inches
84 Inches
Page 4 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Access:
SAG582140001
Issue AF, July 14, 2010
Front and Rear Access for Installation and Maintenance, Front
for Operation.
Home
Maximum Number of
Power Bays per System:
7
Maximum Number of
Distribution Bays per System:
8
Control:
Microprocessor
Color:
Gray
List Options:
380/480VAC Input Option, 208VAC Input Option, Primary Power Bay (2
AC Input Feeds), Primary Power Bay (6, 12 or 24 AC Input Feeds),
Secondary Power Bay (2 AC Input Feeds), Secondary Power Bay (6, 12
or 24 AC Input Feeds), Distribution Bay, Rectifier Module (208V),
Rectifier Module (380/480V), Optional LMS Main CPU Circuit Card
(Primary Power Bay) (Refer to SAG586505000 for additional LMS
options.), Optional LMS Expansion CPU Circuit Card (Secondary Power
Bays), Interface Kit to a 582121900 Power System, Interface Kit to a
582121901 Power System, Interface Kit to a Vortex Power System,
Interface Kit to a Model 1231H Legacy Power System, MCA Alarm Relay
Circuit Card, MCA Analog Input/Output and Binary Input Circuit Card,
(24) Position Bullet-Nose Circuit Breaker/Fuse Panel
Accessory Options:
Seismic Anchor Kit, Seismic Anchor Isolation Kit, Main Battery
Termination Bars (MBTB’s), Distribution Devices, Wiring Components,
Battery Charge Temperature Compensation Probe, Replacement MCA
Network Cable, Replacement LMS Network Cable, Replacement
Modules and Circuit Cards
Environment:
0C to +40C (+32F to +104F)
Configurations:
Plant is designed for centralized configuration with customer supplied
Main Battery Termination Bars (MBTB’s). Emerson Network Power
Services has standard MBTB’S in 4000, 6000, 10000, and 16000
ampere capacities. The ultimate plant capacity is determined by the
capacity of the MBTB’S.
Plant can be configured for distributed applications by bay-to-bay cabling
up to 9600 amperes.
Page 5 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
582140001
Power Bays
List 0A: 380/480VAC
Plant Input
List 04: Primary Power Bay
(2 AC Input Feeds)
(Includes Circuit
Breakers, One per Two
Rectifier Modules)
List 0B: 208VAC Plant
Input
List 05: Primary Power Bay
(12 or 24 AC Input
Feeds)
AC Input Termination Panel
and Optional AC Input
Breakers
List 06: Primary Power Bay
(6 Input Feeds)
480V only.
List 12: Secondary Power Bay
(2 AC Input Feeds)
(Includes Circuit
Breakers, One per Two
Rectifier Modules)
(see Monitor and
Control Diagram)
List 13: Secondary Power Bay
(12 or 24 AC Input
Feeds)
List 14: Secondary Power Bay
(6 Input Feeds)
480V only.
Rectifier Module
Mounting Positions
See Also
System Overview
Table of Contents
Ordering Information
List Descriptions
Accessory Descriptions
Specifications
Physical Size Information
Related Documentation
List 21: Rectifier Module
(208VAC Input)
List 22: Rectifier Module
(380/480VAC
Input)
Front View
Page 6 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
582140001
Distribution Bays
List 16: Distribution Bay
Blank Panel
or
List 0C: Bullet
Fuse/Circuit
Breaker Panel
Distribution Bus
(see Distribution
Devices in
ACCESSORY
DESCRIPTIONS
Section for
distribution
options)
Distribution Bus
(see Distribution
Devices in
ACCESSORY
DESCRIPTIONS
Section for
distribution
options)
(see Monitor and
Control Diagram)
Distribution Bus
(see Distribution
Devices in
ACCESSORY
DESCRIPTIONS
Section for
distribution
options)
Distribution Bus
(see Distribution
Devices in
ACCESSORY
DESCRIPTIONS
Section for
distribution
options)
Front door removed in
illustration for clarity.
Front View
Page 7 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
582140001
Power Bays Monitor and Control Diagram
Battery Charge Temperature
Compensation Probe Connector
P/O List 4 and 5:
MCA Circuit Card
(Primary Bay)
P/O List 12 and 13: ROUTER Circuit Card
(Secondary Bay)
Front View
List 50: Optional LMS Main CPU
Circuit Card
or
List 63: Optional LMS Expansion
CPU Circuit Card
Available MCA Input/Output (I/O)
Circuit Cards
List 70: MCA Customer Alarm
Relay Circuit Card (Six [6]
Form-C Contacts)
Refer to SAG586505000
for additional LMS options.
List 71: MCA Analog Input/Output
and Binary Input Circuit
Card
582140001
Distribution Bays Monitor and Control Diagram
P/O Lists 16:
ROUTER Circuit Card
Page 8 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
TABLE OF CONTENTS
Ordering Information
System
Overview
Picture
List
Descriptions
Accessory
Descriptions
Specifications
Physical Size
Information
Related
Documentation
SYSTEM OVERVIEW.................................................................................................................................................1
582140001 Power Bays .......................................................................................................................................6
582140001 Distribution Bays..............................................................................................................................7
582140001 Power Bays Monitor and Control Diagram ....................................................................................8
582140001 Distribution Bays Monitor and Control Diagram ..........................................................................8
TABLE OF CONTENTS.............................................................................................................................................9
ORDERING INFORMATION....................................................................................................................................11
List Options........................................................................................................................................................11
Accessory Options............................................................................................................................................13
LIST DESCRIPTIONS ..............................................................................................................................................14
List 0A: 380/480VAC Plant Input Voltage .....................................................................................................14
List 0B: 208VAC Plant Input Voltage ............................................................................................................14
List 04: Primary Power Bay (2 AC Input Feeds) ...........................................................................................14
List 05: Primary Power Bay (12 or 24 AC Input Feeds) ................................................................................15
List 06: Primary Power Bay (6 AC Input Feeds) ...........................................................................................16
List 12: Secondary Power Bay (2 AC Input Feeds) ......................................................................................17
List 13: Secondary Power Bay (12 or 24 AC Input Feeds) ...........................................................................18
List 14: Secondary Power Bay (6 AC Input Feeds) ......................................................................................19
List 16: Distribution Bay ................................................................................................................................20
List 21: Rectifier Module, 208V Input ............................................................................................................20
List 22: Rectifier Module, 380/480V Input .....................................................................................................20
List 50: Optional LMS Main CPU Circuit Card (Primary Power Bay)............................................................21
List 63: Optional LMS Expansion CPU Circuit Card (Secondary Power Bays) ............................................21
List 64: Interface Kit to a Spec. No. 582121900 Power System equipped with a DGU................................21
List 65: Interface Kit to a Spec. No. 582121901 Power System equipped with an LMS1000 ......................22
List 66: Interface Kit to a Vortex Power System without a DGU or LMS1000 ..............................................22
List 67: Interface Kit to a Model 1231H Legacy Power System with 1-8 Rectifiers ......................................23
List 70: Additional MCA Six (6) Output Form-C Relay Circuit Card..............................................................23
List 71: MCA I/O Circuit Card P/N 524550....................................................................................................23
List 0C: 24 Position Bullet-Nose Circuit Breaker/Fuse Panel .......................................................................25
ACCESSORY DESCRIPTIONS...............................................................................................................................26
Seismic Anchor Kit, P/N 545387 ......................................................................................................................26
Seismic Anchor Isolation Kit, P/N 545388 ......................................................................................................26
Main Battery Termination Bars (MBTB’s) .......................................................................................................26
Distribution Device and Load Lug Locations.................................................................................................26
Distribution Devices..........................................................................................................................................30
218 Circuit Breaker Assemblies .....................................................................................................................30
TPL Fuses and Fuseholder Assemblies ........................................................................................................34
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses .......................37
Optional Bullet Nose-Type 10-Position GMT Fuse Module for List C............................................................41
Replacement Alarm, Reference, and Control Fuses......................................................................................42
Fuseblock Located in Bay’s Left Center ........................................................................................................42
Input and Alarm Fuse on Optional Bullet Nose-Type 10-Position GMT Fuse Module, P/N 509128 .............43
Wiring Components ..........................................................................................................................................44
Page 9 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Load Distribution Wire Sizes and Lugs Selection (Distribution Bay) .............................................................44
Power Bay DC Output Cable Sizes and Lugs Selection................................................................................48
Distribution Bay DC Input Cable Sizes and Lugs Selection...........................................................................50
Power Bay Frame Grounding Wire Sizes and Lugs Selection ......................................................................52
Distribution Bay Frame Grounding Wire Sizes and Lugs Selection...............................................................53
AC Input (12 or 24 AC Input Feeds) Wire and Conduit Sizes, Branch Circuit Protection, and Lugs
Selection Lists 5 and 13 .................................................................................................................................54
AC Input (6 AC Input Feeds) Wire and Conduit Sizes, Branch Circuit Protection, and Lugs
Selection Lists 6 and 14 .................................................................................................................................57
AC Input (2 AC Input Feeds) Wire and Conduit Sizes, Branch Circuit Protection, and Lugs
Selection Lists 4 and 12 ................................................................................................................................63
External Alarm, Reference, and Control Wire Sizes - Power Bays ...............................................................66
Optional Battery Charge Temperature Compensation Probe for Digital Compensation...........................67
Replacement/Additional MCA Network Cable ................................................................................................68
Replacement/Additional LMS Network Cable.................................................................................................68
Replacement Modules and Circuit Cards .......................................................................................................69
SPECIFICATIONS....................................................................................................................................................70
1. System ...........................................................................................................................................................70
1.1 DC Operating Voltage ..............................................................................................................................70
1.2 Environmental Ratings .............................................................................................................................70
1.3 Compliance Information ...........................................................................................................................71
1.4 Local Controls and Indicators...................................................................................................................71
2. Distribution Bay ............................................................................................................................................72
2.1 DC Ratings ...............................................................................................................................................72
3. Rectifier Module (Model R48-5800, Spec. No. 1R485800) .........................................................................72
3.1 DC Output Ratings ...................................................................................................................................72
3.2 AC Input Ratings ......................................................................................................................................75
3.3 Environmental Ratings .............................................................................................................................76
3.4 Standard Features....................................................................................................................................78
4. Rectifier Module (Model R48-5800L, Spec. No. 1R485800L).....................................................................83
4.1 DC Output Ratings ...................................................................................................................................83
4.2 AC Input Ratings ......................................................................................................................................86
4.3 Environmental Ratings .............................................................................................................................87
4.4 Standard Features....................................................................................................................................89
5. MCA ................................................................................................................................................................94
5.1 Standard Features....................................................................................................................................94
6. Optional LMS Monitoring System .............................................................................................................105
PHYSICAL SIZE INFORMATION ..........................................................................................................................106
Floor Hole Drilling Pattern Dimensions - Power Bays.................................................................................106
Floor Hole Drilling Pattern Dimensions - Distribution Bays .......................................................................106
Overall Dimensions - Primary and Secondary Power Bays........................................................................107
Overall Dimensions - Distribution Bays........................................................................................................108
Overall Dimensions – Optional Battery Charge Digital Temperature Compensation Probes P/N
107021 (25 feet) and P/N 106824 (100 feet) ...................................................................................................109
RELATED DOCUMENTATION..............................................................................................................................110
REVISION RECORD ..............................................................................................................................................111
Page 10 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
ORDERING INFORMATION
List Options
Order the following by the items Part Number as specified in the following table.
When viewing electronically, click on the link to jump to the detailed description page.
List
Number
Part
Number
0A
5821400010A
Specifies 380/480VAC Plant Input.
0B
5821400010B
Specifies 208VAC Plant Input.
04
58214000104
One (1) 2400A Primary Power Bay
(2 AC Input Feeds).
Note: Expands both left and right.
Includes Circuit Breakers (One per Two Rectifier Modules).
05
58214000105
One (1) 2400A Primary Power Bay
(12 or 24 AC Input Feeds).
Note: Expands both left and right.
06
58214000112
One (1) 2400A Primary Power Bay
(6 AC Input Feeds).
58214000112
One (1) 2400A Secondary Power Bay
(2 AC Input Feeds).
Note: Expands both left and right.
Includes Circuit Breakers (One per Two Rectifier Modules).
Expansion to List 4.
13
58214000113
One (1) 2400A Secondary Power Bay
(12 or 24 AC Input Feeds).
Note: Expands both left and right.
Expansion to List 5.
14
58214000113
One (1) 2400A Secondary Power Bay
(6 AC Input Feeds).
16
58214000116
One (1) 6000A Distribution Bay.
Note: Expands both left and right.
21
58214000121
Model R48-5800L Rectifier Module (100A), 208VAC Input
22
58214000122
Model R48-5800 Rectifier Module (100A), 380/480VAC Input
50
58214000150
Optional LMS Main CPU Circuit Card (Primary Power Bay)
63
58214000163
Optional LMS Expansion CPU Circuit Card (Secondary Power Bays)
64
58214000164
Interface Kit to a Spec. No. 582121900 Power System equipped with a DGU
65
58214000165
Interface Kit to a Spec. No. 582121901 Power System equipped with an
LMS1000
66
58214000166
Interface Kit to a Vortex Power System without a DGU or LMS1000
67
58214000167
Interface Kit to a Model 1231H Legacy Power System with 1-8 Rectifiers
70
58214000170
Optional MCA Customer Alarm Relay Circuit Card (6 Form-C Contacts)
71
58214000171
Optional MCA Analog Input/Output and Binary Input Circuit Card
12
Description
Page 11 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
List
Number
0C
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Part
Number
Description
5821400010C
24 Position Bullet-Nose Circuit Breaker/Fuse Panel.
(One per List 16) (The List C Circuit Breaker/Fuse Panel requires distribution
position #12 in the Bus #1 Distribution Panel. Also, distribution position #36 in
the Bus #3 Distribution Panel must remain empty.)
When installed, bay can be loaded with up to (46) 218 Circuit Breakers or TPL
Fuses, and (24) Bullet Nose Circuit Breakers or TLS/TPS Fuses.
Page 12 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Accessory Options
Order the following by the items Part Number as specified in the following table.
When viewing electronically, click on the link to jump to the detailed description page.
Description
Part Number
Seismic Anchor Kit
Seismic Anchor Isolation Kit
Main Battery Termination Bars (MBTB’s)
218 Circuit Breaker Assemblies
TPL Fuses and Fuseholder Assemblies
Bullet Nose-Type Circuit Breakers and
Bullet Nose-Type Fuseholders with TLS/TPS Fuses
Optional Bullet Nose-Type 10-Position GMT Fuse Module for List C
See ACCESSORY
DESCRIPTIONS
Section
Replacement Alarm, Reference, and Control Fuses
Wiring Components
Optional Battery Charge Temperature Compensation Probe
Replacement/Additional MCA Network Cables
Replacement/Additional LMS Network Cables
Page 13 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
LIST DESCRIPTIONS
List 0A: 380/480VAC Plant Input Voltage
Features

Specifies 380/480VAC Plant Input Voltage.
List 0B: 208VAC Plant Input Voltage
Features

Specifies 208VAC Plant Input Voltage.
List 04: Primary Power Bay (2 AC Input Feeds)
Features

Provides common equipment for one (1) Power Bay rated for up to 2400 amperes.

Mounted in a 7'0"H x 24.375"W x 30"D seismic rated (Zone 4) box framework.

Provides twenty-four (24) Rectifier Module mounting positions.

Provides an AC input termination panel that accepts two (2) AC input branch circuits, one (1) per twelve
(12) Rectifier Module mounting positions. A 60A AC input circuit breaker rated for 65kA interrupting
capacity is provided for each pair of rectifier positions in the List B Bay. A 30A AC input circuit breaker
rated for 22kA interrupting capacity is provided for each pair of rectifier positions in the List A Bay.

Provides the MCA Assembly and Local MCA Control Panel.

Provides mounting for optional LMS Main CPU circuit card.

Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards. Two (2) MCA customer alarm relay circuit cards furnished,
providing twelve (12) Form-C relay contacts

Side cover panels are factory installed on both sides of the bay.
Restrictions
Only one (1) Primary Bay per power system required.
Ordering Notes
1) Specify List A (380/480VAC Input) or List B (208VAC Input).
2) Order up to twenty-four (24) Rectifiers Modules per bay per List 21 (208VAC Input) or List 22
(380/480VAC Input).
3) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
4) Order a Battery Charge Temperature Compensation Probe as required per Optional Battery Charge
Temperature Compensation Probe for Digital Compensation in the ACCESSORY DESCRIPTIONS
section.
5) Order optional LMS Monitor and LMS options as required per List 50, and SAG586505000.
6) Order “Power Bay DC Output” lugs as required per Power Bay DC Output Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
7) Order “AC Input” lugs as required per AC Input (Dual AC Input Feeds) Wire and Conduit Sizes, Branch
Circuit Protection, and Lugs Selection in the ACCESSORY DESCRIPTIONS section.
Page 14 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
8) Order “Power Bay Frame Grounding” lugs as required per Power Bay Frame Grounding Wire
Sizes and Lugs Selection in the ACCESSORY DESCRIPTIONS section.
Home
9) If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.
List 05: Primary Power Bay (12 or 24 AC Input Feeds)
Features

Provides common equipment for one (1) Power Bay rated for up to 2400 amperes.

Mounted in a 7'0"H x 24.375"W x 30"D seismic rated (Zone 4) box framework.

Provides twenty-four (24) Rectifier Module mounting positions.

Provides an AC input termination panel that accepts twenty-four (24) AC input branch circuits [one (1) per
Rectifier Module mounting position] or twelve (12) AC input branch circuits [one (1) per two Rectifier
Module mounting positions]. The bay ships with the 12 Feed option installed.

Provides the MCA Assembly and Local MCA Control Panel.

Provides mounting for optional LMS Main CPU circuit card.

Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards. Two (2) MCA customer alarm relay circuit cards furnished,
providing twelve (12) Form-C relay contacts.

Side cover panels are factory installed on both sides of the bay.
Restrictions
Only one (1) Primary Bay per power system required.
Ordering Notes
10) Specify List A (380/480VAC Input) or List B (208VAC Input).
11) Order up to twenty-four (24) Rectifiers Modules per bay per List 21 (208VAC Input) or List 22
(380/480VAC Input).
12) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
13) Order a Battery Charge Temperature Compensation Probe as required per Optional Battery Charge
Temperature Compensation Probe for Digital Compensation in the ACCESSORY DESCRIPTIONS
section.
14) Order optional LMS Monitor and LMS options as required per List 50, and SAG586505000.
15) Order “Power Bay DC Output” lugs as required per Power Bay DC Output Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
16) Order “AC Input Ground” lugs as required per AC Input (Individual/Twin AC Input Feeds) Wire and
Conduit Sizes, Branch Circuit Protection, and Lugs Selection in the ACCESSORY DESCRIPTIONS
section.
17) Order “Power Bay Frame Grounding” lugs as required per Power Bay Frame Grounding Wire Sizes and
Lugs Selection in the ACCESSORY DESCRIPTIONS section.
18) If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.
Page 15 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
List 06: Primary Power Bay (6 AC Input Feeds)
Home
Features

Provides common equipment for one (1) Power Bay rated for up to 2400 amperes.

Mounted in a 7'0"H x 24.375"W x 30"D seismic rated (Zone 4) box framework.

Provides twenty-four (24) Rectifier Module mounting positions.

Provides an AC input termination panel that accepts six (6) AC input branch circuits [one (1) per four
Rectifier Module mounting positions].

Provides the MCA Assembly and Local MCA Control Panel.

Provides mounting for optional LMS Main CPU circuit card.

Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards. Two (2) MCA customer alarm relay circuit cards furnished,
providing twelve (12) Form-C relay contacts.

Side cover panels are factory installed on both sides of the bay.
Restrictions
Only one (1) Primary Bay per power system required. 480V only.
Ordering Notes
1) Specify List A (480VAC Input).
2) Order up to twenty-four (24) Rectifiers Modules per bay per List 22 (380/480VAC Input).
3) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
4) Order a Battery Charge Temperature Compensation Probe as required per Optional Battery Charge
Temperature Compensation Probe for Digital Compensation in the ACCESSORY DESCRIPTIONS
section.
5) Order optional LMS Monitor and LMS options as required per List 50, and SAG586505000.
6) Order “Power Bay DC Output” lugs as required per Power Bay DC Output Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
7) Order “AC Input Ground” lugs as required per AC Input Wire and Conduit Sizes, Branch Circuit
Protection, and Lugs Selection in the ACCESSORY DESCRIPTIONS section.
8) Order “Power Bay Frame Grounding” lugs as required per Power Bay Frame Grounding Wire Sizes and
Lugs Selection in the ACCESSORY DESCRIPTIONS section.
9) If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.
Page 16 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
List 12: Secondary Power Bay (2 AC Input Feeds)
Home
Features

Provides common equipment for one (1) Power Bay rated for up to 2400 amperes.

Mounted in a 7'0"H x 24.375"W x 30"D seismic rated (Zone 4) box framework.

Provides twenty-four (24) Rectifier Module mounting positions.

Provides an AC input termination panel that accepts two (2) AC input branch circuits, one (1) per twelve
(12) Rectifier Module mounting positions. A 60A AC input circuit breaker rated for 65kA interrupting
capacity is provided for each pair of rectifier positions in the List B Bay. A 30A AC input circuit breaker
rated for 22kA interrupting capacity is provided for each pair of rectifier positions in the List A Bay.

Includes a Router Assembly for bay communication to the MCA in the Primary Power Bay.

Provides mounting for optional LMS Expansion CPU circuit card.

Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards.

MCA Network bay interconnect cable provided (Qty. 1 P/N 514642).
Ordering Notes
1) Specify List A (380/480VAC Input) or List B (208VAC Input).
2) Order up to twenty-four (24) Rectifiers Modules per bay per List 21 (208VAC Input) or List 22
(380/480VAC Input).
3) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
4) Order optional LMS Expansion CPU circuit card and LMS options as required per List 63, and
SAG586505000. Also order additional LMS Network cables as required per Replacement/Additional LMS
Network Cables.
5) Order “Power Bay DC Output” lugs as required per Power Bay DC Output Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
6) Order “AC Input” lugs as required per AC Input (Dual AC Input Feeds) Wire and Conduit Sizes, Branch
Circuit Protection, and Lugs Selection in the ACCESSORY DESCRIPTIONS section.
7) Order “Power Bay Frame Grounding” lugs as required per Power Bay Frame Grounding Wire Sizes and
Lugs Selection in the ACCESSORY DESCRIPTIONS section.
8) If a different length LMS and/or MCA Network cable is required, order per Replacement/Additional LMS
Network Cables and/or Replacement/Additional MCA Network Cables. Refer to the Installation
Instructions (Section 6016) for Network cabling requirements.
9) Side cover panels are not provided. When bays are placed next to each other, the side cover panels
from the ‘inside’ side of the Primary Power Bay are moved to the ‘outside’ side of the last Secondary
Power Bay. In installations where a Secondary Power Bay is placed by itself, order (4) P/N 535092 side
cover panels.
Page 17 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
List 13: Secondary Power Bay (12 or 24 AC Input Feeds)
Home
Features

Provides common equipment for one (1) Power Bay rated for up to 2400 amperes.

Mounted in a 7'0"H x 24.375"W x 30"D seismic rated (Zone 4) box framework.

Provides twenty-four (24) Rectifier Module mounting positions.

Provides an AC input termination panel that accepts twenty-four (24) AC input branch circuits [one (1) per
Rectifier Module mounting position] or twelve (12) AC input branch circuits [one (1) per two Rectifier
Module mounting positions]. The bay ships with the 12 Feed option installed.

Includes a Router Assembly for bay communication to the MCA in the Primary Power Bay.

Provides mounting for optional LMS Expansion CPU circuit card.

Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards.

MCA Network bay interconnect cable provided (Qty. 1 P/N 514642).
Ordering Notes
1) Specify List A (380/480VAC Input) or List B (208VAC Input).
2) Order up to twenty-four (24) Rectifiers Modules per bay per List 21 (208VAC Input) or List 22
(380/480VAC Input).
3) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
4) Order optional LMS Expansion CPU circuit card and LMS options as required per List 63, and
SAG586505000. Also order additional LMS Network cables as required per Replacement/Additional LMS
Network Cables.
5) Order “Power Bay DC Output” lugs as required per Power Bay DC Output Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
6) Order “AC Input Ground” lugs as required per AC Input (Individual/Twin AC Input Feeds) Wire and
Conduit Sizes, Branch Circuit Protection, and Lugs Selection in the ACCESSORY DESCRIPTIONS
section.
7) Order “Power Bay Frame Grounding” lugs as required per Power Bay Frame Grounding Wire Sizes and
Lugs Selection in the ACCESSORY DESCRIPTIONS section.
8) If a different length LMS and/or MCA Network cable is required, order per Replacement/Additional LMS
Network Cables and/or Replacement/Additional MCA Network Cables. Refer to the Installation
Instructions (Section 6016) for Network cabling requirements.
9) Side cover panels are not provided. When bays are placed next to each other, the side cover panels
from the ‘inside’ side of the Primary Power Bay are moved to the ‘outside’ side of the last Secondary
Power Bay. In installations where a Secondary Power Bay is placed by itself, order (4) P/N 535092 side
cover panels.
Page 18 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
List 14: Secondary Power Bay (6 AC Input Feeds)
Home
Features

Provides common equipment for one (1) Power Bay rated for up to 2400 amperes.

Mounted in a 7'0"H x 24.375"W x 30"D seismic rated (Zone 4) box framework.

Provides twenty-four (24) Rectifier Module mounting positions.

Provides an AC input termination panel that accepts six (6) AC input branch circuits [one (1) per four
Rectifier Module mounting positions].

Includes a Router Assembly for bay communication to the MCA in the Primary Power Bay.

Provides mounting for optional LMS Expansion CPU circuit card.

Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards.

MCA Network bay interconnect cable provided (Qty. 1 P/N 514642).
Restrictions
480V only.
Ordering Notes
1) Specify List A (480VAC Input).
2) Order up to twenty-four (24) Rectifiers Modules per bay per List 21 (208VAC Input) or List 22
(380/480VAC Input).
3) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
4) Order optional LMS Expansion CPU circuit card and LMS options as required per List 63, and
SAG586505000. Also order additional LMS Network cables as required per Replacement/Additional LMS
Network Cables.
5) Order “Power Bay DC Output” lugs as required per Power Bay DC Output Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
6) Order “AC Input Ground” lugs as required per AC Input (Individual/Twin AC Input Feeds) Wire and
Conduit Sizes, Branch Circuit Protection, and Lugs Selection in the ACCESSORY DESCRIPTIONS
section.
7) Order “Power Bay Frame Grounding” lugs as required per Power Bay Frame Grounding Wire Sizes and
Lugs Selection in the ACCESSORY DESCRIPTIONS section.
8) If a different length LMS and/or MCA Network cable is required, order per Replacement/Additional LMS
Network Cables and/or Replacement/Additional MCA Network Cables. Refer to the Installation
Instructions (Section 6016) for Network cabling requirements.
9) Side cover panels are not provided. When bays are placed next to each other, the side cover panels
from the ‘inside’ side of the Primary Power Bay are moved to the ‘outside’ side of the last Secondary
Power Bay. In installations where a Secondary Power Bay is placed by itself, order (4) P/N 535092 side
cover panels.
Page 19 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
List 16: Distribution Bay
Features

Provides common equipment for one (1) Distribution Bay rated for up to 6000 amperes.

Mounted in a 7'0"H x 31.375"W x 30"D seismic rated (Zone 4) box framework.

Provides forty-eight (48) distribution device mounting positions.

Provides four (4) buses of distribution. Each bus contains an MCA monitoring circuit card; which can be
set for no group designation, Group A designation, or Group B designation.

Includes a Router Assembly for bay communication to the MCA in the Primary Power Bay.

MCA Network bay interconnect cable provided (P/N 514644).
Ordering Notes
1) Order distribution fuse and/or circuit breaker devices as required per Distribution Devices in the
ACCESSORY DESCRIPTIONS section.
2) Order load distribution lugs as required per Load Distribution Wire Sizes and Lugs Selection (Distribution
Bay) in the ACCESSORY DESCRIPTIONS section.
3) Order “Distribution Bay DC Input” lugs as required per Distribution Bay DC Input Cable Sizes and Lugs
Selection in the ACCESSORY DESCRIPTIONS section.
4) Order “Distribution Bay Frame Grounding” lugs as required per Distribution Bay Frame Grounding Wire
Sizes and Lugs Selection in the ACCESSORY DESCRIPTIONS section.
5) Order one (1) “Twenty-Four (24) Position Bullet-Nose Circuit Breaker/Fuse Panel” per Distribution Bay as
required per List C.
6) If a different length MCA Network cable is required, order per Replacement/Additional MCA Network
Cables. Refer to the Installation Instructions (Section 6016) for Network cabling requirements.
7) Side cover panels are factory installed on one side of the bay. In installations where a Distribution Bay is
placed by itself, order (2) P/N 528633 side cover panels for the other side.
List 21: Rectifier Module, 208V Input
Features

Model R48-5800L, Spec. No. 1R485800L, 100A / 48 volt rectifier module.
Restrictions
For use in List B bays only.
Ordering Notes
1) Order List 21 Rectifier Modules as required. Each Power Bay holds up to twenty-four (24) Rectifier
Modules.
List 22: Rectifier Module, 380/480V Input
Features

Model R48-5800, Spec. No. 1R485800, 100A / 48 volt rectifier module.
Restrictions
For use in List A bays only.
Page 20 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Ordering Notes
1) Order List 22 Rectifier Modules as required. Each Power Bay holds up to twenty-four (24) Rectifier
Modules.
List 50: Optional LMS Main CPU Circuit Card (Primary Power Bay)
Features

Provides the LMS Monitoring System.

Refer to SAG586505000 for further information.
Restrictions
The LMS Monitoring System Main CPU circuit card is mounted in the Primary Power Bay only.
Ordering Notes
1) Order the optional LMS Monitor if increased monitoring capabilities are required. Order the LMS Main
CPU circuit card (List 50) for the Primary Power Bay. Order the LMS Expansion CPU circuit card (List 63)
for Secondary Power Bays that are to be equipped with LMS I/O circuit cards.
2) Order additional LMS Network cables as required per Replacement/Additional LMS Network Cables.
Note that an LMS Network cable is factory provided with List 63.
3) This List option only provides the LMS CPU circuit card for the Primary Power Bay, additional LMS
options must be ordered separately per SAG586505000.
List 63: Optional LMS Expansion CPU Circuit Card (Secondary Power Bays)
Features

Allows LMS I/O cards to be installed in Secondary Power Bays.

LMS Network bay interconnect cable provided (Qty. 1 P/N 514639).
Restrictions
The LMS Monitoring System Expansion CPU circuit cards are mounted in Secondary Power Bays (required
only if LMS I/O circuit cards are to be installed in the same bay).
Ordering Notes
1) Order the LMS Expansion CPU circuit card for Secondary Power Bays that are to be equipped with LMS
I/O circuit cards.
List 64: Interface Kit to a Spec. No. 582121900 Power System equipped with a DGU
Features

Provides the following...
LMS Dual MCA Interface Software Option
LMS Gateway Software Option
P/N 526843 50’ LMS Dual MCA Option Cable
P/N 545783 50’ LMS Gateway Port Null Modem Cable

LMS Dual MCA Interface Software Option enables the Spec. No. 582140001 Power System to be
integrated with an existing Power System. Specifically, List 64 allows the MCA in Spec. No. 582140001
to interface with the MCA in a Spec. No. 582121900 via the LMS in Spec. No. 582140001. Refer to the
LMS documentation for further information.
Page 21 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010

System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
LMS Gateway Software Option allows the LMS to emulate a “dumb” RS-232 asynchronous
terminal interface. Specifically, List 64 enables user input through either a local or remote LMS
port to be directed to a DGU connected to the LMS Gateway port. Refer to the LMS documentation for
further information.
Restrictions
Operation of Energy Management is disabled with this option installed.
The Gateway port is provided via the port located on the front of the LMS CPU circuit card installed in the
Spec. No. 582140001 Primary Bay.
Ordering Notes
1) Order as required.
List 65: Interface Kit to a Spec. No. 582121901 Power System equipped with an LMS1000
Features

Provides the following...
LMS Dual MCA Interface Software Option
P/N 506153 LMS Expansion CPU Card
P/N 514641 150’ Echelon Cable
P/N 526843 50’ LMS Dual MCA Option Cable

LMS Dual MCA Interface Software Option enables the Spec. No. 582140001 Power System to be
integrated with an existing Power System. Specifically, List 65 allows the MCA in Spec. No. 582140001
to interface with the MCA in Spec. No. 582121901 via the LMS in Spec. No. 582140001. Refer to the
LMS documentation for further information.
Restrictions
Operation of Energy Management is disabled with this option installed.
The Main LMS CPU card in 582121901 must be replaced with the Expansion LMS CPU card (P/N 506153)
provided with List 65.
Ordering Notes
1) Order as required.
List 66: Interface Kit to a Vortex Power System without a DGU or LMS1000
Features

Provides the following...
LMS Dual MCA Interface Software Option
P/N 526843 50’ LMS Dual MCA Option Cable

LMS Dual MCA Interface Software Option enables the Spec. No. 582140001 Power System to be
integrated with an existing Power System. Specifically, List 66 allows the MCA in Spec. No. 582140001
to interface with the MCA in a Vortex Power System via the LMS in Spec. No. 582140001. Refer to the
LMS documentation for further information.
Restrictions
Operation of Energy Management is disabled with this option installed.
Ordering Notes
1) Order as required.
Page 22 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
List 67: Interface Kit to a Model 1231H Legacy Power System with 1-8 Rectifiers
Features

Provides the following...
LMS Gateway Software Option
P/N 545783 50’ LMS Gateway Port Null Modem Cable
Two (2) P/N 506336 LMS 4-Input Universal Analog Cards
One (1) P/N 506334 LMS 8-Input Binary Card

LMS Gateway Software Option allows the LMS to emulate a “dumb” RS-232 asynchronous terminal
interface. Specifically, List 67 enables user input through either a local or remote LMS port to be directed
to a DGU (in the legacy plant) connected to the LMS Gateway port. Refer to the LMS documentation for
further information.

The analog and binary DGU I/O cards provide monitoring of the legacy system’s rectifiers
Restrictions
LMS Channels must be configured.
Ordering Notes
1) Order as required.
List 70: Additional MCA Six (6) Output Form-C Relay Circuit Card
Features

Provides six relays each with one set of Form-C relay contacts.

These relays are used for alarm applications and can be programmed by the user.

Refer to the "Specifications" section of this document for further information.

Plugs into any slot in 7-position card cage in Primary and Secondary Power Bays.

User maps relay closure to any or multiple programmable alarm functions.
Restrictions
Relay contacts rated for 2A at 30 volts DC.
The system may contain up to 16 MCA Relay circuit cards.
Ordering Notes
1) Order one (1) List 70 relay circuit card for every six (6) customer relay contacts to be provided by the
MCA.
List 71: MCA I/O Circuit Card P/N 524550
Features

Provides 1 analog input, 1 analog output (for remote plant output current monitoring), and 4 binary inputs.

Refer to the "Specifications" section of this document for further information.

Plugs into any slot in 7-position card cage in Primary and Secondary Power Bays.
Restrictions
The system may contain up to 16 MCA I/O circuit cards.
Page 23 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Only one (1) P/N 524550 card can be installed per bay.
Analog input and output rating = 0-50mv DC.
Binary input rating = dry contact.
Analog inputs should be protected by a 49.9 ohm resistor.
Recommended to use current limiting resistors to protect binary input wiring.
Ordering Notes
1) Order optional MCA I/O circuit cards as required.
2) Use of the “Alternate Current Limit” feature requires that an MCA I/O circuit card be installed.
Page 24 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
List 0C: 24 Position Bullet-Nose Circuit Breaker/Fuse Panel
Home
Features

Provides twenty-four (24) Bullet
Nose Device positions.

Accepts a choice of TLS/TPS-type
fuseholders, Bullet Nose-Type
circuit breakers, or Bullet NoseType GMT Fuse Modules.

The List C Fuse/Circuit Breaker
Panel is equipped with one (1)
shunt for all distribution positions for
MCA load current measurements.

Optional List C
Bullet Nose Device Panel
Refer also to Bullet Nose-Type
Circuit Breakers and Bullet NoseType Fuseholders e/w TLS/TPS
Fuses and Optional Bullet NoseType 10-Position GMT Fuse
Module for List C.
Restrictions
Each Distribution Bay can be equipped
with only one (1) List C panel.
The List C Circuit Breaker/Fuse Panel
requires distribution position #12 in the
Bus #1 Distribution Panel. Also,
distribution position #36 in the Bus #3
Distribution Panel must remain empty.
Front door removed in
illustration for clarity.
Current monitoring for the List C Fuse/Circuit Breaker Panel is for the complete panel. Circuit Breakers
and/or fuses are not individually monitored.
When installed, bay can be loaded with up to (46) 218 Circuit Breakers or TPL Fuses, and (24) Bullet Nose
Circuit Breakers or TLS/TPS Fuses.
The List C Circuit Breaker/Fuse Panel is rated for a maximum continuous load of 500 amps.
The total load combination of List C and Distribution Panel #1 cannot exceed 1500A.
Ordering Notes
1) Order as required.
2) Also order distribution fuses, circuit breakers, and/or Bullet Nose-Type 10-Position GMT Fuse Modules as
required per Distribution Devices in the ACCESSORY DESCRIPTIONS section.
Page 25 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
ACCESSORY DESCRIPTIONS
Seismic Anchor Kit, P/N 545387
Features
Provides four (4) Relay Rack Seismic Mounting Anchors, P/N 216821200.
Ordering Notes
1) Order Seismic Anchor Kit, P/N 545387, as required.
Seismic Anchor Isolation Kit, P/N 545388
Features
Provides four (4) bushings, P/N 124866 (one per seismic anchor) and one (1) insulator, P/N 112490.
Ordering Notes
1) Order Seismic Isolation Anchor Kit, P/N 545388, as required.
Main Battery Termination Bars (MBTB’s)
Plant is designed for centralized configuration with customer supplied Main Battery Termination Bars
(MBTB’s). Emerson Network Power Services has standard MBTB’S in 4000, 6000, 10000, and 16000
ampere capacities. The ultimate plant capacity is determined by the capacity of the MBTB’S. Refer to the
EA3434-41xx Series MBTB’s drawings.
Distribution Device and Load Lug Locations
Each Distribution Bay has four (4) distribution buses. Each distribution bus has twelve (12) fuse/circuit
breaker device mounting positions. Note that the various fuse/circuit breaker devices require different number
of mounting positions, as detailed in the following sections. Note also that each distribution bus is divided into
half, and each half MUST be populated with distribution devices as shown in the following illustration, without
skipping any distribution device mounting positions within each half. This allows automatic monitoring of each
position and allows the controller to located all distribution positions. The load side of each fuse/circuit
breaker mounting position is bused to the rear of the bay. Each fuse/circuit breaker device requires a load lug
adapter plate kit that mounts to the appropriate load side busbars at the rear of the bay (except 1-pole
devices). Load return leads are terminated outside the bay to customer provided return busbars.
Page 26 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
13
Top Half 12
Bus #1
Distribution Device
Mounting Location
Bottom Half
Bottom Half
Bus #2
Distribution Device
Mounting Location
7
6
18
19
1
24 Bottom Half
37 Top Half
Top Half 36
Bus #3
Distribution Device
Mounting Location
Top Half
Bus #4
Distribution Device
Mounting Location
31
30
42
43
25
48 Bottom Half
Front View
Door removed in illustration for clarity.
Note: On the right side, each half of
each bus MUST be populated with
distribution devices from top-to-bottom,
without skipping any distribution device
mounting positions within each half.
Note: On the left side, each half of
each bus MUST be populated with
distribution devices from bottom-to-top,
without skipping any distribution device
mounting positions within each half.
This allows automatic monitoring of each position and
allows the controller to located all distribution positions.
Load Lug Adapter Plates
are Mounted on the
Rear of the Bay
Page 27 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Rear View
Rear View
Rear cover panels removed in illustration for clarity.
to Distribution:
Bus #2
Position #13
to Distribution:
Bus #1
Position #12
to Distribution:
Bus #2
Position #18
to Distribution:
Bus #1
Position #7
to Distribution:
Bus #2
Position #19
to Distribution:
Bus #1
Position #6
to Distribution:
Bus #2
Position #24
to Distribution:
Bus #1
Position #1
to Distribution:
Bus #4
Position #37
to Distribution:
Bus #3
Position #36
to Distribution:
Bus #4
Position #42
to Distribution:
Bus #3
Position #31
to Distribution:
Bus #4
Position #43
to Distribution:
Bus #3
Position #30
to Distribution:
Bus #4
Position #48
to Distribution:
Bus #3
Position #25
Page 28 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
1-Position Devices
(Load Busbars with NO
Lug Adapters Installed)
(see Note 6)
3-Position
Lug Adapter Kit
P/N 529131
(see Notes 2, 3, 4, 5)
4-Position
Lug Adapter Kit
P/N 534420
(see Notes 2, 3, 4)
2-Position
Lug Adapter Kit
P/N 529132
(see Notes 1, 3, 4, 5)
Notes:
1. Lug adapter accepts a maximum of (2) 750 kcmil or (4) 350 kcmil lugs.
2. Lug adapter accepts a maximum of (4) 750 kcmil lugs.
3. Lugs are not part of the kit, shown for illustration only.
4. Bay busbars are not part of the kit, shown for illustration only.
5. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
6. Maximum lug width (without using an adapter plate) is 1.250 inches.
Page 29 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Distribution Devices
See Distribution Device and Load Lug Locations at the beginning of this section for illustrations of distribution
device and load lug mounting locations.
218 Circuit Breaker Assemblies
Features

Each circuit breaker assembly is equipped with a shunt for MCA load current measurements.

Bolts into bay's distribution device mounting positions.

Load lug busbars and adapter plates provide 3/8" clearance holes on 1" centers for installation of
customer provided two-hole lugs.
Restrictions
Load should not exceed 80% of device rating.
Refer to Table 1 for required distribution bus mounting positions.
Each distribution bus is divided into half. Each half MUST be populated with distribution devices as shown in
the illustrations at the beginning of this section, without skipping any distribution device mounting positions
within each half.
Four (4) position devices can only be installed in the 1st four or last four positions within each half of a
distribution bus. This is because the lug adapter plate for four (4) position devices can only be installed in
positions starting with the load busbar tops even with each other (not staggered).
Divide distribution equally between rows.
Refer to the illustrations in this section for lug and wire size restrictions.
Load return leads are terminated outside the bay to customer provided return busbars.
Ordering Notes
1) Order circuit breaker assemblies and load lug adapter kits per Table 1.
2) See Table 9 for recommended load distribution wire sizes and lugs.
Page 30 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Ampere
Rating
No.
of
Poles
Required
Distribution Bus
Mounting
Positions
100
125
150
175
200
225
250
300
350
400
450
500
600
800
1
1
1
1
1
1
1
2
2
2
3
3
3
4
1
1
1
1
1
1
1
2
2
2
3
3
3
4
Circuit Breaker
Part Number
Electrical Trip1
(White Handle)
Electrical/
Mechanical Trip2
(Black Handle)
513766
513768
513770
513772
513774
513776
513778
513780
513782
513784
513786
513788
513790
513792
513767
513769
513771
513773
513775
513777
513779
513781
513783
513785
513787
513789
513791
513793
Lug Adapter Kit
Part Number
(Qty 1)
not required
not required
not required
not required
not required
not required
not required
529132
529132
529132
529131
529131
529131
534420
See Table 9 for recommended load distribution wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Table 1
218 Circuit Breaker Assemblies
Page 31 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Lug Adapter Kit
NO LUG ADAPTER
KIT REQUIRED
1-Pole 218 Circuit
Breakers Assemblies
Lug Adapter Kit
3/8" Clearance Hole
1.000"
2-Pole 218 Circuit
Breaker Assemblies
2-Position
Lug Adapter Kit
P/N 529132
(see Notes 1, 2, 3, 4)
Notes:
1. Lug adapter accepts a maximum of (2) 750 kcmil or (4) 350 kcmil lugs.
2. Lugs are not part of the kit, shown for illustration only.
3. Bay busbars are not part of the kit, shown for illustration only.
4. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
Page 32 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Lug Adapter Kit
1.000"
3-Pole 218 Circuit
Breaker Assemblies
3/8"
Clearance
Hole
3-Position
Lug Adapter Kit
P/N 529131
(see Notes 1, 2, 3, 4)
Lug Adapter Kit
1.000"
3/8"
Clearance
Hole
4-Position
Lug Adapter Kit
P/N 534420
(see Notes 1, 2, 3, 5)
4-Pole 218 Circuit
Breaker Assemblies
Notes:
1. Lug adapter accepts a maximum of (4) 750 kcmil lugs.
2. Lugs are not part of the kit, shown for illustration only.
3. Bay busbars are not part of the kit, shown for illustration only.
4. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
5. Can only be installed in positions starting with
busbar tops even with each other (not staggered).
Page 33 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
TPL Fuses and Fuseholder Assemblies
Features

Each fuseholder assembly is equipped with a shunt for MCA load current measurements.

Bolts into bay's distribution device mounting positions.

Load lug busbars and adapter plates provide 3/8" clearance holes on 1" centers for installation of
customer provided two-hole lugs.
Restrictions
Load should not exceed 80% of device rating.
Refer to Table 2 for required distribution bus mounting positions.
Each distribution bus is divided into half. Each half MUST be populated with distribution devices as shown in
the illustrations at the beginning of this section, without skipping any distribution device mounting positions
within each half.
Divide distribution equally between rows.
Refer to the illustrations in this section for lug and wire size restrictions.
Load return leads are terminated outside the bay to customer provided return busbars.
Ordering Notes
1) Order fuses, the appropriate fuseholder assembly for each fuse, and load lug adapter kits per Table 2.
2) For each fuse ordered, also order one (1) P/N 248610301 alarm fuse,
and one (1) P/N 248898700 safety fuse cover.
3) See Table 9 for recommended load distribution wire sizes and lugs.
Ampere
Rating
Required
Distribution
Bus Mounting
Positions
70
80
100
150
200
225
250
300
400
500
600
800
2
2
2
2
2
2
2
2
2
2
2
3
Part Number
Fuse
Fuseholder
Assembly
248251500
248252000
248252600
248253300
248254000
248254500
248255000
248255700
248257000
248258000
248259000
102901
514403
514403
514403
514403
514403
514403
514403
514403
514403
514403
514403
514404
Lug Adapter Kit
Part Number
(Qty. 1)
529132
529132
529132
529132
529132
529132
529132
529132
529132
529132
529132
529131
For each fuse ordered, also order: one (1) P/N 248610301 alarm fuse
(GMT-18/100A), and one (1) P/N 248898700 safety fuse cover (GMT-X).
See Table 9 for recommended load distribution wire sizes and lugs.
Table 2
TPL Fuses and Fuseholder Assemblies
Page 34 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Lug Adapter Kit
3/8" Clearance Hole
1.000"
2-Position
Lug Adapter Kit
P/N 529132
(see Notes 1, 2, 3, 4)
TPL Fuse
GMT-18/100A
Alarm Fuse
and GMT-X
Safety Fuse Cover
Fuseholder Assembly
P/N 514403
Notes:
1. Lug adapter accepts a maximum of (2) 750 kcmil or (4) 350 kcmil lugs.
2. Lugs are not part of the kit, shown for illustration only.
3. Bay busbars are not part of the kit, shown for illustration only.
4. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
Page 35 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Lug Adapter Kit
TPL Fuse
GMT-18/100A
Alarm Fuse
and GMT-X
Safety Fuse Cover
Fuseholder Assembly
P/N 514404
1.000"
3/8" Clearance Hole
3-Position
Lug Adapter Kit
P/N 529131
(see Notes 1, 2, 3, 4)
Notes:
1. Lug adapter accepts a maximum of (4) 750 kcmil lugs.
2. Lugs are not part of the kit, shown for illustration only.
3. Bay busbars are not part of the kit, shown for illustration only.
4. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
Page 36 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses
Home
Features

Installs in the optional List C Fuse/Circuit Breaker Panel.

Load lugs are connected to busbars provided on the List C Fuse/Circuit Breaker Panel. These busbars
provide 1/4-20 threaded holes on 5/8" centers for installation of customer provided two-hole lugs. Load
return leads are terminated outside the bay to customer provided return busbars.
Restrictions
Load should not exceed 80% of device rating.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an
empty mounting position between it and any other overcurrent protective device within the
List C Fuse/Circuit Breaker Panel.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width is 0.610.
Customer must provide lug mounting bolts and additional hardware.
Bolt length: 3/4”.
Load return leads are terminated outside the bay to customer provided return busbars.
Ordering Notes
1) Order circuit breakers per Table 3.
2) Order fuses per Table 4.
3) For each fuse ordered, also order (1) Bullet Nose-Type Fuseholder P/N 117201.
Note: Fuseholder P/N 117201 also includes...
(1) Alarm Fuse P/N 248610301 and
(1) Safety Fuse Cover P/N 248898700.
4) See Table 8 for recommended load distribution wire sizes and lugs.
Page 37 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Ampere
Rating
1
3
5
10
15
20
25
30
35
40
45
50
60
70
75
80
100
125
150 (see
Caution
below)
200 (see
Caution
below)
250 (see
Caution
below)
Part Number
Number of Poles
(and mounting positions
required in the List C
Fuse/Circuit Breaker Panel)
Electrical Trip1
(White Handle)
Electrical/
Mechanical Trip2
(Black Handle)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
102272
102273
102274
102275
102276
102277
102278
102279
102280
102281
121998
102282
102283
102284
102285
121996
102286
516991
101596
101597
101598
101599
101600
101601
101602
101603
101604
101605
121997
101606
101607
101608
101609
121995
101610
516838
2
516993
516839
2
121831
121832
3
121835
121836
See Table 8 for recommended load distribution wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an
empty mounting position between it and any other overcurrent protective device within the
List C Fuse/Circuit Breaker Panel.
Table 3
Bullet Nose-Type Circuit Breakers
Page 38 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Ampere
Rating
Part
Number
Bussmann
P/N
Littelfuse
P/N
3
5
6
10
15
20
25
30
40
50
60
70
80
90
100
248230900
248231000
248231200
248231500
248231800
248232100
248232400
248232700
248233300
248233900
248234200
248234500
118413
118414
118415
TPS-3
TPS-5
TPS-6
TPS-10
TPS-15
TPS-20
TPS-25
TPS-30
TPS-40
TPS-50
TPS-60
TPS-70
----
TLS003
TLS005
TLS006
TLS010
TLS015
TLS020
TLS025
TLS030
TLS040
TLS050
TLS060
TLS070
TLS080
TLS090
TLS100
For each fuse ordered, also order a Bullet Nose-Type
Fuseholder P/N 117201.
Fuseholder P/N 117201 also includes...
(1) P/N 248610301 alarm fuse (GMT-18/100A), and
(1) P/N 248898700 safety fuse cover (GMT-X).
See Table 8 for recommended
load distribution wire sizes and lugs.
Table 4
Bullet Nose-Type Fuseholders (TLS/TPS Fuses)
Page 39 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Note: Load leads are connected to load busbars.
These busbars provide 1/4-20 threaded holes
on 5/8" centers for installation of customer
provided two-hole lugs. Customer must
provide lug mounting bolts and additional
hardware. Bolt length: 3/4".
GMT-18/100A
Alarm Fuse
and GMT-X
Safety Fuse Cover
TLS/TPS
Fuse
Assembled View
Bullet Nose-Type
Fuseholder
Bullet Nose-Type
Circuit Breaker
Bullet Nose-Type
Fuseholder,
P/N 117201
Page 40 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Optional Bullet Nose-Type 10-Position GMT Fuse Module for List C
Features

Installs in the optional List C Fuse/Circuit Breaker Panel.

Provides 10 GMT fuse positions.
(1/4A to 15A GMT Alarm-Type Fuses).

Screw clamp type load and load return terminals provided.

Includes ten dummy fuses equipped with safety fuse covers.

Includes 35A input fuse and associate alarm fuse.
Restrictions
30A maximum capacity per block.
Terminal block wire size capacity: 24 to 14 AWG.
Requires five (5) bullet device mounting positions.
When used for power distribution, load should not exceed 80% of device
rating, except 10 and 15 Amp fuses, for which load should not exceed 70% of device
rating.
P/N 509128
GMT Fuse Module
Ordering Notes
1) Order optional Bullet Nose-Type 10-Position GMT Fuse Module (P/N 509128) as required.
2) Order GMT fuses as required per Table 5.
3) See “Replacement Alarm, Reference, and Control Fuses” and Table 7 for ordering replacement input fuse
and associated alarm fuse.
Ampere Rating
Part Number
Fuse Color
18/100 GMT-A
1/4
1/2
3/4
1-1/3
2
3
5
7-1/2
10
15
Replacement
Safety Fuse
Cover
Replacement
Dummy Fuse
248610301
248610200
248610300
248610500
248610700
248610800
248610900
248611000
248611300
248611200
248611500
--VIOLET
RED
BROWN
WHITE
ORANGE
BLUE
GREEN
BLACK-WHITE
RED-WHITE
RED-BLUE
102774
---
248872600
---
Table 5
Bussmann GMT-Type Fuses
Page 41 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Replacement Alarm, Reference, and Control Fuses
Fuseblock Located in Bay’s Left Center
Features

Alarm, reference, and control fuses are located on the fuseblock mounted in the left center of the Power
Bays and Distribution Bays. These fuses are not available for customer connected loads. Note also that
distribution fuses also contain alarm-type fuses as detailed in the previous sections of this document.
Ordering Notes
1) Order replacement fuses as required per Table 6 (Replaceable Alarm, Reference, and Control Fuses).
ASSEMBLY
DESIG.
TYPE
PART NO.
3
SAN-O AX-1
248609200
--
--
--
3
SAN-O AX-1
248609200
--
SAN-O SAX-1
248898600
3
SAN-O AX-1
248609200
3
SAN-O AX-1
248609200
3
SAN-O AX-1
248609200
--
--
248898600
FA
Fuse Alarm
18/100A
--
Safety Fuse Cover
--
SAN-O SAX-1
Bussmann
GMT-18/100A
Bussmann GMT-X
F2
F3
-F1
F2
Distribution Bays
F3
Distribution
Fuseholder
Alarm Fuse
SIZE
(Amperes)
LMS CPU
Circuit Card
Input Power
-MCA/Router
Circuit Card
Input Power
Safety Fuse Cover
Router
Circuit Card
Input Power
Distribution Bus
Monitoring
Circuit Cards
Input Power
(Bus #1 and #2)
Distribution Bus
Monitoring
Circuit Cards
Input Power
(Bus #3 and #4)
Safety Fuse Cover
F1
Power Bays
FUNCTION
248610301
248898700
Table 6
Replaceable Alarm, Reference, and Control Fuses
Page 42 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Input and Alarm Fuse on Optional Bullet Nose-Type 10-Position GMT Fuse Module, P/N 509128
Home
Features

Located on the optional Bullet Nose-Type 10-Position GMT Fuse Module (P/N 509128) is an input fuse.
If this fuse opens, an alarm type fuse also opens to activate the fuse alarm circuit. The alarm-type fuse is
located in fuse position #11 on the Fuse Module.
Restrictions
These fuses are not available for customer connected loads.
Ordering Notes
1) Order replacement fuses as required per Table 7.
Ampere
Rating
35
0.18
Safety
Fuse Cover
(Bussmann
GMT-Y)
Part Number
110982
248610301
102774
Table 7
Replacement Input Fuse and Associated Alarm Fuse on
Bullet Nose-Type 10-Position GMT Fuse Module P/N 509128
Page 43 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Wiring Components
Load Distribution Wire Sizes and Lugs Selection (Distribution Bay)
Features

Load distribution leads are connected as described in the section titled Distribution Devices under
"Accessory Descriptions".

For lug mounting hole size and spacing dimensions, refer to the illustrations in the section titled
Distribution Devices under "Accessory Descriptions".
Restrictions
All lugs for customer connections must be ordered separately.
Ordering Notes
1) The type of distribution device determines the load lug hole size and spacing requirements. The rating of
the distribution device determines the wire size requirements. For wire size and lug selection; refer to
Table 8 and Table 9 (Load Side). (Load return leads are terminated outside the bay to customer provided
return busbars.)
2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.
Page 44 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Fuse/Circuit
Breaker
Amperage
1, 3, 5,
6, 10A
15A
20A
25A
30A
35A
40A
45A
50A
60A
70A
75A
80A
90A
100A
125A
150A
200A
250A
Lug
Recm 90C Wire Size (1)
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
4 AWG
2 AWG
Loop Length (feet) (2)
37 (3, 4)
58 (3, 4)
93 (3, 4)
--
--
--
--
24 (3, 4)
--------------
39 (3, 4)
29 (3, 4)
-------------
62 (3, 4)
46 (3, 4)
37 (3, 4)
31 (3, 4)
-----------
-74 (3, 4)
59 (3, 4)
49 (3, 4)
42 (3, 4)
37 (3, 4)
33 (3, 4)
29 (3, 4)
-------
--94 (3, 4)
78 (3, 4)
67 (3, 4)
59 (3, 4)
52 (3, 4)
47 (3, 4)
39 (3, 4)
33 (3)
31 (3)
----
----107 (3, 4)
94 (3, 4)
83 (3, 4)
75 (3, 4)
62 (3, 4)
53 (3, 4)
50 (3, 4)
47 (3, 4)
41 (3)
--
--------99 (3, 4)
85 (3, 4)
79 (3, 4)
74 (3, 4)
66 (3, 4)
59 (3, 4)
Two Pole Devices.
Use Load Lug Adapter Plate P/N 513700, Kit P/N 520891 (kit includes mtg. hardware)
and select Wire Sizes and Lugs per Table 9.
Three Pole Devices.
Use Load Lug Adapter Plate P/N 514676, Kit P/N 534703 (kit includes mtg. hardware)
and select Wire Sizes and Lugs per Table 9.
Recommended Crimp Lug (5)
245342300 245342300 245342300 245390200 245346700 245346800 245346900
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30C and 40C was used. For other operating
ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized,
follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping
information.
Table 8
Recommended Load Distribution Wire Size and Lug Selection for
TLS/TPS Fuse and Bullet Nose-Type Circuit Breaker (Load Side)
Page 45 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Recm 90C Wire Size (1)
Fuse/
Circuit
Breaker
Amperage
6
AWG
70A
33 (3)
80A
100A
125A
150A
175A
200A
225A
250A
4
AWG
2
AWG
1/0
AWG
2/0
AWG
3/0
AWG
4/0
AWG
250
kcmil
300
kcmil
350
kcmil
Loop Length (feet) (2)
---------
53 (3, 4)
85 (3, 4)
135 (3, 4)
--
--
--
--
--
--
(3, 4)
74
(3, 4)
(3, 4)
--
--
--
--
--
--
59
(3, 4)
--
47
--------
47
(3)
------
118
95
(3, 4)
76
(3, 4)
63
(3, 4)
-----
119
(3, 4)
95
(3, 4)
79
(3, 4)
68
(3, 4)
--
--
--
--
120
(3, 4)
--
--
--
--
100
(3, 4)
--
--
--
--
--
--
--
--
--
----
86
(3, 4)
75
(3, 4)
67
(3)
--
108
(3, 4)
95
(3, 4)
84
(3, 4)
76
(3)
112
(3, 4)
100
(3, 4)
90
(3, 4)
120
(3, 4)
--
108
(3, 4)
126 (3, 4)
Recommended Crimp Lug (5)
Lug
245349900
245350000
245348200
245347100
245347200
245347300
245347400
245347500
245347600
245347700
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30C and 40C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For operation in countries where the NEC is
not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
Table 9 (cont'd on next page)
Recommended Load Distribution Wire Size and Lug Selection for
TPL Fuse and 218 Circuit Breaker (Load Side)
Page 46 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Recm 90C Wire Size (1)
Fuse/
Circuit
Breaker
Amperage
2/0 AWG
300A
--
--
--
350A
68 (3, 4)
(2) Wires
86 (3, 4)
(2) Wires
75 (3, 4)
(2) Wires
67 (3)
(2) Wires
108 (3, 4)
(2) Wires
95 (3, 4)
(2) Wires
84 (3, 4)
(2) Wires
76 (3)
(2) Wires
150 (3, 4)
(2) Wires
128 (3, 4)
(2) Wires
112 (3, 4)
(2) Wires
100 (3, 4)
(2) Wires
90 (3, 4)
(2) Wires
4/0 AWG
250 kcmil
--
500A
--
600A
--
--
--
--
--
84 (3)
(3) Wires
800A
300 kcmil
350 kcmil
400 kcmil
90 (3)
105 (3, 4)
120 (3, 4)
--
90 (3)
103 (3)
--
--
--
--
--
126 (3, 4)
(2) Wires
--
105 (3, 4)
(2) Wires
120 (3, 4)
(2) Wires
118 (3, 4)
(3) Wires
135 (3, 4)
(3) Wires
245347700
(per cable)
245347800
(per cable)
Loop Length (feet) (2)
400A
450A
3/0 AWG
--
120 (3, 4)
(2) Wires
108 (3, 4)
(2) Wires
90 (3)
(2) Wires
135 (3, 4)
(3) Wires
101 (3, 4)
(3) Wires
Recommended Crimp Lug (5)
Lug
245347200
(per cable)
245347300
(per cable)
245347400
(per cable)
245347500
(per cable)
245347600
(per cable)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30C and 40C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For operation in countries where the NEC is
not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
Table 9 (cont'd from previous page)
Recommended Load Distribution Wire Size and Lug Selection for
TPL Fuse and 218 Circuit Breaker (Load Side)
Page 47 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Power Bay DC Output Cable Sizes and Lugs Selection
Features

3/8” clearance holes on 1" centers are provided for installation of customer provided DC output cables
terminated in two-hole lugs. These are accessed from the rear of each Power Bay.

For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting hardware.
Maximum size of wire to be connected to a single lug position is 750 kcmil (2 per lug position).
Maximum lug width, 1.937 inches.
Ordering Notes
1) DC output cable size varies depending on power requirements, therefore no specific information is
provided for cable size. Refer to Table 10 for recommended cable sizes and lugs at rated maximum bay
output (2400 amperes). When making connections, observe correct polarity.
2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.
Ambient Operating
Temperature (1)
30°C
40°C
Loop
Length (2)
(Ft)
Recm 90C
Wire Size (1, 2)
Recommended
Crimp Lug (3)
140
140
168
(5) 750 kcmil
(5) 750 kcmil
(6) 750 kcmil
245392000
1
Cable sizes are based on recommendations of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC). Table 310-16 for copper wire rated at 90C conductor temperature operating in
ambients of 30C and 40C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended cable sizes are sufficient to restrict voltage drop to 1.0 volt or less at rated full
output current of the bay for the loop lengths shown. Loop length is the sum of the lengths of
the positive and negative leads.
3
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug
crimping information.
Table 10
Recommended Power Bay DC Output Cable Size and Lug Selection
Page 48 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
3/8" Clearance
Hole (21)
2.00"
1.00"
1.25"
DC Output
Negative Busbar (-)
(Supply -48V Bus)
DC Output
Positive Busbar (+)
(Ground Return Bus)
Rear Cover Panel
Removed in Illustration
Rear View
Power Bay
Page 49 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Distribution Bay DC Input Cable Sizes and Lugs Selection
Features

3/8” clearance holes on 1" centers are provided for installation of customer provided DC input cables
terminated in two-hole lugs. These are accessed from the rear of each Distribution Bay.

For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting hardware.
Maximum size of wire to be connected to a single lug position is 750 kcmil (2 per lug position).
Maximum lug width, 2.000 inches.
Ordering Notes
1) DC input cable size varies depending on power requirements, therefore no specific information is
provided for cable size. Refer to Table 11 for recommended cable sizes and lugs at rated maximum bay
load (6000 amperes). When making connections, observe correct polarity.
2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.
Ambient Operating
Temperature (1)
30°C
40°C
Loop
Length (2)
(Ft)
Recm 90C
Wire Size (1, 2)
Recommended
Crimp Lug (3)
112
112
157
(10) 750 kcmil
(10) 750 kcmil
(14) 750 kcmil
245392000
1
Wire sizes are based on recommendations of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC). Table 310-16 for copper wire rated at 90C conductor temperature operating in
ambients of 30C and 40C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at rated full
load output current of the bay for the loop lengths shown. Loop length is the sum of the
lengths of the positive and negative leads.
3
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug
crimping information.
Table 11
Recommended Distribution Bay DC Input Cable Size and Lug Selection
Page 50 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
3/8" Clearance Hole (22)
2.031"
DC Input
(Supply -48V)
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
Rear View
Distribution Bay
Page 51 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Power Bay Frame Grounding Wire Sizes and Lugs Selection
Home
Features

1/4” clearance holes on 5/8" centers are provided for installation of customer provided two-hole lugs, as
shown in the following illustration.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
The recommended frame grounding wire size is 6 AWG.
Recommended lug P/N 245346700.
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.
Top View
Power Bay
Page 52 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Distribution Bay Frame Grounding Wire Sizes and Lugs Selection
SAG582140001
Issue AF, July 14, 2010
Home
Features

1/4” clearance holes on 5/8" centers are provided for installation of customer provided two-hole lugs, as
shown in the following illustration.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
The recommended frame grounding wire size is 6 AWG.
Recommended lug P/N 245346700.
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.
Top View
Distribution Bay
Page 53 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
AC Input (12 or 24 AC Input Feeds)
Wire and Conduit Sizes, Branch Circuit Protection, and Lugs Selection
Lists 5 and 13
Home
Features

3/8-16 studs on 1” centers are provided for installation of customer provided two-hole AC Input lugs.

1/4-20 studs are provided for installation of customer provided two-hole AC equipment grounding lugs.

For AC input wiring, refer to the illustration provided in this section.
Restrictions
Twelve (12) or twenty-four (24) AC input feeds are required in Lists 5 and 13 only.
24 Feeds, 208VAC, List B w/ List 5 or 13: Three feeds per conduit and one ground per conduit.
Customer must provide a 25A high inrush circuit breaker overcurrent protection device in each AC input
feed.
24 Feeds, 380/480VAC, List A w/ List 5 or 13: Three feeds per conduit and one ground per conduit.
Customer must provide a 15A high inrush circuit breaker overcurrent protection device in each AC input
feed.
12 Feeds, 208VAC, List B w/ List 5 or 13: Two feeds per conduit and one ground per conduit. Customer
must provide a 50A high inrush circuit breaker overcurrent protection device in each AC input feed.
12 Feeds, 380/480VAC, List A w/ List 5 or 13: Two feeds per conduit and one ground per conduit.
Customer must provide a 30A high inrush circuit breaker overcurrent protection device in each AC input
feed.
All lugs for equipment grounding connections must be ordered separately. Customer needs to supply lug
mounting hardware.
Ordering Notes
1) Refer to Table 12 for recommended AC input wire and conduit sizes, branch circuit protection, and
equipment grounding lugs.
Page 54 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
24 Feeds
Input
Voltage
Input
Current
Overcurrent
Protection (1)
40°C Ambient
Temperature (2)
Wire
AWG (2) (3)
Conduit
Size (in.)
THWN - 75°C Wire - Individual Feed
Three Rectifiers (9 Current and 1 Ground Wire) per Conduit
480V
380V
208V
7.8A
10A
18A
15A
15A
25A
14
14
10
1/2
1/2
3/4
THHN - 90°C Wire - Individual Feed
Three Rectifiers (9 Current and 1 Ground Wire) per Conduit
480V
380V
208V
7.8A
10A
18A
15A
15A
25A
14
14
10
1/2
1/2
3/4
Recommended Equipment Grounding Wire Crimp Lugs
Wire AWG
14
10
8
Crimp Lug P/N (4)
245359650
245342300
245346600
1
The AC input branch circuit protective device should be of the
time-delay or high inrush type.
2
Wire sizes based on recommendations of the American National
Standards Institute (ANSI) approved National Fire Protection
Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 75°C and 90°C conductor temperature;
operating in an ambient of 40C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For
operation in countries where the NEC is not recognized, follow
applicable codes.
3
Equipment grounding conductors must be provided with the AC
input conductors supplied to the Bay. Frame ground terminals
must be connected to earth ground, not power system neutral.
Equipment grounding conductor size based on recommendations
of the NEC Table 250-122 for copper wire. When aluminum or
copper clad aluminum grounding conductor is used, refer to Table
250-122 for increased conductor size. For operation in countries
where the NEC is not recognized, follow applicable codes.
4
Single-hole lug, 1/4” bolt clearance hole.
Table 12
Recommended AC Input Wire and Conduit Size, and Lug Selection
(24 AC Input Feeds, 1 per Rectifier Module)
Page 55 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
12 Feeds
Input
Voltage
Input
Current
Overcurrent
Protection (1)
40°C Ambient
Temperature (2)
Wire
AWG (2) (3)
Conduit
Size (in.)
THWN - 75°C Wire - Individual Feed
Four Rectifiers (6 Current and 1 Ground Wire) per Conduit
480V
380V
208V
15.6A
20A
35.8A
20A
25A
50A
12
10
6
1/2
3/4
1
THHN - 90°C Wire - Individual Feed
Four Rectifiers (6 Current and 1 Ground Wire) per Conduit
480V
380V
208V
15.6A
20A
35.8A
20A
25A
50A
12
10
6
1/2
3/4
1
Recommended Equipment Grounding Wire Crimp Lugs
Wire AWG
8
6
Crimp Lug P/N (4)
245346600
245346500
1
The AC input branch circuit protective device should be of the
time-delay or high inrush type.
2
Wire sizes based on recommendations of the American National
Standards Institute (ANSI) approved National Fire Protection
Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 75°C and 90°C conductor temperature;
operating in an ambient of 40C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For
operation in countries where the NEC is not recognized, follow
applicable codes.
3
Equipment grounding conductors must be provided with the AC
input conductors supplied to the Bay. Frame ground terminals
must be connected to earth ground, not power system neutral.
Equipment grounding conductor size based on recommendations
of the NEC Table 250-122 for copper wire. When aluminum or
copper clad aluminum grounding conductor is used, refer to Table
250-122 for increased conductor size. For operation in countries
where the NEC is not recognized, follow applicable codes.
4
Single-hole lug, 1/4” bolt clearance hole.
Table 13
Recommended AC Input Wire and Conduit Size, and Lug Selection
(12 AC Input Feeds, 1 per 2 Rectifier Modules)
Page 56 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
AC Input (6 AC Input Feeds)
Wire and Conduit Sizes, Branch Circuit Protection, and Lugs Selection
Lists 6 and 14
SAG582140001
Issue AF, July 14, 2010
Home
Features

3/8-16 studs on 1” centers are provided for installation of customer provided two-hole AC Input lugs.

1/4-20 studs are provided for installation of customer provided two-hole AC equipment grounding lugs.

For AC input wiring, refer to the illustration provided in this section.
Restrictions
Six (6) AC input feeds are required in Lists 6 and 14 only.
6 Feeds, 480V, List A w/ List 6 or 14: One feed per conduit and one ground per conduit. Customer must
provide a 40-50A high inrush circuit breaker overcurrent protection device in each AC input feed.
All lugs for equipment grounding connections must be ordered separately. Customer needs to supply lug
mounting hardware.
Ordering Notes
Refer to Table 12 for recommended AC input wire and conduit sizes, branch circuit protection, and equipment
grounding lugs.
Page 57 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
6 Feeds
Input
Voltage
Input
Current
Overcurrent
Protection (1)
40°C Ambient
Temperature (2)
Wire
AWG (2) (3)
Conduit
Size (in.)
THWN - 75°C Wire - Individual Feed
Four Rectifiers (6 Current and 1 Ground Wire) per Conduit
480V
480V
31A
31A
40A
50A
8
6
3/4
3/4
THHN - 90°C Wire - Individual Feed
Four Rectifiers (6 Current and 1 Ground Wire) per Conduit
480V
480V
31A
31A
40A
50A
8
6
3/4
3/4
Recommended Equipment Grounding Wire Crimp Lugs
Wire AWG
8
6
Crimp Lug P/N (4)
245346600
245346500
1
The AC input branch circuit protective device should be of the
time-delay or high inrush type.
2
Wire sizes based on recommendations of the American National
Standards Institute (ANSI) approved National Fire Protection
Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 75°C and 90°C conductor temperature;
operating in an ambient of 40C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For
operation in countries where the NEC is not recognized, follow
applicable codes.
3
Equipment grounding conductors must be provided with the AC
input conductors supplied to the Bay. Frame ground terminals
must be connected to earth ground, not power system neutral.
Equipment grounding conductor size based on recommendations
of the NEC Table 250-122 for copper wire. When aluminum or
copper clad aluminum grounding conductor is used, refer to Table
250-122 for increased conductor size. For operation in countries
where the NEC is not recognized, follow applicable codes.
4
Single-hole lug, 1/4” bolt clearance hole.
Table 14
Recommended AC Input Wire and Conduit Size, and Lug Selection
(6 AC Input Feeds, 1 per 4 Rectifier Modules)
Page 58 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
See Detail A
(12 Feeds)
Six (6) 1.125" openings for 3/4" conduit.
Two (2) conduit plates with
2.5", 1.75", and 1.125" knock-outs
for 2", 1.5", and 3/4" conduit.
Six (6) 1.75" openings for 1.5" conduit
(under plate).
See Detail B
(24 Feeds)
See Detail C
(6 Feeds)
Top View
Power Bay
Front cover panel
removed in illustration
Note: Rectif i er nu mbring is for
c e wiring identif i ation only.
s
The MCA identif i esrectif i er
f
dif erently.
Rectif i er #1Mounting Slot
Rectif i er #2 Mounting Slot
Rectif i er #3 Mounting Slot
Rectif i er #4 Mounting Slot
Rectif i er #5 Mounting Slot
Rectif i er #6 Mounting Slot
Rectif i er #7 Mounting Slot
Rectif i er #8 Mounting Slot
Rectif i er #9 Mounting Slot
Rectif i er #10 Mounting Slot
Rectif i er #11 Mounting Slot
Rectif i er #12 Mounting Slot
Rectif i er #13 Mounting Slot
Rectif i er #14 Mounting Slot
Rectif i er #15 Mounting Slot
Rectif i er #16 Mounting Slot
Rectif i er #17 Mounting Slot
Rectif i er #18 Mounting Slot
Rectif i er #19 Mounting Slot
Rectif i er #20 Mounting Slot
Rectif i er #21 Mounting Slot
Rectif i er #22 Mounting Slot
Rectif i er #23 Mounting Slot
Rectif i er #24 Mounting Slot
Front View
Power Bay
Page 59 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Detail A
380/480VAC (List A) or 208VAC (List B)
3 Phase, 50/60Hz
(12 AC Input Feeds,
1 per 2 Rectifier Modules)
Equipment
Grounding
(1/4-20 Studs
on 1" Centers)
AC Input
(3/8-16 Studs
on 1" Centers)
Phase A
Phase B
Phase C
Rectifier #1 & #2
Mounting Slot
Phase A
Phase B
Phase C
Rectifier #5 & #6
Mounting Slot
Phase A
Phase B
Phase C
Rectifier #9 & #10
Mounting Slot
Phase A
Phase B
Phase C
Rectifier #13 & #14
Mounting Slot
Phase A
Phase B
Phase C
Rectifier #17 & #18
Mounting Slot
Phase A
Phase B
Phase C
Rectifier #21 & #22
Mounting Slot
Rectifier #3 & #4 Phase A
Phase B
Mounting Slot
Phase C
Rectifier #7 & #8 Phase A
Mounting Slot Phase B
Phase C
Rectifier #11 & #12 Phase A
Mounting Slot Phase B
Phase C
Rectifier #15 & #16 Phase A
Phase B
Mounting Slot
Phase C
Phase A
Rectifier #19 & #20 Phase B
Mounting Slot
Phase C
Phase A
Rectifier #23 & #24
Phase B
Mounting Slot
Phase C
Ensure jumper busbars are installed.
Refer to the Installation Instructions (Section 6016).
Page 60 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Detail B
380/480VAC (List A) or 208VAC (List B)
3 Phase, 50/60Hz
(24 AC Input Feeds,
1 per Rectifier Module)
Equipment
Grounding
(1/4-20 Studs
on 1" Centers)
AC Input
(3/8-16 Studs
on 1" Centers)
Rectifier #1 Phase A
Phase B
Mounting Slot
Phase C
Rectifier #3 Phase A
Phase B
Mounting Slot
Phase C
Phase A
Rectifier #5
Phase B
Mounting Slot
Phase C
Rectifier #7 Phase A
Mounting Slot Phase B
Phase C
Rectifier #9 Phase A
Mounting Slot Phase B
Phase C
Rectifier #11 Phase A
Mounting Slot Phase B
Phase C
Rectifier #13 Phase A
Mounting Slot Phase B
Phase C
Rectifier #15 Phase A
Phase B
Mounting Slot
Phase C
Rectifier #17 Phase A
Phase B
Mounting Slot
Phase C
Phase A
Rectifier #19 Phase B
Mounting Slot
Phase C
Phase A
Rectifier #21
Phase B
Mounting Slot
Phase C
Phase A
Rectifier #23
Phase B
Mounting Slot
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Rectifier #2
Mounting Slot
Rectifier #4
Mounting Slot
Rectifier #6
Mounting Slot
Rectifier #8
Mounting Slot
Rectifier #10
Mounting Slot
Rectifier #12
Mounting Slot
Rectifier #14
Mounting Slot
Rectifier #16
Mounting Slot
Rectifier #18
Mounting Slot
Rectifier #20
Mounting Slot
Rectifier #22
Mounting Slot
Rectifier #24
Mounting Slot
Ensure jumper busbars are NOT installed.
Refer to the Installation Instructions (Section 6016).
Page 61 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
Detail C
380/480VAC(List A) or 208VAC(List B)
3 Phase, 50/60Hz
(24ACInput Feeds,
1 per Rectifier Module)
Equipment
Grounding
(1/4-20 Studs
on 1" Centers)
ACInput
(3/8-16 Studs
on 1" Centers)
PhaseA
Rectifier #1, #2, #3 &#4 Phase B
Mounting Slot Phase C
PhaseA
Phase B Rectifier #5, #6, 7 &#8
Phase C Mounting Slot
PhaseA
Rectifier #9, #10, #11 & #12 Phase B
Mounting Slot Phase C
PhaseA Rectifier #13, #14, #15 &#16
Phase B Mounting Slot
Phase C
Rectifier #13, #14, #15 &#16 PhaseA
Phase B
Mounting Slot
Phase C
PhaseA
Rectifier #21, #22, #23 &#24
Phase B
Phase C Mounting Slot
Ensure jumper busbars are NOTinstalled.
Refer to the Installation Instructions (Section 6016).
Page 62 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
AC Input (2 AC Input Feeds)
Wire and Conduit Sizes, Branch Circuit Protection, and Lugs Selection
Lists 4 and 12
SAG582140001
Issue AF, July 14, 2010
Home
Features

3/8-16 studs on 1” centers are provided for installation of customer provided two-hole AC Input lugs.

1/4-20 studs are provided for installation of customer provided two-hole AC equipment grounding lugs.

For AC input wiring, refer to the illustration provided in this section.
Restrictions
Two (2) AC input feeds are required in Lists 4 and 12 only. One feed per conduit and one ground per conduit.
2 Feeds, 208VAC, List B w/ List 4 or 12: Customer must provide a 300A high inrush circuit breaker
overcurrent protection device in each AC input feed.
2 Feeds, 380VAC, List A w/ List 4 or 12: Customer must provide a 150A high inrush circuit breaker
overcurrent protection device in each AC input feed.
2 Feeds, 480VAC, List A w/ List 4 or 12: Customer must provide a 125A high inrush circuit breaker
overcurrent protection device in each AC input feed.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting hardware.
Ordering Notes
1) Refer to Table for recommended AC input wire and conduit sizes, branch circuit protection, and lugs.
Page 63 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Input
Voltage
Input
Current
Overcurrent
Protection (1)
40°C Ambient
Temperature (2)
Wire
AWG (2) (3)
Conduit
Size (in.)
THWN - 75°C Wire - Dual Feed
Twelve Rectifiers (3 Current and 1 Ground Wire) per Conduit
480V
380V
208V
91A
115A
212A
125A
150A
300A
1/0
1/0
300 kcmil
1-1/2
1-1/2
2-1/2
THHN - 90°C Wire - Dual Feed
Twelve Rectifiers (3 Current and 1 Ground Wire) per Conduit
480V
380V
208V
91A
115A
212A
125A
150A
300A
2
1/0
300 kcmil
1-1/2
1-1/2
2-1/2
Recommended Crimp Lugs
Wire AWG
1/0
350 kcmil
Crimp Lug P/N (4)
245347100
245347700
1
The AC input branch circuit protective device should be of the
time-delay or high inrush type.
2
Wire sizes based on recommendations of the American National
Standards Institute (ANSI) approved National Fire Protection
Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 75°C and 90°C conductor temperature;
operating in an ambient of 40C, was used. For other operating
ambient temperatures, refer to the National Electrical Code. For
operation in countries where the NEC is not recognized, follow
applicable codes.
3
Equipment grounding conductors must be provided with the AC
input conductors supplied to the Bay. Frame ground terminals
must be connected to earth ground, not power system neutral.
Equipment grounding conductor size based on recommendations
of the NEC Table 250-122 for copper wire. When aluminum or
copper clad aluminum grounding conductor is used, refer to Table
250-122 for increased conductor size. For operation in countries
where the NEC is not recognized, follow applicable codes.
4
Two-hole lug, 3/8” bolt clearance hole, 1" centers. Refer to
drawing 031110100 for lug crimping information.
Table 15
Recommended AC Input Wire and Conduit Size, and Lug Selection
(2 AC Input Feeds, 1 per 12 Rectifier Modules)
Page 64 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
380/480VAC (List A) or 208VAC (List B)
3 Phase, 50/60Hz
(2 AC Input Feeds,
1 per 12 Rectifier Modules)
Odd Numbered
Rectifier Mounting
Slots
Even Numbered
Rectifier Mounting
Slots
C B A
A B C
Equipment
Grounding
(1/4-20 Studs
on 1" Centers)
AC Input
(3/8-16 Studs
on 1" Centers)
Front cover panel
removed in illustration
Six (6) 1.125" openings for 3/4" conduit.
Two (2) conduit plates with
2.5", 1.75", and 1.125" knock-outs
for 2", 1.5", and 3/4" conduit.
Six (6) 1.75" openings for 1.5" conduit
(under plate).
Top View
Power Bay
CB1
CB7
CB2
CB8
CB3
CB9
CB4
CB10
CB5
CB11
Note: Rectifier numbering is for
wiring identification only.
The MCA identifies rectifiers
differently.
CB6
CB12
Rectifier #1 Mounting Slot
Rectifier #2 Mounting Slot
Rectifier #3 Mounting Slot
Rectifier #4 Mounting Slot
Rectifier #5 Mounting Slot
Rectifier #6 Mounting Slot
Rectifier #7 Mounting Slot
Rectifier #8 Mounting Slot
Rectifier #9 Mounting Slot
Rectifier #10 Mounting Slot
Rectifier #11 Mounting Slot
Rectifier #12 Mounting Slot
Rectifier #13 Mounting Slot
Rectifier #14 Mounting Slot
Rectifier #15 Mounting Slot
Rectifier #16 Mounting Slot
Rectifier #17 Mounting Slot
Rectifier #18 Mounting Slot
Rectifier #19 Mounting Slot
Rectifier #20 Mounting Slot
Rectifier #21 Mounting Slot
Rectifier #22 Mounting Slot
Rectifier #23 Mounting Slot
Rectifier #24 Mounting Slot
Front View
Power Bay
Page 65 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
External Alarm, Reference, and Control Wire Sizes - Power Bays
Features

External Alarm, Reference, and Control connections are made to TB1 on the MCA circuit card and TB1
on the MCA Customer Alarm Relay Circuit Cards.
Terminals
Recm
Wire Size
Capacity
Type
28 to 16
AWG
Screw Clamp
22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Table 16
Recommended Alarm, Reference, and Control Wire Size
(TB1 on MCA Circuit Card)
(TB1 on MCA Customer Alarm Relay Circuit Card)
MCA Circuit Card
(Primary Power Bay only)
MCA Customer Alarm Relay Circuit Cards
and/or LMS Input/Output (I/O) Circuit Cards.
TB1
18
1
10
9
1
10
TB1
MCA Circuit Card P/N 509478
(Primary Bay)
MCA Customer Alarm
Relay Circuit Card P/N 514348
(Primary and/or Secondary Bays)
Page 66 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Optional Battery Charge Temperature
Compensation Probe for Digital Compensation
Features

This system can be used with a Battery Charge Temperature Compensation Probe. This probe must be
mounted near the battery to sense battery ambient temperature. The probe connects to and allows the
MCA to automatically increase or decrease the output voltage of the system to maintain battery float
current as battery ambient temperature decreases or increases, respectively. Battery life can be
extended when an optimum charge voltage to the battery with respect to temperature is maintained.

Refer to the "Specifications" section of this document for further information.

Temperature Curve: The following figure details a user defined, via the MCA, Temperature
Compensation Probe Curve.
Ordering Notes
1) Order one Battery Charge Temperature Compensation Probe per power system. Part No. 107021 has a
25-foot long cord. Part No. 106824 has a 100 foot-long cord.
Decreasing
Voltage
Increasing
MAX W/T
Adjustable from
Float to 58.5V max.*
SLOPE
Adjustable from 0.0 V / °C
to 0.2 V / °C
FLOAT
Determines Float Mode
Output Voltage at 25°C.
Adjustable from 47.0V
to 58.0V max.*
MIN W/T
Adjustable from
Float to 44V
* Maximum setting is automatically
limited to 1.0 volt less than HVSD setting.
Decreasing
Temperature
Increasing
+25°C
(+77°F)
Typical Float Charge Thermal Characteristics
Using Optional Battery Charge Digital Temperature Compensation Probe
Page 67 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Replacement/Additional MCA Network Cable
Home
Features

MCA bay-to-bay interconnect cable. Connects between bay expansion ports located on the bay's MCA
(Primary Power Bay) and Router (Secondary Power Bays and Distribution Bays) circuit cards.

Cable identification color is yellow.
Restrictions
Maximum combined cable length must not exceed 125 feet.
Ordering Notes
1) For a replacement or additional cable, order the proper length cable from those listed below.
P/N 514642 (3 feet) (factory provided with List 9 and 10)
P/N 514643 (4 feet)
P/N 514644 (6 feet) (factory provided with List 16)
P/N 524726 (15 feet)
P/N 514645 (25 feet)
P/N 514646 (50 feet)
P/N 514647 (100 feet)
Replacement/Additional LMS Network Cable
Features

LMS bay-to-bay interconnect cable. Connects between the bay's LMS Echelon expansion ports. Also
connects the LMS System to LMS Expansion Cabinets and Assemblies, if furnished.

Cable identification color is blue.
Restrictions
Refer to SAG586505000 (LMS System Application Guide) for maximum LMS network cabling length.
Ordering Notes
1) For a replacement or additional cable, order the proper length cable from those listed below.
P/N 524409 (5 inches)
P/N 509070 (6 inches)
P/N 528520 (10 inches)
P/N 509071 (15 inches)
P/N 524410 (2 feet)
P/N 514639 (3 feet) (factory provided with List 63)
P/N 509900 (4 feet)
P/N 514640 (25 feet)
P/N 514641(150 feet)
Page 68 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Replacement Modules and Circuit Cards
Ordering Notes
1) Refer to the following table.
Item
Rectifier Module, 208VAC Input
Rectifier Module, 380/480VAC Input
Rectifier Module Fan
MCA Circuit Card
(Primary Power Bay)
Router Circuit Card
(Secondary Power Bay
and Distribution Bays)
Distribution Monitoring Circuit Card
(Distribution Bays)
LMS Primary CPU Circuit Card
(Primary Power Bay)
LMS Expansion CPU Circuit Card
(Secondary Power Bay)
MCA Customer Alarm
Relay Circuit Card
MCA I/O Circuit Card
Part Number
Order via List 21
Order via List 22
32010109
509478
509509
524982
Order via List 50
Order via List 63
Order via List 70
Order via List 71
Page 69 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
SPECIFICATIONS
1. SYSTEM
1.1
1.2
DC Operating Voltage
1.1.1
Nominal: -48Vdc.
1.1.2
Range: -42Vdc to -60Vdc.
Environmental Ratings
Note: See also ‘Environmental Ratings’ in the Rectifier Module section.
1.2.1
Operating Ambient Temperature Range: 0°C to +40°C (+32°F to +104°F).
1.2.2
Storage Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F).
1.2.3
Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
1.2.4
Altitude: The maximum operating ambient temperature should be derated by 10°C at an
elevation of 10,000 feet above sea level. For elevations between 3,000 feet and 10,000 feet,
derate the maximum operating ambient temperature linearly.
1.2.5
Heat Dissipation: With Rectifier Module output adjusted to 54.48 volt DC at rated full load and
nominal input voltage.
No. of
Rectifier
Modules
Power Bay Output
Current (Amperes)
1
24
100
2400
BTU/Hr
(Typical)
1R485800
Rectifier
1R485800L
Rectifier
1472
35328
1739
41726
1.2.6
Ventilation Requirements: The Rectifier Modules are fan cooled and utilize front to back
forced ventilation. The Power Bays must be mounted so ventilating openings are not blocked
and temperature of the air entering the Rectifier Module shelf does not exceed the Operating
Ambient Temperature Range stated above.
1.2.7
Audible Noise: The audible noise does not exceed the following when measured at any point
two feet from any vertical surface of a Power Bay and five feet from the floor using a Sound
Level Meter conforming to ANSI S1.4.
1.2.8
No. of
Rectifier
Modules
Audible Noise
1
24
50 dBA
60 dBA
EMI/RFI Suppression: Rectifier Modules operating in a Power Bay conform to the
requirements of FCC rules Part 15, Subpart B, Class A for Radiated and Conducted emissions
limits.
Page 70 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
1.2.9
SAG582140001
Issue AF, July 14, 2010
Surge Protection: Compliance with EN61000-4-5 Installation Class 4, and capable of
withstanding surges per ANSI/IEEE C 62.41-1991 Category B across the input
terminals.
Home
Note: This level of protection is a widely used standard for telecommunications power
equipment. As with all such equipment, it is the end user's responsibility to provide an
adequately sized Surge Suppression Device at the commercial power service entrance of
the building that reduces all incoming surges to levels below the classes/categories
stated for the equipment.
1.2.10 ESD Protection: Complies with EN61000-4-2 Level 4 (8kV contact).
1.2.11 Electrical Fast Transient / Burst Immunity: Complies with EN61000-4-4 Level 4.
1.2.12 Mounting: This Power System is intended only for installation in a Restricted Access Location
on or above a non-combustible surface. Typical industry standards recommend minimum aisle
space clearance of 2'6" for the front of the relay rack and 2' for the rear of the relay rack.
1.3
Compliance Information
1.3.1
Safety Compliance
(A) Model 801NLEB and 801NLDB (Power Bay): This unit meets the requirements of UL 60950,
Standard for Information Technology Equipment, and is UL Listed as a power supply for use
in Telephone, Electronic Data Processing or Information Processing Equipment.
(B) Model 801NL-B (Distribution Bay): This power board is UL Listed as a DC Power
Distribution Center for Communications Equipment.
1.3.2
NEBS Compliance
(A) Model 801NLEB (Power Bay) and Model 801NL-B (Distribution Bay): Compliance verified
by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE and
GR-63-CORE. Contact Emerson Network Power for NEBS compliance reports.
(B) Model 801NLDB (Power Bay) (Lists 0B, 05, 13, 21, 50, 63, 64, 65, 66, 67, 70, 71):
Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per
GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS
compliance reports.
In order to remain compliant during a fan failure condition, the backup battery connection must
be utilized to provide sufficient power to the loads for up to eight (8) hours when the system is
operated at greater than 50% output power. If no backup battery connection is used, the system
must operate with a redundant module installed.
1.4
Local Controls and Indicators
1.4.1
"Bay Alarm" Indicator: Located at the top center of each bay.
Green = OK
Red = Bay Failure
Yellow (flashing) = Identified by the MCA
1.4.2
MCA Component Identification Indicator: Each MCA component (i.e. Rectifier Module, Bus
Monitoring Circuit Card, Bay Router Circuit Card, MCA Relay Circuit Card) contains an ID LED
Indicator. The ID indicator illuminates Green when the component is OK, Red when the
component has failed, and flashing yellow when the component is identified by the MCA.
1.4.3
"Distribution Bus" Indicators: Each distribution bus contains and indicator located on a
hinged door panel covering the bus's MCA Monitoring circuit card.
Green = OK
Red = Card Failure
Yellow (flashing) = Identified by the MCA
Page 71 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
1.4.4
See also ‘Local Controls and Indicators’ in the Rectifier Module, MCA, and LMS
sections.
Home
2. DISTRIBUTION BAY
2.1
DC Ratings
6000 amperes, maximum, per bay.
16,800 amperes, maximum, per system.
2.1.1
Bay:
2.1.2
1500 amperes, maximum.
Each bay has four (4) Distribution Buses.
Optional Distribution Panel: 500 amperes, maximum.
One optional Distribution Panel per Distribution Bay.
2.1.3
Fuse/Circuit Breaker Mounting Positions: Each Distribution Bus contains 12 fuse/circuit
breaker mounting positions which provides 48 fuse/circuit breaker mounting positions per bay.
Note that some fuse/circuit breaker combinations require more than one fuse/circuit breaker
mounting position. Refer to Distribution Devices under ACCESSORY DESCRIPTIONS for
details.
Bus:
The optional Distribution Panel provides twenty-four (24) Bullet Nose Device positions. The
panel accepts a choice of TLS/TPS-type fuseholders or Bullet Nose-type circuit breakers. When
installed, bay can be loaded with up to (46) 218 Circuit Breakers or TPL Fuses, and (24) Bullet
Nose Circuit Breakers or TLS/TPS Fuses.
Note: The List C Circuit Breaker/Fuse Panel requires distribution position #12 in the Bus #1
Distribution Panel. Also, distribution position #36 in the Bus #3 Distribution Panel must
remain empty.
3. RECTIFIER MODULE (MODEL R48-5800, SPEC. NO. 1R485800)
3.1
DC Output Ratings
3.1.1
Voltage: Nominal -48 volts DC, Positive Ground.
(A) Without Battery Charge Temperature Compensation: Float voltage is adjustable from
47.00 to 58.00 volts DC. Test/equalize voltage is adjustable from 45.00 to 58.00 volts DC.
Adjustment is made via the MCA. Both float and test/equalize voltages are factory set at
52.00 volts, unless otherwise specified. The output voltage temperature coefficient (1/°C)
does not exceed 0.01% per degree centigrade from 0°C to +40°C.
(B) With Battery Charge Digital Temperature Compensation Probe: With an optional battery
charge digital temperature compensation probe installed, the MCA automatically increases
or decreases the output voltage as battery ambient temperature decreases or increases,
respectively. Float voltage is factory set at approximately 54.48 volts at 25C battery
ambient. The float and test/equalize voltage range is the same as without battery charge
temperature compensation. Using battery and equipment manufacturers’ recommendations,
the user selects the following temperature compensation curve parameters via the MCA.
Refer to "Typical Float Charge Thermal Characteristics Using Optional Battery Charge
Digital Temperature Compensation Probe" in Battery Charge Temperature Compensation
Probe for Digital Compensation under ACCESSORY DESCRIPTIONS.
(1) The temperature compensation slope in volts/C. Adjustable from zero to 200
millivolts/C. Adjustment is made via the MCA. Factory set at 0V/C (DIGITAL TC
OFF).
(2) The maximum voltage limit in volts DC. Adjustable from float up to 58.5 volts DC, but
automatically limited to one volt below the High Voltage Shutdown setting. Adjustment
is made via the MCA. Factory set at 56.5 volts DC.
(3) The minimum voltage limit in volts DC. Adjustable from float down to 44 volts DC.
Adjustment is made via the MCA. Factory set at 50.0 volts DC.
Page 72 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
3.1.2
Current: One hundred amperes (100A) per Rectifier Module.
3.1.3
Output Power: 5800W @ Vout > 48VDC.
3.1.4
Output Characteristics: The relationship between output voltage and current is summarized in
the following table and depicted graphically in the following illustration.
Output
Power
Output
Current
Output
Voltage
5800 W
5800 W
100.0 A
121.0 A
58 VDC
48 VDC
Output Voltage (V)
Output Voltage vs. Output Current,
Max. Output Power 5800 W
70
60
50
40
30
20
10
0
0
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160
Output Current (A)
3.1.5
Power Derating Based on Input Voltage: The Rectifier Module power varies with changes in
input voltage and output voltage. It uses an advanced power limitation method. The Rectifier
Module can provide its maximum rated power (5800W) as long as the input voltage is within the
range of 304 to 530 VAC (hysteresis is less than 3V). Below 304 VAC (and down to 260 VAC),
the Rectifier Module will continue to operate normally but will be in a power derating mode. The
relationship between the output power and input voltage is illustrated in the following illustration.
Note: As depicted in the following illustration, the output power will derate from 100% of the
rated capacity as the input voltage drops below 304 VAC, and to 50% of the rated
capacity as the input voltage falls to 260 VAC.
% of max. output power
Output Power vs. Input Voltage at Tamb < 45 C
120
100
80
60
40
20
0
250
275
300
325
350
375
400
425
450
475
500
525
550
Input Voltage (VAC)
Page 73 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
3.1.6
Power Derating Based on Temperature: The Rectifier Module delivers full power
when operating at an ambient temperature of +45C (+113F) or below. Refer to the
following illustration to view the relationship between the output power and the ambient
temperature.
Home
Other power rating values are as follows:

At an ambient temperature of +50C (+122°F), the power delivered by the Rectifier Module
is greater than 5400W.

At an ambient temperature of +55C (+131F), the power delivered by the Rectifier Module
is greater than 4640W.
Output power vs. Temperature at Uin > 304 VAC
% of output power
120
100
80
60
40
20
0
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
Temperature (C)
3.1.7
Regulation (Rectifier Module)
(A) Voltage Regulation: ≤±1%
(B) Load Regulation: ≤±0.5%
(C) Line Regulation: ≤±0.1%
(D) Overshoot at Startup: ≤±1%
(E) Dynamic Response (at rated input and output voltage values):
3.1.8

Response time is ≤200 s, and the overshoot is ≤5% for load changes at 50%-25%-50%
and 50%-75%-50%.

Overshoot or undershoot is ≤5% and within ±1% of the regulation band, ≤4 ms at 50 s
for load changes at 10%-90% and 90%-10%.
Regulation (via MCA)
(A) Static: The MCA controls the steady state output voltage to within ±0.5% of any voltage
setting within the range of 44.0 to 58.0 volts DC for any and all combinations of load from no
load to full load, input voltage, and input frequency at a constant ambient temperature. If the
MCA's regulation feature is disabled for any reason, steady state regulation is ±1.0% as
controlled within the Rectifier Modules.
(B) Dynamic Response: For any step load change from 10% to 90% or from 90% to 10% of
full rated load within 250 microseconds, shall not cause the voltage measured at the output
to overshoot or undershoot more than 5% of the regulated output level within 1 millisecond.
The output voltage must return and stay within the ±1% regulation band within 4 milliseconds
and within the ±0.5% regulation band within 3 seconds.
Page 74 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Any step change of the line voltage within the limits specified in Paragraph 3.2.1
shall not cause the output voltage to deviate outside the ±0.5% regulation band.
3.1.9
Filtering (with or without battery): Typical readings were taken at nominal input voltage,
nominal output voltage, 50% load, and 25 degrees C ambient.
(A) Voice Band Noise: Complies with Telcordia GR-947_CORE.
(1) Typically 20.4 dBrn C-message weighting. Does not exceed 32 dBrn C.
(2) Typically 0.28 millivolts psophometric. Does not exceed 1 millivolt psophometric.
(B) Wide Band Noise: Complies with Telcordia GR-947_CORE.
(1) Typically 55 millivolts peak-to-peak. Does not exceed 200 millivolts peak-to-peak
(2) Typically 15.9 millivolts rms. Does not exceed 100 millivolts rms.
3.1.10 Hold Up Time: 10 ms (The DC voltage is allowed to decrease to 42V from 54V during the test.)
3.2
AC Input Ratings
3.2.1
Voltage: Nominal 380/480 volts AC, three phase, 50/60 Hz, with an operating range of 260 to
530 volts. Acceptable input frequency range is 45 to 65 Hz.
Maximum non-destructive input voltage when rectifier is not operating: 600 VAC
3.2.2
Current: <13A @ 5800 W, and at an input voltage of 260 VAC.
3.2.3
THD (Total Harmonic Distortion): ≤5% when loaded at 50 to 100% of the rated output power.
3.2.4
Inrush Current: <150% of the rated input steady-state peak value.
3.2.5
Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
408
1
480
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Power
Loss
Watts
0
0.50
356
101
28.4
--
101.2
25
2.23
1576
1494
94.8
89.6
155.5
50
4.15
2930
2883
98.3
92.8
208.0
75
6.14
4337
4317
99.5
92.9
307.4
100
8.18
5783
5771
99.8
92.7
423.5
110
9.01
6368
6359
99.8
92.4
483.0
0
0.56
481
98
20.3
--
97.8
25
1.95
1619
1487
91.8
90.0
148.0
50
3.54
2944
2876
97.8
93.0
201.0
75
5.22
4338
4313
99.4
93.0
299.8
100
6.95
5776
5757
99.6
92.9
409.7
110
7.64
6354
6341
99.8
92.7
465.5
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 93% at best point, 91% at full load and nominal input
voltage.
Page 75 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
(D) Maximum Input Current: 9.1A at 100% of full load with output adjusted to 58 volts
DC as measured at the shelf output terminals, and input voltage as shown.
3.2.6
Home
Typical Input Data: 50 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
323
1
380
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Power
Loss
Watts
0
0.36
204
99
48.8
--
99.0
25
2.79
1558
1505
96.7
88.9
166.4
50
5.20
2910
2896
99.5
92.4
221.0
75
7.77
4347
4341
99.8
92.4
331.5
100
10.40
5818
5811
99.8
92.0
463.7
110
11.47
6418
6410
99.8
91.7
534.0
0
0.40
262
96
36.5
--
96.0
25
2.41
1586
1497
94.3
89.4
158.3
50
4.44
2925
2886
98.7
92.7
211.0
75
6.60
4340
4324
99.6
92.8
313.5
100
8.80
5789
5781
99.8
92.5
432.7
110
9.70
6386
6378
99.8
92.2
499.8
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 92.75% at best point, 91% at full load and nominal input
voltage.
(D) Maximum Input Current: 11.6A at 100% of full load with output adjusted to 58 volts DC as
measured at the shelf output terminals, and input voltage as shown.
3.3
Environmental Ratings
3.3.1
Operating Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F)
(A) Full rated output power of 5800 W for temperatures -40°C to +45°C (-40°F to +113°F).
(B) Power limitation for temperatures higher than +45°C (+113°F).
3.3.2
Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
3.3.3
Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
3.3.4
Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
3.3.5
Acoustic Noise: ≤50dB(A), measured at a distance of 0.6 m from the rectifier.
3.3.6
Insulation Resistance and Dielectric Strength
(A) Insulation Resistance

Between the AC input and the enclosure: 20x106 

Between the AC input and the DC output: 20x106 
Page 76 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)

SAG582140001
Issue AF, July 14, 2010
Between the DC output and the enclosure: 20x106 
Home
(B) Dielectric Strength

Between the AC input and the enclosure: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 2120 V.

Between the AC input and the DC output: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 4242 V.

Between the DC output and the enclosure: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 707 V.

Between the DC output and the ground: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 1500 V (with the varistor and filter
capacitors removed before doing the test).
3.3.7
Surge Protection: Complies with IEEE C62 41-1991 Class B3, 6kV/3kA (1.2/50 s surge
voltage and 8/20 s surge current).
3.3.8
Compliance Information
(A) Safety and EMC: The rectifier has been recognized to meet the UL/EN/IEC 60950-2000
safety standard and is CE marked. The rectifier also meets the latest EMC requirements, as
listed in the following table.
Page 77 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Item
Standard
EN61000-4-5
Surge
Immunity
EFT
AC Port: 4kV/2Ω
6kV/12Ω for com.
DC Port: 800V/2Ω
CAN Bus: 1kV diff. /
2kV com.
GR-1089-CORE
R4-8, R4-9,
R4-24, R-25
EN 61000-4-4
AC and DC Port: 4kV
CAN Bus: 1kV
GR-1089-CORE
O2-8
EN 61000-4-2 and
Conducted
immunity
GR-1089-CORE
Radiated
immunity
EN 61000-4-6
GR-1089-CORE
8kV/15kV
R2-1, R2-2,
R2-3, O2-4
3Vrms 0.15-80MHz
R3-15,
CO3-16, R3-17
10V 80-2GHz
R3-11, CR3-12
Mains
frequency
Magnetic
fields
immunity
EN 61000-4-8
30A/m
Conducted
emissions
EN 55022
CFR 47 Part 15
GR-1089-CORE
R3-5 (Class B)
Conducted
current
emissions
GR-1089-CORE
R3-6
ESD
GR-1089-CORE
EN 61000-4-6
EN 55022
Radiated
emissions
3.4
Class
CFR 47 Part 15
GR-1089-CORE
Class B
Class B
R3-1,
R3-4 (Class B)
Standard Features
3.4.1
Type of Power Conversion Circuit: High frequency.
3.4.2
Float Charging Output Mode: In this mode of operation, system output voltage is constant and
output current does not exceed the current limit setting. During normal operation, the battery is
not required to furnish load current and remains in a fully charged condition.
The float voltage setting can be checked and/or adjusted without removing a Rectifier Module or
affecting the load. One adjustment changes the output of all Rectifier Modules.
Page 78 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Note: If the current demanded by the load exceeds the current limit setting of the
system, the battery is required to furnish the difference in load current and
begins discharging.
Home
Note: If the system is used with a digital battery charge temperature compensation probe, the
MCA automatically adjusts system output. This ensures proper voltage to the battery as
battery ambient temperature fluctuates.
3.4.3
Test/Equalize Charging Output Mode: This mode of operation is used if higher output voltage
is required for equalizing the charge on all battery cells of a conventional flooded cell battery, or
for recharging the battery following a commercial power failure.
If the installation site does not require system equalize mode of operation, the equalize feature
can be used as a test feature. System equalize voltage can be adjusted to a test voltage value.
Placing the system into the test/equalize mode causes system output voltage to increase or
decrease to this test voltage value.
The test/equalize voltage setting can be checked and/or adjusted without removing a Rectifier
Module or affecting the load. One adjustment changes the output of all Rectifier Modules.
Note: If the system is used with a battery charge temperature compensation probe, typical
equalize mode of operation is not used.
3.4.4
Output Mode of Operation Selection: There are four methods of placing the system from the
float mode to the test/equalize mode.
(A) Method 1 (Manual Test/Equalize): A user manually places the system into the
test/equalize mode via the MCA interface. A user must manually return the system to the
float mode via the MCA interface.
(B) Method 2 (Manually Initiated Timed Test/Equalize): A user manually places the system
into the test/equalize mode via the MCA interface. The system automatically returns to the
float mode after a preset programmable time period (1-99 hours, in increments of one hour).
(C) Method 3 (Automatic Test/Equalize):
THE AUTOMATIC EQUALIZE FEATURE IS INTENDED FOR USE ONLY WITH WET
CELL BATTERIES. USING THIS FEATURE WITH VALVE REGULATED BATTERIES IS
NOT RECOMMENDED.
This feature can be enabled or disabled by a user via the MCA. The default state is
disabled.
The Automatic Equalize feature is a time based function that is controlled by a customer
selectable multiplier and by the Battery on Discharge (BOD) alarm setpoint. The MCA’s
default setting is for a multiplier of zero, which disables the Automatic Equalize feature.
When the Automatic Equalize feature is enabled, if system voltage drops to less than the
BOD alarm setpoint, the MCA initiates a timing cycle to measure the discharge time period.
The MCA requires at least 15 minutes of continuous BOD alarm in order to prevent
nuisance equalization cycles. When system voltage rises to above the BOD alarm
setpoint, the MCA ends the discharge timing cycle and (assuming a minimum of 15
minutes has elapsed) places the Rectifier Modules into the equalize mode for a customer
selectable multiple of the discharge time period (the discharge time period includes the
initial 15 minutes).
The equalize time period can be set for 0 to 15 times the discharge time period, up to a
maximum of 300 hours. A zero (0) setting disables the feature.
(D) Method 4 (External Test/Equalize): A user (or external equipment) places the system into
the test/equalize mode by applying an external signal to the system. The system returns to
the float mode when the external signal is removed. This method overrides the other three
methods.
Page 79 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
3.4.5
Home
Input Protection: Lists 1 and 9 provide connections for twenty-four (24) AC input
branch circuits (one per Rectifier Module mounting position). Lists 2 and 10 provide
connections for two (2) AC input branch circuits (two per Power Bay). Customer to provide AC
input branch circuit protection.
(A) Input Over/Under Voltage Protection: The Rectifier Module shuts down and its protection
indicator (yellow) illuminates when the input voltage is lower than 260VAC or higher than
530VAC. This condition is reported to the power system controller and the power system
controller processes the alarms accordingly.
(B) Input Fusing: Input fusing is provided in each Rectifier Module. This fusing is not customer
replaceable.
3.4.6
Output Protection
(A) Current Limiting: The maximum current delivered by the system can be programmed from
10% to 110% of total system capacity. The MCA automatically adjusts the current limit
circuit on each Rectifier Module so that this value is not exceeded. If a Rectifier Module
fails, the MCA automatically resets each remaining Rectifier Module's current limit point to
maintain this value. The MCA also insures that the current limit circuit on any Rectifier
Module is not set above 110% of its capacity. The default current limit setting is the sum of
each installed Rectifier Module's output rating. If an additional Rectifier Module is added to
the system, the system current limit is automatically increased by the rating of the new
Rectifier Module and the new current limit value is displayed.
The current limiting point can be adjusted without removing a Rectifier Module. One
adjustment changes the setting of all Rectifier Modules.
The current limit is factory set at 100% of rated full load, unless otherwise specified.
(B) Output Fusing: Output fusing is provided in each Rectifier Module. If a fuse opens, local
and remote Rectifier Module Fail Alarms activate. This fusing is not customer replaceable.
(C) High Voltage Shutdown
(1) Internal: If Rectifier Module output voltage exceeds an adjustable preset value, the
Rectifier Module shuts down.
After approximately 5 seconds, the Rectifier Module automatically restarts. If Rectifier
Module output voltage again exceeds the high voltage shutdown value within 5 minutes,
the Rectifier Module shuts down and locks out. Manual restart is then required. If the
Rectifier Module does not experience a high voltage condition within the 5 minute time
period, the restart circuit is reset.
If two or more Rectifier Modules are installed in the Power Bay, or if the Power Bay is
paralleled with other Power Bays, only the Rectifier Module causing the high voltage
condition shuts down.
The high voltage shutdown point can be checked and/or adjusted without removing a
Rectifier Module. One adjustment changes the setting of all Rectifier Modules.
Adjustable from 56.0 to 59.0 volts DC. Factory set at 57.50 volts, unless otherwise
specified.
(2) Remote: See Paragraph 4.1.14 (B).
(3) Backup: If Rectifier Module output voltage exceeds a second (non-adjustable) value,
the Rectifier Module shuts down and locks out regardless of load. Manual restart is
then required. The fixed hardware HVSD is 59.5V (within the range of 58.5 to 60V).
Page 80 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
3.4.7
SAG582140001
Issue AF, July 14, 2010
Home
High Temperature Protection:
(A) When the PFC board temperature is higher than 85°C, the rectifier turns off. When the PFC
board temperature is lower than 75°C, the rectifier resumes to normal operation, and the
hysteresis is at least 10°C.
(B) When the “ambient temperature – PFC board temperature” is higher than 5°C, the rectifier
turns off. When the “ambient temperature – PFC board temperature” is lower than 2°C, the
rectifier resumes to normal operation, and the hysteresis is at least 3°C.
(C) When the DC board temperature is higher than 105°C, the rectifier turns off. When the DC
board temperature is lower than 95°C, the rectifier resumes to normal operation, and the
hysteresis is at least 10°C.
3.4.8
Fan Fault Protection: An alarm will be generated upon a fan fault. In such cases, the fault
indicator (red) on the Rectifier Module front panel will flash and the Rectifier Module will also
inhibit its output. Auto-recovery is enabled upon the clearing of the corresponding fault.
3.4.9
PFC Over/Under Voltage: The rectifier will shut down when its bus voltage is higher than the
over voltage set point or is lower than the under voltage set point. During such conditions, the
rectifier does not output any power and its protection indicator (yellow) will light up.
3.4.10 Load Sharing (via MCA): The MCA load sharing feature automatically balances the load. If the
MCA's load sharing feature is disabled for any reason, pre-programmed slope control in each
Rectifier Module balances the load. The MCA's load sharing feature is disabled whenever the
system is in current limit, the system is delivering more than 97% capacity, or the system is
delivering less than 3% capacity.
Active Load Sharing (Rectifier Module): The Rectifier Module uses advanced digital active
load sharing technology that maintains balancing to within ±3A. The difference in the average
current between rectifiers is <±3A for loads in the 10 to 100% range.
3.4.11 Startup Time: The Rectifier Module has two startup modes:
(A) Normal Soft Start Time: The duration from the time when the rectifier is powered on to the
time when the rectifier provides output voltage is 8s.
(B) Current Walk-In: The rise time of the rectifier output voltage is 8s at 90% of the rated
load, and the maximum time is 90s at 100% of the rated load.
3.4.12 Hot Swappable: The Rectifier Module is designed to be plug-and-play. The Rectifier Module
can be inserted or removed from a live DC power system with no damage. When the Rectifier
Module is plugged into the system, the system output voltage will not be affected.
3.4.13 Cooling: Each Rectifier Module contains a fan for forced convection cooling.
3.4.14 Fan Control: When the PFC bus voltage is within a normal range, the built-in processor adjusts
the fan’s speed according to the Rectifier Module’s internal temperature and output current. For
example, a higher temperature or output current will increase the fan speed. Above 45°C at full
load, the fan operates at full speed. When the PFC bus voltage is abnormal, such as very low
bus voltage, the fan turns off.
3.4.15 Communication Failure: The Rectifier Module’s protection indicator (yellow) will flash should it
experience a communication failure. The failure information will be reported to the Controller
and the Controller will process the failure accordingly. During a communication failure, in order
to protect the battery, the Rectifier Module output voltage will automatically adjust to 53.5 V (this
is a default value which can be modified using the Controller). The Rectifier Module will revert to
normal operation once normal communication is restored.
3.4.16 Unbalance of Rectifier Module Output Current: When the output current of the Rectifier
Modules in a DC power system is unbalanced, the Rectifier Module having the unbalanced
output current will be identified automatically and its protection indicator (yellow) will turn on.
Page 81 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
The failure information will be reported to the Controller and the Controller will process
the failure accordingly.
Home
3.4.17 Paralleling: This system may be connected in parallel with any rectifier of the same polarity and
adjusted to the same output voltage.
3.4.18 Monitoring Function: The Rectifier Module has a built-in advanced DSP that monitors and
controls the operation of the Rectifier Module. The DSP also communicates with the Controller
in real time through the CAN bus. The following table lists the different commands and
information exchanged between the Rectifier Module and the Controller.
Commands / signals that can be
received by the Rectifier Module
from the Controller.
Information gathered by the
Controller from the Rectifier
Module.

Turn on/off

Input voltage

Current walk-in on/off

Output voltage

HVSD reset

Output current

Current limit adjustment

Current limit setting

Voltage regulation

Temperature

Over voltage setting

On/off status

Fault alarms, such as:
HVSD
Fan fail

Protection alarms, such as:
Input voltage protection
Inner DC bus voltage protection
High temperature protection

Thermal derating

AC derating

AC fail

Unbalanced output current

Address

Code

Date

SW version

HW version
3.4.19 Dimensions:
Millimeters: 87.5 (Height) X 243.5 (Width) X 371.5 (Depth).
Inches:
3.44 (Height) X 9.59 (Width) X 14.63 (Depth).
3.4.20 Weight: < 8 kg (17.6 lbs).
3.4.21 Local Status and Alarm Indicators: Refer to the "Operating Procedures" chapter in the Power
System User Instructions (Section 6017) for a complete description.
(A) Power (Green)
(B) Protection (Yellow)
Page 82 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
(C) Alarm (Red)
(D) A 10-segment Green LED is located on the front panel to represent output current, each
segment represents 10A.
4. RECTIFIER MODULE (MODEL R48-5800L, SPEC. NO. 1R485800L)
4.1
DC Output Ratings
4.1.1
Voltage: Nominal -48 volts DC, Positive Ground.
(A) Without Battery Charge Temperature Compensation: Float voltage is adjustable from
47.00 to 58.00 volts DC. Test/equalize voltage is adjustable from 45.00 to 58.00 volts DC.
Adjustment is made via the MCA. Both float and test/equalize voltages are factory set at
52.00 volts, unless otherwise specified. The output voltage temperature coefficient (1/°C)
does not exceed 0.01% per degree centigrade from 0°C to +40°C.
(B) With Battery Charge Digital Temperature Compensation Probe: With an optional battery
charge digital temperature compensation probe installed, the MCA automatically increases
or decreases the output voltage as battery ambient temperature decreases or increases,
respectively. Float voltage is factory set at approximately 54.48 volts at 25C battery
ambient. The float and test/equalize voltage range is the same as without battery charge
temperature compensation. Using battery and equipment manufacturers’ recommendations,
the user selects the following temperature compensation curve parameters via the MCA.
Refer to "Typical Float Charge Thermal Characteristics Using Optional Battery Charge
Digital Temperature Compensation Probe" in Battery Charge Temperature Compensation
Probe for Digital Compensation under ACCESSORY DESCRIPTIONS.
(1) The temperature compensation slope in volts/C. Adjustable from zero to 200
millivolts/C. Adjustment is made via the MCA. Factory set at 0V/C (DIGITAL TC
OFF).
(2) The maximum voltage limit in volts DC. Adjustable from float up to 58.5 volts DC, but
automatically limited to one volt below the High Voltage Shutdown setting. Adjustment
is made via the MCA. Factory set at 56.5 volts DC.
(3) The minimum voltage limit in volts DC. Adjustable from float down to 44 volts DC.
Adjustment is made via the MCA. Factory set at 50.0 volts DC.
4.1.2
Current: One hundred amperes (100A) per Rectifier Module.
4.1.3
Output Power: 5800W @ Vout > 48VDC.
4.1.4
Output Characteristics: The relationship between output voltage and current is summarized in
the following table and depicted graphically in the following illustration.
Output
Power
Output
Current
Output
Voltage
5800 W
5800 W
100.0 A
121.0 A
58 VDC
48 VDC
Page 83 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Output voltage vs. output current,
max. output power 5800 W
Output voltage (V)
70
60
50
40
30
20
10
0
0
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160
Output current (A)
4.1.5
Power Derating Based on Input Voltage: The Rectifier Module power varies with changes in
input voltage and output voltage. It uses an advanced power limitation method. The Rectifier
Module can provide its maximum rated power (5800W) as long as the input voltage is within the
range of 176 to 264 VAC (hysteresis is less than 3V). Below 176 VAC (and down to 145 VAC),
the Rectifier Module will continue to operate normally but will be in a power derating mode. The
relationship between the output power and input voltage is illustrated in the following illustration.
Note: As depicted in the following illustration, the output power will derate from 100% of the
rated capacity as the input voltage drops below 176 VAC, and to 50% of the rated
capacity as the input voltage falls to 145 VAC.
% of max. output power
Output power vs. input voltage at Tamb < 45 C
120
100
80
60
40
20
0
140
150
160
170
180
190
200
210
220
230
240
250
260
270
Input voltage (VAC)
4.1.6
Power Derating Based on Temperature: The Rectifier Module delivers full power when
operating at an ambient temperature of +45C (+113F) or below. Refer to the following
illustration to view the relationship between the output power and the ambient temperature.
Other power rating values are as follows:

At an ambient temperature of +50C (+122°F), the power delivered by the Rectifier Module
is greater than 5400W.
Page 84 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)

SAG582140001
Issue AF, July 14, 2010
Home
At an ambient temperature of +55C (+131F), the power delivered by the
Rectifier Module is greater than 4640W.
Output power vs. Temperature at Uin > 166 VAC
% of output power
120
100
80
60
40
20
0
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
Temperature (C)
4.1.7
Regulation (Rectifier Module)
(A) Voltage Regulation: ≤±1%
(B) Load Regulation: ≤±0.5%
(C) Line Regulation: ≤±0.1%
(D) Overshoot at Startup: ≤±1%
(E) Dynamic Response (at rated input and output voltage values):
4.1.8

Response time is ≤200 s, and the overshoot is ≤5% for load changes at 50%-25%-50%
and 50%-75%-50%.

Overshoot or undershoot is ≤5% and within ±1% of the regulation band, ≤4 ms at 50 s
for load changes at 10%-90% and 90%-10%.
Regulation (via MCA)
(A) Static: The MCA controls the steady state output voltage to within ±0.5% of any voltage
setting within the range of 44.0 to 58.0 volts DC for any and all combinations of load from no
load to full load, input voltage, and input frequency at a constant ambient temperature. If the
MCA's regulation feature is disabled for any reason, steady state regulation is ±1.0% as
controlled within the Rectifier Modules.
(B) Dynamic Response: For any step load change from 10% to 90% or from 90% to 10% of
full rated load within 250 microseconds, shall not cause the voltage measured at the output
to overshoot or undershoot more than 5% of the regulated output level within 1 millisecond.
The output voltage must return and stay within the ±1% regulation band within 4 milliseconds
and within the ±0.5% regulation band within 3 seconds.
Any step change of the line voltage within the limits specified in Paragraph 3.2.1 shall not
cause the output voltage to deviate outside the ±0.5% regulation band.
4.1.9
Filtering (with or without battery): Typical readings were taken at nominal input voltage,
nominal output voltage, 50% load, and 25 degrees C ambient.
(A) Voice Band Noise: Complies with Telcordia GR-947_CORE.
(1) Typically 23 dBrn C-message weighting. Does not exceed 32 dBrn C.
(2) Typically 0.335 millivolts psophometric. Does not exceed 1 millivolt psophometric.
Page 85 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
(B) Wide Band Noise: Complies with Telcordia GR-947_CORE.
(1) Typically 45.4 millivolts peak-to-peak. Does not exceed 200 millivolts peak-to-peak
(2) Typically 15.9 millivolts rms. Does not exceed 100 millivolts rms.
4.1.10 Hold Up Time: 10 ms (The DC voltage is allowed to decrease to 42V from 54V during the test.)
4.2
AC Input Ratings
4.2.1
Voltage: Nominal 208 volts AC, three phase, 50/60 Hz, with an operating range of 176 to 264
volts. Acceptable input frequency range is 45 to 65 Hz.
Maximum non-destructive input voltage when rectifier is not operating: 600 VAC
4.2.2
Current: <18A @ 5800 W, and at an input voltage of 176 VAC.
4.2.3
THD (Total Harmonic Distortion): ≤5% when loaded at 50 to 100% of the rated output power.
4.2.4
Inrush Current: <150% of the rated input steady-state peak value.
4.2.5
Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
176
1
208
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Power
Loss
Watts
0
0.4135
128.32
111.48
76.9
0.78
110.6
25
5.139
1579.5
1522.7
96.9
89.12
165.62
50
9.571
2929
2922
99.7
92.03
232.82
75
14.476
4408
4405
99.9
91.43
377.6
100
19.651
5957
5950
99.8
91.04
509.4
110
21.68
6562
6552
99.8
90.09
578.4
120
21.89
6620
6608
99.8
89.17
638.1
0
0.3972
142.76
110.25
78.4
0.79
109.4
25
4.333
1570
1526
97.2
88.93
168.97
50
8.114
2930
2903
99.2
92.62
214.34
75
12.142
4371
4365
99.8
91.80
357.7
100
16.38
5873
5870
99.9
91.32
509.4
110
18.127
6489
6487
99.9
91.08
578.4
120
18.283
6545
6542
99.9
90.02
638.1
(B) Typical Power Factor: Greater than or equal to 99.2% for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 92.62% at best point, 90.25% at full load and nominal input
voltage.
(D) Maximum Input Current: 21.92A at 100% of full load with output adjusted to 58 volts DC
as measured at the shelf output terminals, and input voltage as shown.
Page 86 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
4.2.6
SAG582140001
Issue AF, July 14, 2010
Home
Typical Input Data: 50 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
176
1
208
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Power
Loss
Watts
0
0.4278
131.7
119.85
76.1
1.27
118.3
25
5.112
1569.8
1522.7
96.9
89.13
165.47
50
9.577
2930
2922
99.7
92.04
232.72
75
14.472
4409
4405
99.9
91.43
377.38
100
19.64
5957
5950
99.8
91.04
532.93
110
21.82
6601
6590
99.8
90.47
627.86
120
21.86
6613
6602
99.8
89.98
661.18
0
0.3572
136.7
106.8
76.3
0.62
106.14
25
4.347
1573.1
1527.6
97.9
88.8
171.07
50
8.112
2926
2905
99.2
92.55
216.43
75
12.154
4371
4365
99.6
91.79
358.42
100
16.383
5872
5869
99.9
91.41
504.2
110
18.125
6488
6485
99.9
90.48
617.14
120
18.271
6541
6537
99.9
90.08
648.52
(B) Typical Power Factor: Greater than or equal to 99.2% for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 92.55% at best point, 90.08% at full load and nominal input
voltage.
(D) Maximum Input Current: 21.89A at 100% of full load with output adjusted to 58 volts DC
as measured at the shelf output terminals, and input voltage as shown.
4.3
Environmental Ratings
4.3.1
Operating Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F)
(A) Full rated output power of 5800 W for temperatures -40°C to +45°C (-40°F to +113°F).
(B) Power limitation for temperatures higher than +45°C (+113°F).
4.3.2
Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
4.3.3
Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
4.3.4
Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
4.3.5
Acoustic Noise: ≤50dB(A), measured at a distance of 0.6 m from the rectifier.
4.3.6
Insulation Resistance and Dielectric Strength
(A) Insulation Resistance

Between the AC input and the enclosure: 20x106 

Between the AC input and the DC output: 20x106 
Page 87 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010

Between the DC output and the enclosure: 20x106 
Home
(B) Dielectric Strength

Between the AC input and the enclosure: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 2120 V.

Between the AC input and the DC output: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 4242 V.

Between the DC output and the enclosure: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 707 V.

Between the DC output and the ground: the leakage current is 1 mA, with no
breakdown within 1 minute using an applied voltage of 1500 V (with the varistor and filter
capacitors removed before doing the test).
4.3.7
Surge Protection: Complies with IEEE C62 41-1991 Class B3, 6kV/3kA (1.2/50 s surge
voltage and 8/20 s surge current).
4.3.8
Compliance Information
(A) Safety and EMC: The rectifier has been recognized to meet the UL/EN/IEC 60950-2000
safety standard and is CE marked. The rectifier also meets the latest EMC requirements, as
listed in the following table.
Page 88 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Item
Standard
EN61000-4-5
Surge
Immunity
EFT
AC Port: 4kV/2Ω
6kV/12Ω for com.
DC Port: 800V/2Ω
CAN Bus: 1kV diff. /
2kV com.
GR-1089-CORE
R4-8, R4-9,
R4-24, R-25
EN 61000-4-4
AC and DC Port: 4kV
CAN Bus: 1kV
GR-1089-CORE
O2-8
EN 61000-4-2 and
Conducted
immunity
GR-1089-CORE
Radiated
immunity
EN 61000-4-6
GR-1089-CORE
8kV/15kV
R2-1, R2-2,
R2-3, O2-4
3Vrms 0.15-80MHz
R3-15,
CO3-16, R3-17
10V 80-2GHz
R3-11, CR3-12
Mains
frequency
Magnetic
fields
immunity
EN 61000-4-8
30A/m
Conducted
emissions
EN 55022
CFR 47 Part 15
GR-1089-CORE
R3-5 (Class B)
Conducted
current
emissions
GR-1089-CORE
R3-6
ESD
GR-1089-CORE
EN 61000-4-6
EN 55022
Radiated
emissions
4.4
Class
CFR 47 Part 15
GR-1089-CORE
Class B
Class B
R3-1,
R3-4 (Class B)
Standard Features
4.4.1
Type of Power Conversion Circuit: High frequency.
4.4.2
Float Charging Output Mode: In this mode of operation, system output voltage is constant and
output current does not exceed the current limit setting. During normal operation, the battery is
not required to furnish load current and remains in a fully charged condition.
The float voltage setting can be checked and/or adjusted without removing a Rectifier Module or
affecting the load. One adjustment changes the output of all Rectifier Modules.
Page 89 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Note: If the current demanded by the load exceeds the current limit setting of the
system, the battery is required to furnish the difference in load current and
begins discharging.
Home
Note: If the system is used with a digital battery charge temperature compensation probe, the
MCA automatically adjusts system output. This ensures proper voltage to the battery as
battery ambient temperature fluctuates.
4.4.3
Test/Equalize Charging Output Mode: This mode of operation is used if higher output voltage
is required for equalizing the charge on all battery cells of a conventional flooded cell battery, or
for recharging the battery following a commercial power failure.
If the installation site does not require system equalize mode of operation, the equalize feature
can be used as a test feature. System equalize voltage can be adjusted to a test voltage value.
Placing the system into the test/equalize mode causes system output voltage to increase or
decrease to this test voltage value.
The test/equalize voltage setting can be checked and/or adjusted without removing a Rectifier
Module or affecting the load. One adjustment changes the output of all Rectifier Modules.
Note: If the system is used with a battery charge temperature compensation probe, typical
equalize mode of operation is not used.
4.4.4
Output Mode of Operation Selection: There are four methods of placing the system from the
float mode to the test/equalize mode.
(A) Method 1 (Manual Test/Equalize): A user manually places the system into the
test/equalize mode via the MCA interface. A user must manually return the system to the
float mode via the MCA interface.
(B) Method 2 (Manually Initiated Timed Test/Equalize): A user manually places the system
into the test/equalize mode via the MCA interface. The system automatically returns to the
float mode after a preset programmable time period (1-99 hours, in increments of one hour).
(C) Method 3 (Automatic Test/Equalize):
THE AUTOMATIC EQUALIZE FEATURE IS INTENDED FOR USE ONLY WITH WET
CELL BATTERIES. USING THIS FEATURE WITH VALVE REGULATED BATTERIES IS
NOT RECOMMENDED.
This feature can be enabled or disabled by a user via the MCA. The default state is
disabled.
The Automatic Equalize feature is a time based function that is controlled by a customer
selectable multiplier and by the Battery on Discharge (BOD) alarm setpoint. The MCA’s
default setting is for a multiplier of zero, which disables the Automatic Equalize feature.
When the Automatic Equalize feature is enabled, if system voltage drops to less than the
BOD alarm setpoint, the MCA initiates a timing cycle to measure the discharge time period.
The MCA requires at least 15 minutes of continuous BOD alarm in order to prevent
nuisance equalization cycles. When system voltage rises to above the BOD alarm
setpoint, the MCA ends the discharge timing cycle and (assuming a minimum of 15
minutes has elapsed) places the Rectifier Modules into the equalize mode for a customer
selectable multiple of the discharge time period (the discharge time period includes the
initial 15 minutes).
The equalize time period can be set for 0 to 15 times the discharge time period, up to a
maximum of 300 hours. A zero (0) setting disables the feature.
(D) Method 4 (External Test/Equalize): A user (or external equipment) places the system into
the test/equalize mode by applying an external signal to the system. The system returns to
the float mode when the external signal is removed. This method overrides the other three
methods.
Page 90 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
4.4.5
SAG582140001
Issue AF, July 14, 2010
Home
Input Protection: Lists 1 and 9 provide connections for twenty-four (24) AC input
branch circuits (one per Rectifier Module mounting position). Lists 2 and 10 provide
connections for two (2) AC input branch circuits (two per Power Bay). Customer to provide AC
input branch circuit protection.
(A) Input Over/Under Voltage Protection: The Rectifier Module shuts down and its protection
indicator (yellow) illuminates when the input voltage is lower than 260VAC or higher than
530VAC. This condition is reported to the power system controller and the power system
controller processes the alarms accordingly.
(B) Input Fusing: Input fusing is provided in each Rectifier Module. This fusing is not customer
replaceable.
4.4.6
Output Protection
(A) Current Limiting: The maximum current delivered by the system can be programmed from
10% to 110% of total system capacity. The MCA automatically adjusts the current limit
circuit on each Rectifier Module so that this value is not exceeded. If a Rectifier Module
fails, the MCA automatically resets each remaining Rectifier Module's current limit point to
maintain this value. The MCA also insures that the current limit circuit on any Rectifier
Module is not set above 110% of its capacity. The default current limit setting is the sum of
each installed Rectifier Module's output rating. If an additional Rectifier Module is added to
the system, the system current limit is automatically increased by the rating of the new
Rectifier Module and the new current limit value is displayed.
The current limiting point can be adjusted without removing a Rectifier Module. One
adjustment changes the setting of all Rectifier Modules.
The current limit is factory set at 100% of rated full load, unless otherwise specified.
(B) Output Fusing: Output fusing is provided in each Rectifier Module. If a fuse opens, local
and remote Rectifier Module Fail Alarms activate. This fusing is not customer replaceable.
(C) High Voltage Shutdown
(1) Internal: If Rectifier Module output voltage exceeds an adjustable preset value, the
Rectifier Module shuts down.
After approximately 5 seconds, the Rectifier Module automatically restarts. If Rectifier
Module output voltage again exceeds the high voltage shutdown value within 5 minutes,
the Rectifier Module shuts down and locks out. Manual restart is then required. If the
Rectifier Module does not experience a high voltage condition within the 5 minute time
period, the restart circuit is reset.
If two or more Rectifier Modules are installed in the Power Bay, or if the Power Bay is
paralleled with other Power Bays, only the Rectifier Module causing the high voltage
condition shuts down.
The high voltage shutdown point can be checked and/or adjusted without removing a
Rectifier Module. One adjustment changes the setting of all Rectifier Modules.
Adjustable from 56.0 to 59.0 volts DC. Factory set at 57.50 volts, unless otherwise
specified.
(2) Remote: See Paragraph 4.1.14 (B).
(3) Backup: If Rectifier Module output voltage exceeds a second (non-adjustable) value,
the Rectifier Module shuts down and locks out regardless of load. Manual restart is
then required. The fixed hardware HVSD is 59.5V (within the range of 58.5 to 60V).
Page 91 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
4.4.7
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
High Temperature Protection:
(A) When the PFC board temperature is higher than 85°C, the rectifier turns off. When the PFC
board temperature is lower than 75°C, the rectifier resumes to normal operation, and the
hysteresis is at least 10°C.
(B) When the “ambient temperature – PFC board temperature” is higher than 5°C, the rectifier
turns off. When the “ambient temperature – PFC board temperature” is lower than 2°C, the
rectifier resumes to normal operation, and the hysteresis is at least 3°C.
(C) When the DC board temperature is higher than 105°C, the rectifier turns off. When the DC
board temperature is lower than 95°C, the rectifier resumes to normal operation, and the
hysteresis is at least 10°C.
4.4.8
Fan Fault Protection: An alarm will be generated upon a fan fault. In such cases, the fault
indicator (red) on the Rectifier Module front panel will flash and the Rectifier Module will also
inhibit its output. Auto-recovery is enabled upon the clearing of the corresponding fault.
4.4.9
PFC Over/Under Voltage: The rectifier will shut down when its bus voltage is higher than the
over voltage set point or is lower than the under voltage set point. During such conditions, the
rectifier does not output any power and its protection indicator (yellow) will light up.
4.4.10 Load Sharing (via MCA): The MCA load sharing feature automatically balances the load. If the
MCA's load sharing feature is disabled for any reason, pre-programmed slope control in each
Rectifier Module balances the load. The MCA's load sharing feature is disabled whenever the
system is in current limit, the system is delivering more than 97% capacity, or the system is
delivering less than 3% capacity.
Active Load Sharing (Rectifier Module): The Rectifier Module uses advanced digital active
load sharing technology that maintains balancing to within ±3A. The difference in the average
current between rectifiers is <±3A for loads in the 10 to 100% range.
4.4.11 Startup Time: The Rectifier Module has two startup modes:
(A) Normal Soft Start Time: The duration from the time when the rectifier is powered on to the
time when the rectifier provides output voltage is 8s.
(B) Current Walk-In: The rise time of the rectifier output voltage is 8s at 90% of the rated
load, and the maximum time is 90s at 100% of the rated load.
4.4.12 Hot Swappable: The Rectifier Module is designed to be plug-and-play. The Rectifier Module
can be inserted or removed from a live DC power system with no damage. When the Rectifier
Module is plugged into the system, the system output voltage will not be affected.
4.4.13 Cooling: Each Rectifier Module contains a fan for forced convection cooling.
4.4.14 Fan Control: When the PFC bus voltage is within a normal range, the built-in processor adjusts
the fan’s speed according to the Rectifier Module’s internal temperature and output current. For
example, a higher temperature or output current will increase the fan speed. Above 45°C at full
load, the fan operates at full speed. When the PFC bus voltage is abnormal, such as very low
bus voltage, the fan turns off.
4.4.15 Communication Failure: The Rectifier Module’s protection indicator (yellow) will flash should it
experience a communication failure. The failure information will be reported to the Controller
and the Controller will process the failure accordingly. During a communication failure, in order
to protect the battery, the Rectifier Module output voltage will automatically adjust to 53.5 V (this
is a default value which can be modified using the Controller). The Rectifier Module will revert to
normal operation once normal communication is restored.
4.4.16 Unbalance of Rectifier Module Output Current: When the output current of the Rectifier
Modules in a DC power system is unbalanced, the Rectifier Module having the unbalanced
output current will be identified automatically and its protection indicator (yellow) will turn on.
Page 92 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
The failure information will be reported to the Controller and the Controller will process
the failure accordingly.
Home
4.4.17 Paralleling: This system may be connected in parallel with any rectifier of the same polarity and
adjusted to the same output voltage.
4.4.18 Monitoring Function: The Rectifier Module has a built-in advanced DSP that monitors and
controls the operation of the Rectifier Module. The DSP also communicates with the Controller
in real time through the CAN bus. The following table lists the different commands and
information exchanged between the Rectifier Module and the Controller.
Commands / signals that can be
received by the Rectifier Module
from the Controller.
Information gathered by the
Controller from the Rectifier
Module.

Turn on/off

Input voltage

Current walk-in on/off

Output voltage

HVSD reset

Output current

Current limit adjustment

Current limit setting

Voltage regulation

Temperature

Over voltage setting

On/off status

Fault alarms, such as:
HVSD
Fan fail

Protection alarms, such as:
Input voltage protection
Inner DC bus voltage protection
High temperature protection

Thermal derating

AC derating

AC fail

Unbalanced output current

Address

Code

Date

SW version

HW version
4.4.19 Dimensions:
Millimeters: 87.5 (Height) X 243.5 (Width) X 371.5 (Depth).
Inches:
3.44 (Height) X 9.59 (Width) X 14.63 (Depth).
4.4.20 Weight: < 8 kg (17.6 lbs).
4.4.21 Local Status and Alarm Indicators: Refer to the "Operating Procedures" chapter in the Power
System User Instructions (Section 6017) for a complete description.
(A) Power (Green)
(B) Protection (Yellow)
Page 93 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
Home
(C) Alarm (Red)
(D) A 10-segment Green LED is located on the front panel to represent output current, each
segment represents 10A.
5. MCA
5.1
Standard Features
5.1.1
MCA Interface: You interface with the MCA locally via the MCA Control Panel located on the
outside of the primary Power Bay's front door.
You can also interface with the MCA via the LMS, if furnished.
Note: Option switches are provided to lockout changing adjustment/configuration/calibration
settings via the MCA control panel and/or via the LMS.
5.1.2
MCA Local Display: Provides digital metering of system load voltage and current, individual
Rectifier Module output, and individual load shunts. Also displays system alarm messages and
adjustment information, as detailed in Paragraph 4.1.13 (MCA Display).
5.1.3
MCA Meter Accuracy: ±0.01 V, ±0.005% / °C
5.1.4
MCA Universal Adjustment Circuit: Provides single point control of float output voltage,
test/equalize output voltage, high voltage shutdown, and current limit adjustments.
Note: If the MCA should fail, the Rectifier Modules remember the float and high voltage
shutdown settings last delivered by the MCA. The current limit setting of each Rectifier
Module goes to 100% of rated full load.
Provides adjustments for all MCA alarm and control circuits. Adjustment ranges and factory
settings as follows.
All adjustments can be performed locally via the MCA Control Panel, and most can be performed
remotely via the LMS (if furnished).
(A) Rectifier Module Output Voltage: See Paragraph 3.1.1.
(B) Rectifier Module Current Limit: See Paragraph 3.4.6 (A).
(C) Rectifier Module High Voltage Shutdown: See Paragraph 3.4.6 (C).
(D) System High Voltage #1 Alarm: Adjustable from 48.00 to 59.00 volts DC. Factory set at
55.5 volts, unless otherwise specified.
(E) System High Voltage #2 Alarm: Adjustable from 48.00 to 59.00 volts DC. Factory set at
56.5 volts, unless otherwise specified.
(F) Battery On Discharge Alarm: Adjustable from 40.00 to 56.00 volts DC. Factory set at 51.0
volts, unless otherwise specified.
(G) Very Low Voltage Alarm: Adjustable from 40.00 to 56.00 volts DC. Factory set at 47.0
volts, unless otherwise specified.
(H) Total Distribution Load Alarm: Adjustable from 0 to 60000 amperes. Factory set at 2000
amperes, unless otherwise specified.
(I) Distribution Group A Load Alarm: Adjustable from 0 to 60000 amperes. Factory set at
2000 amperes, unless otherwise specified.
(J) Distribution Group B Load Alarm: Adjustable from 0 to 60000 amperes. Factory set at
2000 amperes, unless otherwise specified.
Page 94 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
(K) High Battery Ambient Temperature #1 Alarm (if battery charge digital
temperature compensation probe installed): Adjustable from -50C to +99C.
You disable the feature by selecting the setting above +99C. Factory set to off, unless
otherwise specified.
(L) High Battery Ambient Temperature #2 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -50C to +99C. You disable the feature
by selecting the setting above +99C. Factory set to off, unless otherwise specified.
(M) Low Battery Ambient Temperature #1 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -49C to +100C. You disable the
feature by selecting the setting below -49C. Factory set to off, unless otherwise specified.
(N) Low Battery Ambient Temperature #2 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -49C to +100C. You disable the
feature by selecting the setting below -49C. Factory set to off, unless otherwise specified.
(O) Audible Alarm Cutoff Reset Feature: Adjustable from 0 to 15 minutes, in one minute
intervals. A zero setting disables the feature. Factory set at 15 minutes, unless otherwise
specified.
(P) Rectifier Module Sequencing: The time delay between turning individual Rectifier Modules
on is adjustable from 1 to 20 seconds, or feature disabled. The Rectifier Module Sequencing
feature is factory set to ‘disabled’.
(Q) Timed Test/Equalize Period (also enables/disables the manually initiated timed
test/equalize feature): Adjustable from 1 to 99 hours, in one hour intervals. When a value
is set, the feature is enabled. You disable the feature by selecting the setting above 99.
Factory set at 1 (one) hour, unless otherwise specified.
(R) Automatic Test/Equalize Period (also enables/disables the automatic test/equalize
feature): Adjustable from 0 to 15 times the discharge time period, up to a maximum of 300
hours. A zero (0) setting disables the feature. Factory set at zero (0), unless otherwise
specified.
(S) Relay Test Seconds: Adjustable from 5 to 120 seconds, in one second intervals. Factory
set at 45 seconds, unless otherwise specified.
5.1.5
MCA Audible Alarm and Audible Alarm Cutoff: The MCA contains an Audible Alarm, which is
located on the MCA Control Panel. The audible alarm sounds when any alarm condition
monitored by the MCA occurs. The alarm can be manually silenced (cutoff) by pressing a local
pushbutton. A local indicator illuminates when the audible alarm has been cutoff. The alarm
remains silenced for the current alarm condition only. If another alarm condition occurs, the
audible alarm again sounds.
A programmable audible alarm cutoff reset feature is provided. Once an audible alarm has been
cutoff, it automatically resets (and sounds if the alarm condition is still present) after the time
period programmed expires. If another alarm condition occurs, the audible alarm again sounds.
5.1.6
Remote On/Off (TR): The operation of any or all Rectifier Modules can be inhibited (TR) via the
MCA Control Panel or from the LMS (if furnished). A Rectifier Module fail alarm is NOT issued.
5.1.7
MCA Alarm Logging: The MCA logs (with a date/time stamp) up to 500 recordable events.
5.1.8
Rectifier Module Sequencing: The MCA can be set to provide Rectifier Module Sequencing.
When the MCA senses an “AC Power is OFF to All Rectifier Modules” alarm, it turns off all
Rectifier Modules. When the “AC Power is OFF to All Rectifier Modules” alarm clears, the MCA
turns on Rectifier Module #1, then turns on the other Rectifier Modules starting with Rectifier
Module #2 every n seconds (n is user programmable from 1 to 20 seconds). If the MCA fails or
the communication link is broken during a Rectifier Module Sequencing routine, all Rectifier
Modules turn on immediately.
Page 95 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
5.1.9
Home
MCA Power Share Feature: The MCA Power Share feature allows you to connect the
Spec. No. 582140001 Power System to an existing DC power system instead of
extending or completely replacing the existing power system. The MCA Power Share feature
provides for the sharing of the total load in a controlled manner. When Power Share is
programmed, the MCA in the 582140001 Power System adjusts PCU output voltage per load
demands to ensure proper sharing between the two systems. For further information, request
Application Note AN38.
5.1.10 MCA Alternate Current Limit Feature: The MCA Alternate Current Limit feature provides a
means to limit the output current of all rectifiers based on the state of an external signal. The
rectifiers output current is limited to a percentage of rectifier output capacity as configured by the
user. A binary input on an installed MCA I/O circuit card is used to monitor the external signal
that triggers the current limiting action.
5.1.11 Local Controls: Refer to the "Operating Procedures" chapter in the Power System User
Instructions (Section 6017) for a complete description.
Location
MCA
Control
Panel
NAME / Description
Type
Function Select Up
Function Select Down
Function Set Enter / Move Left / Move Right
Function Set Yes / + / i
Function Set No / Alarm Cutoff
Pushbutton Switch
Pushbutton Switch
Pushbutton Switch
Pushbutton Switch
Pushbutton Switch
Pushbutton Switch
5.1.12 Local Status and Alarm Indicators: Refer to the "Operating Procedures" chapter in the Power
System User Instructions (Section 6017) for a complete description.
Location
NAME / Description
Type
Message Display, Shows...
MCA
Control
Panel

Active Alarms or "SYSTEM OK"

Various Measurement Items and Values

Various Inventory Items

Various Adjustment Items and Values

Various Operation Items
 Various Configuration Items and Settings
See Paragraph 4.1.13 "MCA Display"
Alarm Cutoff
Major
Minor
AC
Test/EQ
---
LED - yellow
LED - flashing red
LED - red
LED - green/red
LED - yellow
Page 96 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
5.1.13 MCA Numbering Scheme: The MCA identifies (numbers) the components of the
system as follows.
MCA IDENTIFICATION NUMBER
COMPONENT
MCA NUMBERING
SCHEME (note
that each line
shown below is
separated with a
dash in the MCA
display)
NOTES
EXAMPLE
Primary Power Bay
1
Bay #
MCA/Router
Primary Power Bay is #1, other bays are
numbered consecutively, following the bay-tobay cabling scheme.
Second Bay
2
Fifth Bay
5
Bay #
Rectifier
(PCU)
MCA Rectifier ID#
within the Bay / # of
Rectifiers Installed
in System
Bay #
MCA Relay
Circuit Card
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Rectifiers are identified from 1 to 24, as they are
powered-up and recognized by the MCA.
Primary Power Bay,
First Recognized
Rectifier (w/ 36
rectifiers installed)
1-01/36
Second Bay, Third
Recognized Rectifier
(w/ 24 rectifiers
installed)
2-03/24
Fifth Bay, Tenth
Recognized Rectifier
(w/ 12 rectifiers
installed)
5-10/12
Primary Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Card Position #
w/in Bay
Card #1 = left slot,
Card #7 = right slot.
Relay # w/in Card
Relay # (see illustration in System Overview
Chapter of the USER INSTRUCTIONS).
Primary Bay, Relay
Card in First Slot,
Relay One on Card
1-1-1
Second Bay, Relay
Card in Third Slot,
Relay Four on Card
2-3-4
Fifth Bay, Relay Card
in Seventh Slot, Relay
Six on Card
5-7-6
Page 97 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582140001
Issue AF, July 14, 2010
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
MCA IDENTIFICATION NUMBER
COMPONENT
MCA NUMBERING
SCHEME (note
that each line
shown below is
separated with a
dash in the MCA
display)
Bay #
MCA I/O
Circuit Card
Card Position #
w/in Bay
NOTES
Primary Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Card #1 = left slot,
Card #7 = right slot.
EXAMPLE
Primary Bay, I/O Card
in First Slot
1-1
Second Bay, I/O Card
in Third Slot
2-3
Fifth Bay, I/O Card in
Seventh Slot
5-7
Fifth Bay, Top Left
Bus, Set for B
Designation
5-1B
Distribution
Bay’s
Distribution
Bus
Bay #
Primary Power Bay is #1, other bays are
numbered consecutively, following the bay-tobay cabling scheme.
Distribution Bus #
w/in Bay (A or B
Designation)
Distribution Bus #1 = Top Left,
Distribution Bus #2 = Top Right,
Distribution Bus #3 = Bottom Left,
Distribution Bus #4 = Bottom Right,
A or B as set by jumper on MCA Distribution
Bus Monitoring Circuit Card.
Sixth Bay, Top Right
Bus, Set for B
Designation
6-2B
Seventh Bay, Bottom
Left Bus, Set for B
Designation
7-3B
Seventh Bay, Bottom
Right Bus, Designation
Not Set
7-4
Distribution
Bay’s
Distribution
Device
Type
Type = Breaker or Fuse or MISC 50-73.
Bay #
Primary Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Distribution Point #
w/in Bay
Distribution Point =
1-12 (bottom - top, Top Left Bus, Bus #1).
13-24 (top - bottom, Top Right Bus, Bus #2).
25-36 (bottom - top, Bottom Left Bus, Bus #3).
37-48 (top - bottom, Bottom Right Bus, Bus #4).
Note that distribution components may take
more than one mounting position, designation
number is the left most mounting position.
Fifth Bay, Circuit
Breaker Mounted in
Position One, Bus 1
Set for A Designation
Breaker 5-01A
Sixth Bay, Fuse
Mounted in Position
Thirteen, Bus 2
Designation Not Set
Fuse 6-13
Note: The optional bullet-device fuse panel is
displayed as MISC 50-73.
Page 98 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
5.1.14 MCA Display: Presented next are illustrations from the MCA Menu Tree (Section
5886). Refer to the latest version of Section 5886 for the most recent MCA Menu Tree. Refer to
the Power System User Instructions (Section 6017) for a complete description of menu items
(the MCA is used in multiple platforms, some menu items may not be available as detailed in
Section 6017).
Page 99 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
The User navigates Lines 3 and 4 of the MCA Display using the Keypad on the MCA Control Panel.
(The following indicates the actual text shown on each line of Lines 3 and 4 of the MCA Display, Line
4 also displays applicable navigation key codes, see previous page for explanation of codes.)
MAIN ALARM MENU
INITIALIZATION MENU
A
############ WAIT ##
V###########
1
2
2A
B
CHECK VALUES BEFORE
STARTING
C
FLOAT SETPOINT
= vv.vvV
D
E
F
TEST/EQUALIZE
= vv.vvV
HI VOLTAGE SHUTDOWN
= vv.vvV
PCU CURRENT LIMIT
= aaaaaA
or
PCU CURRENT LIMIT
POWER SHARE
or
PCU CURRENT LIMIT
ALT. LIMIT
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
SYSTEM HI VOLTAGE #1
= vv.vvV
SYSTEM BATTERY IS ON
DISCHARGE
5
SYSTEM HIGH VOLTAGE
#1 ALARM
6
7
11
12
BATTERY ON DISCHARGE
= vv.vvV
VERY LOW VOLTAGE
= vv.vvV
TOTAL LOAD CURRENT
= aaaaaA
DISTRIBUTION GROUP A
= aaaaaA
40
DISTRIBUTION GROUP B
= aaaaaA
HIGH TEMPERATURE #1
= ttt°C/F
or
NO HIGH TEMPERATURE
#1 ALARM
HIGH TEMPERATURE #2
= ttt°C/F
or
NO HIGH TEMPERATURE
#2 ALARM
LOW TEMPERATURE #1
= ttt°C/F
or
NO LOW TEMPERATURE
#1 ALARM
LOW TEMPERATURE #2
= ttt°C/F
or
NO LOW TEMPERATURE
#2 ALARM
AUDIBLE SILENT TIME
= mm MINUTES
or
AUDIBLE ALARMS STAY
SILENCED
PCU SEQUENCING IS
DISABLED
or
PCU SEQUENCING DELAY
= ss SECONDS
TEST EQUALIZE IS DISABLED
or
MANUAL TEST/EQUALIZE
= hh HOURS
or
TEST/EQUALIZE STOP
IS MANUAL
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
AUTO EQUALIZE IS
DISABLED
or
AUTO EQUALIZE FOR ##
x DISCHARGE
NO TEMPERATURE
COMPENSATION
or
TEMPERATURE SLOPE
= 0.vvvV/ °C/F
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
W
MAXIMUM COMPENSATION
= vv.vvV
X
MINIMUM COMPENSATION
= vv.vvV
Y
IT IS NOW hh:mm:ss
dd-mon-yy
Z
READY TO START THE
SYSTEM NOW?
55
66
78
88
89
AC POWER IS OFF TO
ALL PCUs
1 PCU
HAS FAILED
or
### PCUs
HAVE FAILED
or
NO PCUs ARE
IN INVENTORY
1 DIST. PANEL
HAS FAILED
or
## DIST. PANELS
HAVE FAILED
or
NO DIST. PANELS ARE
IN INVENTORY
1 I/O BOARD
HAS FAILED
or
## I/O BOARDS
HAVE FAILED
or
NO I/O BOARDS ARE
IN INVENTORY
1 ROUTER
HAS FAILED
or
## ROUTERS
HAVE FAILED
or
NO ROUTERS ARE
IN INVENTORY
1 RELAY BOARD
HAS FAILED
or
## RELAY BOARDS
HAVE FAILED
or
NO RELAY BOARDS ARE
IN INVENTORY
HIGH TEMPERATURE #1
ALARM
HIGH TEMPERATURE #2
ALARM
LOW TEMPERATURE #1
ALARM
91
LOW TEMPERATURE #2
ALARM
93
94
95
96
97
98
99
100
19
3A, 4A, 5A, 6A
ALARM LIMIT vv.vvV
NOW AT vv.vvV
8
9
10
13
14
FUSE ALARM MENU
F/CB/PI B#-P#A/B
IS OPEN
GO TO MAIN ALARM
MENU
GO BACK TO MENU TREE
BEGINNING
PCU ALARM MENU
PCU B#-ID#/N#
FAILURE
### REMOTE PCUS
HAVE FAILED
DISTRIBUTION GROUP B
LOAD ALARM
102
THE DISPLAY DOES NOT
RESPOND
103
GO TO FUNCTION MENU
104
GO BACK TO MENU TREE
BEGINNING
25
PCU B#-ID#/N#
H.V. SHUTDOWN
PCU B#-ID#/N#
AC LINE OFF
POSITION B#-P#A/B
NOT FOUND
or
POSITION NOT FOUND
PANEL B#-P#A/B
PCU B#-ID#/N#
AC PHASE LOST
46
POSITION B#-P#A/B
TYPE UNKNOWN
PCU B#-ID#/N#
POWER FACTOR
PCU B#-ID#/N#
DC/DC CONV.
47
26
49
DIST. PANEL B#-P#A/B
A/B CHANGED
27
PCU B#-ID#/N#
INHIBITED
50
DIST. PANEL B#-P#A/B
PROCESSOR
PCU B#-ID#/N#
ON STANDBY
PCU B#-ID#/N#
THERMAL LIMIT
51
DIST. PANEL B#-P#A/B IS
DUPLICATED
52
DIST. PANEL B#-P#A/B
NO RESPONSE
PCU B#-ID#/N#
THERMAL STOP
PCU B#-ID#/N#
HIGH AMBIENT
53
28
29
30
31
GO TO MAIN ALARM
MENU
32
GO BACK TO MENU TREE
BEGINNING
PCU B#-ID#/N#
LOAD SHARE
17
33
PCU B#-ID#/N#
1 FAN SPEED
34
42
GO TO MAIN ALARM
MENU
43
GO BACK TO MENU TREE
BEGINNING
36
PCU B#-ID#/N#
DUPLICATED
37
PCU B#-ID#/N#
NO RESPONSE
38
GO TO PCU ALARM MENU
39
GO BACK TO MENU TREE
BEGINNING
56
57
GO TO MAIN ALARM
MENU
58
GO BACK TO MENU TREE
BEGINNING
67
ROUTER ALARM MENU
ROUTER B#
FAILURE
GO TO MAIN ALARM
MENU
68
69
GO BACK TO MENU TREE
BEGINNING
79
RELAY ALARM MENU
RELAY BOARD B#-P#
FAILURE
GO TO MAIN ALARM
MENU
80
81
GO BACK TO MENU TREE
BEGINNING
GO TO DISTRIBUTION
ALARM MENU
GO BACK TO MENU TREE
BEGINNING
I/O BOARD ALARM DETAIL MENU
59
60
61
62
63
64
65
88A, 89A, 90A, 91A
70
71
ALARM LIMIT ttt°C/F
NOW AT ttt°C/F
54
PCU B#-ID#/N#
2+ FANS SPEED
PCU B#-ID#/N#
NO VOLT SENSE
35
I/O BOARD ALARM MENU
I/O BOARD B#-P#
FAILURE
48
F/CB/PI B#-P#A/B
OVER CURRENT
DIST. PANEL B#-P#A/B
LVD FAILURE
PCU B#-ID#/N#
FUSE/BREAKER
16
DISTRIBUTION ALARM MENU
DIST. PANEL B#-P#A/B
41 FAILURE
DISTRIBUTION ALARM DETAIL MENU
DIST. PANEL B#-P#A/B
DISCONNECTED
or
44
DIST. PANEL B#-P#A/B
RECONNECT?
45
PCU B#-ID#/N#
AC LINE LOW
PCU B#-ID#/N#
AC LINE HIGH
1 REMOTE PCU
HAS FAILED
Binary Input Customer
Text Messages
I/O BOARD B#-P#
OVER CURRENT
I/O BOARD B#-P#
PROCESSOR
I/O BOARD B#-P# IS
DUPLICATED
I/O BOARD B#-P#
NO RESPONSE
GO TO I/O BOARD
ALARM MENU
GO BACK TO MENU TREE
BEGINNING
ROUTER ALARM DETAIL MENU
ROUTER B# REMOTE
SENSE OPEN
ROUTER B# INTERNAL
SENSE OPEN
72
ROUTER B# PROCESSOR
73
ROUTER B# REPORTS AN
ILLEGAL NODE
74
75
ROUTER B# IS
DUPLICATED
ROUTER B#
NO RESPONSE
76
GO TO ROUTER ALARM
MENU
77
GO BACK TO MENU TREE
BEGINNING
RELAY ALARM DETAIL MENU
RELAY B#-P#-R# IS
STUCK
RELAY BOARD B#-P#
83
PROCESSOR
RELAY BOARD B#-P# IS
84
DUPLICATED
82
MONITORING DOES NOT
RESPOND
101
24
PCU ALARM DETAIL MENU
PCU B#-ID#/N#
EMERG. STOP
15
MINOR MONITORING
ALARM(S)
or
Monitoring Minor
LED Messages
MONITORING
INFORMATION
or
Monitoring Info
LED Messages
TOTAL LOAD CURRENT
ALARM
DISTRIBUTION GROUP A
LOAD ALARM
22
23
TEMPERATURE SENSOR
NO SIGNAL
MAJOR MONITORING
ALARM(S)
or
Monitoring Major
LED Messages
CONTROLLER FAILURE
####
THE CONTROLLER IS
INITIALIZING
20
21
SYSTEM HIGH VOLTAGE
#2 ALARM
1 SYSTEM BREAKER OR
FUSE ALARM
or
### SYSTEM BREAKER &
FUSE ALARMS
90
92
18
ALTERNATE CURRENT
LIMIT ACTIVE
SYSTEM VOLTAGE IS
VERY LOW
4
SYSTEM HI VOLTAGE #2
= vv.vvV
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
V
3
EMERGENCY STOP
INPUT ACTIVE
HI VOLTAGE SHUTDOWN
INPUT ACTIVE
99A, 100A, 101A
ALARM LIMIT aaaaaA
NOW AT aaaaaA
85
86
87
RELAY BOARD B#-P#
NO RESPONSE
GO TO RELAY ALARM
MENU
GO BACK TO MENU TREE
BEGINNING
NORMAL DISPLAY MENU
or
REPLACE ### PCUs?
AUTO IN ###
A
to
(Sheet 2 of 4)
Page 100 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
from
(Sheet 1 of 4)
A
FUNCTION MENU
(cont'd on next page)
105
133
134
VIEW THE SYSTEM
MEASUREMENTS
FLOAT MODE IS ACTIVE
SET TEST/EQ?
or
TEST/EQ MODE ACTIVE
SET FLOAT?
or
TEST/EQUALIZE INPUT
IS ACTIVE
or
PCU CURRENT LIMIT
POWER SHARE
or
PCU CURRENT LIMIT
ALT. LIMIT
VIEW THE SYSTEM
INVENTORY
MEASUREMENT MENU
106
111
125
SYSTEM OUTPUT SENSE
vv.vvV (REM)
or
SYSTEM OUTPUT SENSE
vv.vvV (AVG)
TOTAL SYSTEM
LOAD aaaaaA
TOTAL PCU OUTPUT
aaaaaA
or
TOTAL PCU/RECTIFIER
aaaaaA
130
TEMPERATURE SENSOR
ttt°C/F
131
GO TO FUNCTION MENU
132
GO BACK TO MENU TREE
BEGINNING
INVENTORY MENU
135
B
to
(Sheet 3 of 4)
149
150
161
171
181
191
192
199
200
1 PCU IS
REPORTING
or
### PCUs ARE
REPORTING
or
NO PCUs ARE
INSTALLED
1 PCU POSITION
IS EMPTY
or
### PCU POSITIONS
ARE EMPTY
or
NO PCU POSITIONS
ARE EMPTY
or
TOTAL PCU POSITIONS
= ###
1 DIST. PANEL IS
REPORTING
or
## DIST. PANELS ARE
REPORTING
or
NO DIST. PANELS ARE
INSTALLED
1 I/O BOARD IS
REPORTING
or
## I/O BOARDS ARE
REPORTING
or
NO I/O BOARDS ARE
INSTALLED
1 ROUTER IS
REPORTING
or
## ROUTERS ARE
REPORTING
or
NO ROUTERS ARE
INSTALLED
1 RELAY BOARD IS
REPORTING
or
## RELAY BOARDS ARE
REPORTING
or
NO RELAY BOARDS ARE
INSTALLED
TEMPERATURE SENSOR
REPORTING
or
NO TEMPERATURE
SENSOR
MONITORING IS
REPORTING
or
NO MONITORING IS
INSTALLED
SENSE VOLTAGE IS
REMOTE INPUT
or
SENSE VOLTAGE IS
AVERAGED
CONTROLLER ASSEMBLY
############
210
UPDATE THE INVENTORY
211
GO TO FUNCTION MENU
212
GO BACK TO MENU TREE
BEGINNING
SAG582140001
Issue AF, July 14, 2010
ROUTER VOLTAGE MENU
107
108
109
110
ROUTER B# REMOTE
SENSE vv.vvV
ROUTER B# INTERNAL
SENSE vv.vvV
GO TO MEASUREMENT
MENU
GO BACK TO MENU TREE
BEGINNING
SYSTEM LOAD MENU
DISTRIBUTION LOAD MENU
118
DIST. PANEL B#-P#A/B
LOAD aaaaaA
119
I/O BOARD B#-P#
LOAD aaaaaA
120
GO TO SYSTEM LOAD
MENU
121
GO BACK TO MENU TREE
BEGINNING
112
TOTAL DISTRIBUTION
LOAD aaaaaA
or
TOTAL AUXILIARY
LOAD aaaaaA
113
DISTRIBUTION GROUP A
LOAD aaaaaA
122
F/CB/PI B#-P#A/B
LOAD aaaaaA
114
DISTRIBUTION GROUP B
LOAD aaaaaA
123
GO TO DISTRIBUTION
LOAD MENU
115
REMOTE SYSTEM
LOAD aaaaaA
124
GO BACK TO MENU TREE
BEGINNING
116
GO TO MEASUREMENT
MENU
117
GO BACK TO MENU TREE
BEGINNING
139
B#-ID#/N# ASSY.
#####################
PCU CURRENT MENU
140
PCU B#-ID#/N#
aaaaaA
B#-ID#/N# SERIAL
#####################
126
141
B#-ID#/N# BOOT
#####################
127
128
129
PCU INVENTORY DETAIL MENU
RECTIFIER OUTPUT
aaaaaA
GO TO MEASUREMENT
MENU
142
B#-ID#/N# SW VER
#####################
143
GO BACK TO MENU TREE
BEGINNING
PSC B#-ID# ASSEMBLY
#####################
144
PSC B#-ID# SERIAL #
#####################
145
PSC B#-ID# BOOTCODE
#####################
146
PSC B#-ID# SOFTWARE
#####################
PCU INVENTORY MENU
136
DISTRIBUTION LOAD DETAIL MENU
PCU B#-ID#/N#
RATED aaaaaA
137
GO TO INVENTORY MENU
138
GO BACK TO MENU TREE
BEGINNING
147
GO TO PCU
INVENTORY
DISTRIBUTION INVENTORY MENU
148
GO BACK TO MENU TREE
BEGINNING
151
PANEL B#-P#A/B INCLUDES
1 POINT
or
PANEL B#-P#A/B INCLUDES
## POINTS
DISTRIBUTION INVENTORY DETAIL MENU
154
POINT B#-P#A/B IS A
F/CB/PI
152
GO TO INVENTORY MENU
155
PANEL B#-P#A/B ASSEMBLY
############
153
GO BACK TO MENU TREE
BEGINNING
156
PANEL B#-P#A/B SERIAL #
############
I/O BOARD INVENTORY MENU
157
PANEL B#-P#A/B BOOTCODE
############
158
PANEL B#-P#A/B SOFTWARE
############
159
GO TO DISTRIBUTION
INVENTORY
160
GO BACK TO MENU TREE
BEGINNING
162
I/O BOARD B#-P# IS
INSTALLED
163
GO TO INVENTORY MENU
164
GO BACK TO MENU TREE
BEGINNING
ROUTER INVENTORY MENU
172
ROUTER B# IS
INSTALLED
173
GO TO INVENTORY MENU
174
GO BACK TO MENU TREE
BEGINNING
RELAY INVENTORY MENU
I/O BOARD INVENTORY DETAIL MENU
165
BOARD B#-P# ASSEMBLY
############
166
BOARD B#-P# SERIAL #
############
167
BOARD B#-P# BOOTCODE
############
182
RELAY BOARD B#-P# IS
INSTALLED
183
GO TO INVENTORY MENU
168
BOARD B#-P# SOFTWARE
############
184
GO BACK TO MENU TREE
BEGINNING
169
GO TO I/O BOARD
INVENTORY
MONITORING INVENTORY DETAIL MENU
170
MONITORING ASSEMBLY
#####################
MONITORING SERIAL #
#####################
GO BACK TO MENU TREE
BEGINNING
175
193
194
ROUTER INVENTORY DETAIL MENU
ROUTER B# ASSEMBLY
############
195
MONITORING BOOTCODE
#####################
196
MONITORING SOFTWARE
#####################
177
197
GO TO INVENTORY MENU
178
GO BACK TO MENU TREE
BEGINNING
ROUTER B# SOFTWARE
############
198
179
GO TO ROUTER
INVENTORY
180
GO BACK TO MENU TREE
BEGINNING
CONTROLLER INVENTORY DETAIL MENU
201
202
203
204
205
CONTROLLER SERIAL #
#####################
CONTROLLER BOOTCODE
#####################
CONTROLLER SOFTWARE
#####################
DISPLAY ASSEMBLY
#####################
DISPLAY SERIAL #
#####################
206
DISPLAY BOOTCODE
#####################
207
DISPLAY SOFTWARE
#####################
208
GO TO INVENTORY MENU
209
GO BACK TO MENU TREE
BEGINNING
176
ROUTER B# SERIAL #
############
ROUTER B# BOOTCODE
############
RELAY INVENTORY DETAIL MENU
BOARD B#-P# ASSEMBLY
############
185
186
BOARD B#-P# SERIAL #
############
186
BOARD B#-P# BOOTCODE
############
188
BOARD B#-P# SOFTWARE
############
189
GO TO RELAY BOARD
INVENTORY
190
GO BACK TO MENU TREE
BEGINNING
Page 101 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
SYSTEM ADJUSTMENT MENU
214
215
216
from
(Sheet 2 of 3)
B
217
213
225
218
FUNCTION MENU
(cont'd from previous page)
ADJUST THE SYSTEM
VOLTS & AMPS
218A
219
ADJUST THE ALARM
SETPOINTS
239
TURN PCUs ON OR OFF
243
CHANGE CONFIGURATION
PARAMETERS
323
VERIFY TEST, ESTOP,
& HVS INPUTS
or
TEST SHUTDOWN INPUT
IS ON
or
EMERGENCY STOP INPUT
IS ON
or
HI VOLTAGE SHUTDOWN
INPUT IS ON
240
324
VIEW THE ALARM LOG
437
PCU B#-ID#/N#
RECOGNIZED
or
DSM B#-P#A/B
RECOGNIZED
or
I/O B#-P#
RECOGNIZED
or
CRM B#
RECOGNIZED
or
RCB B#-P#
RECOGNIZED
438
241
GO TO FUNCTION MENU
242
GO BACK TO MENU TREE
BEGINNING
244
CHANGE I/O BOARD
PARAMETERS
251
AUDIBLE SILENT TIME
= mm MINUTES
or
AUDIBLE ALARMS STAY
SILENCED
252
253
PCU SEQUENCING IS
DISABLED
or
PCU SEQUENCING DELAY
= ss SECONDS
TEST EQUALIZE IS DISABLED
or
MANUAL TEST/EQUALIZE
= hh HOURS
or
TEST/EQUALIZE STOP
IS MANUAL
or
END TEST/EQUALIZE IN
hh.hh HOURS
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
254
to
(Sheet 4 of 4)
255
310
AUTO EQUALIZE IS
DISABLED
or
AUTO EQUALIZE FOR ##
x DISCHARGE
or
END AUTO EQUALIZE IN
hhh.hh HOURS
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
DEFINE RELAY
FUNCTIONS
START RELAY FUNCTION
TEST
or
TIME PER FUNCTION
= hh:mm:ss
or
TIME PER FUNCTION
NO TIMEOUT
or
AUTOMATICALLY TEST
ALL FUNCTIONS
or
TEST RELAY FUNCTION
A#
or
STOP RELAY FUNCTION
TEST
or
TESTING FUNCTION A#
= hh:mm:ss
or
TESTING FUNCTION A#
NO TIMEOUT
311
ASSIGN RELAYS TO
FUNCTIONS
315
NO TEMPERATURE
COMPENSATION
or
TEMPERATURE SLOPE
= 0.vvvV/°C/F
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
317
MAXIMUM COMPENSATION
= vv.vvV
MINIMUM COMPENSATION
= vv.vvV
318
NOW DISPLAYING °C/F
SET TO °C/F?
319
IT IS NOW hh:mm:ss
dd-mon-yy
320
ERASE THE ALARM LOG
316
ALTERNATE CURRENT
LIMIT = ###%
HI VOLTAGE SHUTDOWN
= vv.vvV
RELAY FUNCTION DEFINITION MENU
259
260
261
261A
262
263
264
265
220
221
LOSS IS POSSIBLE. GO
AHEAD ANYWAY?
266
PCU CURRENT LIMIT
= aaaaaA
or
PCU CURRENT LIMIT
ALT. LIMIT
or
PCU CURRENT LIMIT
POWER SHARE
267
268
269
270
222
100% PCU CURRENT IS
aaaaaA
271
223
GO TO FUNCTION MENU
272
224
GO BACK TO MENU TREE
BEGINNING
ALARM ADJUSTMENT MENU
SYSTEM HI VOLTAGE #1
= vv.vvV
SYSTEM HI VOLTAGE #2
227
= vv.vvV
226
228
229
230
231
273
274
275
BATTERY ON DISCHARGE
= vv.vvV
276
VERY LOW VOLTAGE
= vv.vvV
TOTAL LOAD CURRENT
= aaaaaA
277
DISTRIBUTION GROUP A
= aaaaaA
232
DISTRIBUTION GROUP B
= aaaaaA
233
HIGH TEMPERATURE #1
= ttt°C/F
or
NO HIGH TEMPERATURE
#1 ALARM
234
HIGH TEMPERATURE #2
= ttt°C/F
or
NO HIGH TEMPERATURE
#2 ALARM
235
LOW TEMPERATURE #1
= ttt°C/F
or
NO LOW TEMPERATURE
#1 ALARM
278
279
280
281
282
283
287
288
289
292
238
GO BACK TO MENU TREE
BEGINNING
293
246
248
ANALOG INPUT B#-P#
50mV = aaaaaA
ANALOG OUTPUT B#-P#
50mV = aaaaaA
BINARY INPUT B#-P#-I#
ALARM = CLOSED
or
BINARY INPUT B#-P#-I#
ALARM = OPEN
249 GO TO CONFIGURE MENU
250
GO BACK TO MENU TREE
BEGINNING
290
291
294
295
296
297
298
299
300
301
302
303
RELAY FUNCTION MENU
256
DEFINE RELAY
FUNCTION A#
257
GO TO CONFIGURE MENU
304
305
GO BACK TO MENU TREE
BEGINNING
306
RELAY ASSIGNMENT MENU
307
312
ASSIGN RELAY B#-P#-R#
FUNCTION A#
308
313
GO TO CONFIGURE MENU
314
GO BACK TO MENU TREE
BEGINNING
258
/_AC POWER IS OFF TO
2+ PCUs
/_AC POWER IS OFF TO
ALL PCUs
/_1 PCU FAILURE
ANY TYPE
/_2+ PCU FAILURES
ANY TYPE
/_1 PCU FAILURE
'MAJOR' TYPE
/_2+ PCU FAILURES
'MAJOR' TYPE
/_1 PCU FAILURE
'MINOR' TYPE
/_2+ PCU FAILURES
'MINOR' TYPE
/_NO PCUs ARE
IN INVENTORY
/_1 DIST. PANEL
FAILURE
/_2+ DIST. PANEL
FAILURES
/_NO DIST. PANELS
IN INVENTORY
/_1 I/O BOARD
FAILURE
/_2+ I/O BOARD
FAILURES
/_NO I/O BOARDS ARE
IN INVENTORY
/_2+ ROUTER FAILURES
286
GO TO FUNCTION MENU
247
/_SYSTEM HIGH VOLTAGE
#1 ALARM
/_SYSTEM HIGH VOLTAGE
#2 ALARM
/_1 SYSTEM BREAKER OR
FUSE ALARM
/_2+ SYSTEM BREAKER &
FUSE ALARMS
/_AC POWER IS OFF TO
1 PCU
/_1 ROUTER FAILURE
237
245
/_HI VOLTAGE SHUTDOWN
INPUT ACTIVE
/_ALTERNATE CURRENT
LIMIT ACTIVE
/_SYSTEM VOLTAGE IS
VERY LOW
/_SYSTEM BATTERY ON
DISCHARGE
285
LOW TEMPERATURE #2
= ttt°C/F
or
NO LOW TEMPERATURE
#2 ALARM
I/O BOARD
CONFIGURATION MENU
ANALOG INPUT B#-P# IS
DISTRIBUTION
or
ANALOG INPUT B#-P# IS
AUXILIARY
CHECKED CONDITIONS
DE-ENERGIZE
or
CHECKED CONDITIONS
ENERGIZE
/_EMERGENCY STOP
INPUT ACTIVE
284
236
309
/_NO ROUTERS ARE
IN INVENTORY
/_1 RELAY BOARD
FAILURE
/_2+ RELAY BOARD
FAILURES
/_NO RELAY BOARDS ARE
IN INVENTORY
/_HIGH TEMPERATURE #1
ALARM
/_HIGH TEMPERATURE #2
ALARM
/_LOW TEMPERATURE #1
ALARM
/_LOW TEMPERATURE #2
ALARM
/_TEMPERATURE SENSOR
NO SIGNAL
/_MAJOR MONITORING
ALARM(S)
/_MINOR MONITORING
ALARM(S)
/_All Monitoring LED
Messages
/_MONITORING DOES NOT
RESPOND
/_CONTROLLER FAILURE
/_THE CONTROLLER IS
INITIALIZING
/_TOTAL LOAD CURRENT
ALARM
/_DIST. GROUP A
LOAD ALARM
/_DIST. GROUP B
LOAD ALARM
/_THE DISPLAY DOES
NOT RESPOND
/_TEST/EQUALIZE MODE
IS ACTIVE
/_THE AUDIBLE ALARM
IS ACTIVE
/_AUDIBLE ALARMS ARE
SILENCED
GO TO RELAY FUNCTION
MENU
GO BACK TO MENU TREE
BEGINNING
NETWORK ADDRESS MENU
CHANGE NETWORK
ADDRESSES
320B
321
GO TO FUNCTION MENU
320C
322
GO BACK TO MENU TREE
BEGINNING
320D
320A
POWER SHARE IS OFF
TURN IT ON?
or
POWER SHARE IS ON
TURN IT OFF?
or
ALT. LIMIT IS OFF
TURN IT ON?
or
ALT. LIMIT IS ON
TURN IT OFF?
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
or
TURN OFF TEMPERATURE
COMPENSATION
PS INITIAL CAPACITY
LIMIT = ###%
PS VOLTAGE OFFSET
= v.vV
TEST H.V. SHUTDOWN
= vv.vvV
CONFIGURE MENU
GO BACK TO MENU TREE
BEGINNING
C
PCU ENABLE MENU
PCU B#-ID#/N# ON
TURN IT OFF?
or
PCU B#-ID#/N# OFF
TURN IT ON?
FLOAT SETPOINT
= vv.vvV
TEST/EQUALIZE
= vv.vvV
##.##.##.##.##
MAC ADDRESS
###.###.###.###
IP ADDRESS
###.###.###.###
NET MASK
320E
###.###.###.###
GATEWAY
320F
VALIDATE THE ADDRESS
CHANGES?
or
UPDATE/RESTART LMS
WITH CHANGES?
or
THE CHANGES WERE
REJECTED
320G
GO TO CONFIGURE MENU
320H
GO BACK TO MENU TREE
BEGINNING
Page 102 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
from
(Sheet 3 of 4)
C
MCA ALARM
LOG DETAIL MENU
ALARM LOG MENU
325
356
dd-mon-yy hh:mm:ss /
CONTROLLER
326
PCU ALARM
LOG DETAIL MENU
dd-mon-yy hh:mm:ss /
B#-SN#
384
dd-mon-yy hh:mm:ss /
PANEL B#-P#A/B
400
dd-mon-yy hh:mm:ss /
I/O B#-P#
411
dd-mon-yy hh:mm:ss /
ROUTER B#
425
dd-mon-yy hh:mm:ss /
RELAY B#-P#
435
GO TO FUNCTION MENU
436
GO BACK TO MENU TREE
BEGINNING
ROUTER ALARM
LOG DETAIL MENU
385
329
387
360
330
361
388
POSITION B#-P#A/B
NOT FOUND
or
POSITION NOT FOUND
PANEL B#-P#A/B
389
POSITION B#-P#A/B
TYPE UNKNOWN
391
POSITION B#-P#A/B
OVER CURRENT
391
ROUTER B# REMOTE
SENSE OPEN
393
414
ROUTER B# INTERNAL
SENSE OPEN
394
415
ROUTER B# PROCESSOR
FAILURE
395
ROUTER B# REPORTS AN
ILLEGAL NODE
396
419
420
421
422
ROUTER B# DOES NOT
RESPOND
ROUTER B# REMOTE
SENSE vv.vvV
ROUTER B# INTERNAL
SENSE vv.vvV
SYSTEM OUTPUT SENSE
vv.vvV
TOTAL LOAD CURRENT
aaaaaA
423
GO TO ALARM LOG MENU
424
GO BACK TO MENU TREE
BEGINNING
397
I/O BOARD ALARM
LOG DETAIL MENU
401
402
403
405
427
RELAY B#-P#-R# IS
STUCK
407
428
RELAY BOARD B#-P#
PROCESSOR
408
431
432
TOTAL LOAD CURRENT
aaaaaA
433
GO TO ALARM LOG MENU
434
GO BACK TO MENU TREE
BEGINNING
SYSTEM OUTPUT SENSE
vv.vvV
TOTAL LOAD CURRENT
aaaaaA
GO BACK TO MENU TREE
BEGINNING
406
430
DIST. PANEL B#-P#A/B
NO RESPONSE
399
426
RELAY BOARD B#-P# IS
DUPLICATED
RELAY BOARD B#-P#
NO RESPONSE
SYSTEM OUTPUT SENSE
vv.vvV
DIST. PANEL B#-P#A/B
PROCESSOR
DIST. PANEL B#-P#A/B IS
DUPLICATED
GO TO ALARM LOG MENU
RELAY BOARD B#-P#
NO ALARMS
429
DIST. PANEL B#-P#A/B
LVD FAILURE
DIST. PANEL B#-P#A/B
A/B CHANGED
398
404
RELAY ALARM
LOG DETAIL MENU
328A
PCU B#-SN#
AC LINE OFF
413
418
328
POSITION B#-P#A/B
IS OPEN
392
ROUTER B# IS
DUPLICATED
358
327
359
386
412
417
357
PCU B#-SN#
NO ALARMS
PCU B#-SN#
EMERG. STOP
PCU B#-SN#
H.V. SHUTDOWN
ROUTER B#
NO ALARMS
416
DISTRIBUTION ALARM
LOG DETAIL MENU
DIST. PANEL B#-P#A/B
NO ALARMS
DIST. PANEL B#-P#A/B
DISCONNECTED
I/O BOARD B#-P#
NO ALARMS
I/O BOARD B#-P#
BINARY I#
I/O BOARD B#-P#
OVER CURRENT
I/O BOARD B#-P#
PROCESSOR
I/O BOARD B#-P#
IS DUPLICATED
I/O BOARD B#-P#
NO RESPONSE
SYSTEM OUTPUT SENSE
vv.vvV
TOTAL LOAD CURRENT
aaaaaA
409
GO TO ALARM LOG MENU
410
GO BACK TO MENU TREE
BEGINNING
362
363
364
365
366
367
368
369
370
371
372
PCU B#-SN#
AC LINE LOW
PCU B#-SN#
AC LINE HIGH
PCU B#-SN#
AC PHASE LOST
PCU B#-SN#
POWER FACTOR
PCU B#-SN#
DC/DC CONV.
PCU B#-SN#
FUSE/BREAKER
PCU B#-SN#
INHIBITED
PCU B#-SN#
ON STANDBY
PCU B#-SN#
THERMAL LIMIT
PCU B#-SN#
THERMAL STOP
PCU B#-SN#
HIGH AMBIENT
PCU B#-SN#
LOAD SHARE
331
332
333
334
335
336
337
338
339
340
SYSTEM BATTERY IS ON
DISCHARGE
SYSTEM HIGH VOLTAGE
#1 ALARM
SYSTEM HIGH VOLTAGE
#2 ALARM
NO PCUs ARE
IN INVENTORY
NO DIST. PANELS ARE
IN INVENTORY
NO ROUTERS ARE
IN INVENTORY
NO RELAY BOARDS ARE
IN INVENTORY
HIGH TEMPERATURE #1
ALARM
HIGH TEMPERATURE #2
ALARM
LOW TEMPERATURE #1
ALARM
LOW TEMPERATURE #2
ALARM
342
MAJOR MONITORING
ALARM(S)
343
374
PCU B#-SN#
2+ FANS SPEED
344
376
ALTERNATE CURRENT
LIMIT ACTIVE
SYSTEM VOLTAGE IS
VERY LOW
TEMPERATURE SENSOR
NO SIGNAL
373
PCU B#-SN#
NO VOLT SENSE
PCU B#-SN#
DUPLICATED
HI VOLTAGE SHUTDOWN
INPUT ACTIVE
341
PCU B#-SN#
1 FAN SPEED
375
SYSTEM CONTROLLER
NO ALARMS
EMERGENCY STOP
INPUT ACTIVE
345
MINOR MONITORING
ALARM(S)
Monitoring LED
Messages
MONITORING DOES NOT
RESPOND
346
CONTROLLER FAILURE
####
347
THE CONTROLLER IS
INITIALIZING
377
PCU B#-SN#
NO RESPONSE
378
PCU B#-SN#
TURNED ON
or
PCU B#-SN#
TURNED OFF
379
PCU B#-SN#
aaaaaA
350
380
SYSTEM OUTPUT SENSE
vv.vvV
351
THE DISPLAY DOES NOT
RESPOND
381
TOTAL LOAD CURRENT
aaaaaA
352
SYSTEM OUTPUT SENSE
vv.vvV
382
GO TO ALARM LOG MENU
353
TOTAL LOAD CURRENT
aaaaaA
383
GO BACK TO MENU TREE
BEGINNING
354
GO TO ALARM LOG MENU
355
GO BACK TO MENU TREE
BEGINNING
348
349
TOTAL LOAD CURRENT
ALARM
GROUP A LOAD CURRENT
ALARM
GROUP B LOAD CURRENT
ALARM
Page 103 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
5.1.15 External Control Circuits
(A) Remote Test/Equalize: All Rectifier Modules can be placed into the test/equalize mode by
applying a loop closure signal. The Rectifier Modules operate in the float mode when the
loop closure signal is absent.
(B) Remote High Voltage Shutdown: The high voltage shutdown circuit on all Rectifier
Modules, as described in Paragraph 3.4.6 (C), can be activated by applying a loop closure
signal. This feature is to be used only when the system is connected to battery. See
Section 6016 (Installation Instructions) for details.
(C) Rectifier Module Emergency Shutdown and Fire Alarm Disconnect: The Rectifier
Modules can be inhibited by applying a loop closure signal. Manual restart is required. This
feature is to be used only when the system is connected to battery. See Section 6016
(Installation Instructions) for details.
(D) External "System Voltage" Meter Reading: Leads can be extended from the MCA to an
external voltage source. This is the voltage source the MCA monitors for system alarms and
displays as "System Output Voltage".
(E) Test Input: The High Voltage Shutdown and/or Rectifier Module Emergency Stop circuits
can be tested without affecting the system by applying a test loop closure signal before
applying the Remote High Voltage Shutdown or Rectifier Module Emergency Shutdown loop
closure signal.
5.1.16 Optional MCA Relay Circuit Card, P/N 514348: Each circuit card adds six (6) Form-C external
alarm relay contacts to the system. Plugs into seven-slot card cage provided in each bay for
optional MCA and LMS I/O cards.
(A) Contact Rating: 2A at 30 VDC.
(B) Description of Operation: The MCA provides 25 programmable function channels.
Program each function channel to alarm for selected conditions, then program each external
alarm relay to activate if a specific function channel alarms.
MCA relays can also be programmed to activate if an LMS LED channel activates.
5.1.17 Optional MCA Input/Output (I/O) Circuit Card, P/N 524550: This I/O card provides capability
for monitoring of external shunts and binary signals. Plugs into seven-slot card cage provided in
each bay for optional MCA and LMS I/O cards. Provides 1 analog input, 1 analog output (for
remote plant output current monitoring), and 4 binary inputs.
(A) One analog input with a range of 0-50mV can be used to provide monitoring of additional
load shunt or a plant load shunt.
(B) Four binary inputs can be used to monitor dry contact closures. When the “Alternate Current
Limit” feature is used, binary input #4 is assigned to monitor the signal used to trigger the
MCA to place the rectifiers in the Alternate Current Limit mode.
(C) One analog output with a 50mV full scale output provides a value to indicate the “Total Load
Current” parameter of the NPS system.
The reading displayed for the NPS system parameter “Total Load Current” is derived from
one of two algorithms using multiple data sources. The algorithm and its data sources used
are determined by the presence and configuration of CAN I/O card(s) in the system.
1) Algorithm #1: This source is used when there are no CAN I/O cards installed OR when
the configuration of all installed CAN I/O cards is set to “Distribution” mode.
“Distribution” Mode Operation:
“Total Load Current” =
Page 104 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
NPS bay distribution node current readings,
+ CAN I/O card analog input readings,
+ LMS function channel 63 reading.
Home
The VPS ‘Total System Current’ reading (LMS channel A9002) will be passed to the
NPS through LMS function channel sixty-three. The function channel configuration
will default to provide the reading of the associated LMS channel for the VPS Total
System Current. The NPS controller will include the value of LMS function channel
sixty-four when summing the distribution load currents to determine its Total Load
Current reading to display. (associated LMS channel A9903).
Channel F63 program line is ‘F63 = A9002’ (Vortex Total Load Current).
2) Algorithm #2: This source is used when the configuration of at least one installed CAN
I/O card is set to “Auxiliary” mode.
“Auxiliary” Mode Operation:
“Total Load Current” =
Sum of CAN I/O card analog input readings (only input readings of cards
configured for “Auxiliary” operation are summed),
+ LMS function channel 63 reading.
The reading displayed for the NPS system parameter “Total Auxiliary Load” is
derived from the sum of all analog input readings of CAN I/O cards configured for
“Auxiliary” mode operation
6. OPTIONAL LMS MONITORING SYSTEM
Refer to SAG586505000
Page 105 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
PHYSICAL SIZE INFORMATION
Floor Hole Drilling Pattern Dimensions - Power Bays
0.812 Dia.
(10 PLACES)
24.38
19.86
17.23
26.56
21.24
23.94
30.00
19.38
3.03
1.30
2.27
3.58
1.72
Front
3/8-16
Welded Nut (4)
Floor Hole Drilling Pattern Dimensions - Distribution Bays
3/8-16
Welded Nut (4)
31.375
27.625
25.875
23.250
19.500
26.625
19.500
24.000
30.000
25.375
3.063 1.750
1.875
2.750
4.063
5.937
0.812 Dia.
(8 PLACES)
Front
Page 106 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Overall Dimensions - Primary and Secondary Power Bays
Six (6) 1.125" openings for 3/4" conduit.
Two (2) conduit plates with
2.5", 1.75", and 1.125" knock-outs
for 2", 1.5", and 3/4" conduit.
Six (6) 1.75" openings for 1.5" conduit
(under plate).
30.00
AC Input Wiring Access Opening(s).
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Bay
Net:
Shipping:
Rectifier
Net: 16.75
Shipping: 18.50
3. Finish: Gray.
Top View
24.375
84.00
Left Side View
Front View
Right Side View
Page 107 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Overall Dimensions - Distribution Bays
30.000
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net:
Shipping:
3. Finish: Gray.
Top View
31.375
84.000
Left Side View
Front View
Right Side View
Page 108 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
Overall Dimensions – Optional Battery Charge
Digital Temperature Compensation Probes
P/N 107021 (25 feet) and P/N 106824 (100 feet)
0.25 (6.35) DIA.
0.75
(19.05)
3.00 (76.2)
0.75 (19.05)
2.25 (57.15)
300 (7,620)
or
1200 (30,480)
0.35 (8.89)
NOTE: All dimensions are in inches and (millimeters).
Page 109 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
RELATED DOCUMENTATION
System Installation Instructions:
Section 6016
System User Instructions:
Section 6017
Color MCA Menu Tree:
Section 5886
System Equipment and Assembly Drawing:
J582140001
System Schematic Diagram:
SD582140001
System Wiring Diagram:
T582140001
Load and Battery Lug Detail Drawings:
031110100 through 031110300
LMS Installation Instructions:
Section 5879
LMS User Instructions:
Section 5847
LMS System Application Guide:
SAG586505000
LMS I/O Circuit Card Label Sheet:
520538
LMS Expansion Assembly Schematic Diagram:
SD507606
Page 110 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582140001 (Model 801NLDB, 801NLEB, 801NL-B)
SAG582140001
Issue AF, July 14, 2010
Home
REVISION RECORD
Issue
Change
Number
(ECO)
AA
LLP211167
AB
LLP211530
AC
LLP212313
AD
LLP213470
AE
AF
Description of Change
Date
New
Rectifier is now ordered as List 22.
Misc. updates.
Fan Failure statement added for NEBS. LMS
Dual MCA Option Added. Updates for latest
MCA version. DC Operating Voltage added to
Specification section. List numbers and
descriptions changed to add 208V Bay and
Rectifier Module. Distribution Bay busbars
redesigned. List numbers added for interface to
existing systems.
PCU Spec. Nos. updated. AC wiring tables
updated. Nomenclature “Dual Feed” changed to
“2 Feeds”, and “Twin Feed” to “12 Feeds”, and
“Individual Feed” to “24 Feeds”.
08/13/08
John Jasko
11/11/08
John Jasko
07/13/09
John Jasko
01/13/10
John Jasko
John Jasko
LLP213082
Updates for LMS Firmware 9.1 and MCA version
2.2.
04/12/10
LLP214119
Ordering Information: List option for List 6 and 14; List
Description for List 06 Primary Power Bay (6 AC Input
Feeds) and List 14 Secondary Power Bay (6 AC Input
Feeds); Distribution Bay Frame Grounding Wire Sizes
and Lugs Selection for List 6 and 14; AC Input
Connections for List 6 and 14.
07/14/10
Emerson Network Power, Energy Systems, North America, Inc.
1122 F Street / Lorain, Ohio 44052-2293 / (440) 288-1122
Approved
Khristebelle
Ilagan
Rich Trifiletti
Jul 15, 2010
Bram Bailey
Jul 20, 2010
www.emerson.com
In Canada:
Emerson Electric Canada Limited
122 Edward St. / St. Thomas, Ontario N5P 1Z2 / (519) 637-4900
In Mexico:
Emerson Network Power de Mexico, S.A. de C.V.
Apartado Postal 77001 / Mexico 10 D.F., MX 11200 / (525) 576-8277
Page 111 of 111
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.