POWER PROTECTION ™ INSTALLATION MANUAL 30-130 kVA, 60 Hz Single Module Systems 1+1 Redundant Systems The following WARNING applies to battery cabinets supplied with UPS sysems: INTERNAL BATTERY STRAPPING MUST BE VERIFIED BY MANUFACTURER PRIOR TO MOVING A BATTERY CABINET FROM ITS INITIAL INSTALLATION LOCATION. Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT prior to moving battery cabinets from their initial installation location. BEFORE YOU CALL... ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ DISCONTINUED PRODUCT IMPORTANT SAFETY INSTRUCTIONS Save These Instructions. 7KLVPDQXDOFRQWDLQVLPSRUWDQWLQVWUXFWLRQVWKDWVKRXOGEHIROORZHGGXULQJLQVWDOODWLRQRI\RXU 1SRZHU836DQGEDWWHULHV DISCONTINUED PRODUCT DISCONTINUED PRODUCT Table of Contents DISCONTINUED PRODUCT i DISCONTINUED PRODUCT List of Figures ¡ ¡ ¡ DISCONTINUED PRODUCT iii DISCONTINUED PRODUCT List of Tables Table 1 Table 2 Table 3 Power Wiring Terminals - Factory Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Table 310-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 DISCONTINUED PRODUCT v DISCONTINUED PRODUCT 1.0 SAFETY PRECAUTIONS ,IWKH836V\VWHPKDVDEORZQIXVHWKHFDXVHVKRXOGEHGHWHUPLQHGEHIRUH \RXUHSODFHWKHIXVH&RQWDFW/LHEHUW*OREDO6HUYLFHV DISCONTINUED PRODUCT Safety Precautions 1 2.0 INSTALLATION CONSIDERATIONS 2 Installation Considerations DISCONTINUED PRODUCT Figure 1 Npower UPS modules, left-to-right: 30-50 kVA, 65-80 kVA and 100-130 kVA DISCONTINUED PRODUCT Installation Considerations 3 3.0 UNLOADING AND HANDLING 7RUHGXFHWKHSRVVLELOLW\RIVKLSSLQJGDPDJH836FDELQHWVDUHVHFXUHGWR WKHSDOOHWDVVKRZQLQWKHGUDZLQJVDWULJKW7KHVHSDFNLQJHOHPHQWVPXVW EHFDUHIXOO\UHPRYHGEHIRUHDWWHPSWLQJWRUHPRYHWKHPRGXOHIURPWKHSDOOHW 3OHDVHIROORZWKHVHVWHSV • Cut the metal banding straps and remove. • Unbolt and remove the four corner brackets retaining the 2x4 boards. • Use forklift to remove module from pallet. 4 Unloading and Handling DISCONTINUED PRODUCT Figure 2 Front view, Npower UPS module on pallet (2) 2 X 4 X 33" LG CARDBOARD SHEET BAND USING POLYP. PLASTIC BANDING (3) PLACES BAG PLASTIC COVER UNDER CARDBOARD METAL BANDING 3/4" METAL BANDING BUCKLE CORRUGATED # 72 CARDBOARD NOT SHOWN 1967.3 77.45 REF Z REF X REF FORK LOCATIONS 1371.6 54.00 REF Figure 3 Top view, Npower UPS module on pallet FORK LOCATIONS DISCONTINUED PRODUCT Unloading and Handling 5 4.0 INSPECTIONS 4.1 External Inspections 4.2 Internal Inspections 6 Inspections DISCONTINUED PRODUCT 5.0 EQUIPMENT LOCATION 5.1 General Instructions 5.2 Special Considerations for 1+1 Redundant Systems DISCONTINUED PRODUCT Equipment Location 7 6.0 BATTERY INSTALLATION 6.1 Battery Safety Precautions 6HUYLFLQJRIEDWWHULHVVKRXOGEHSHUIRUPHGRUVXSHUYLVHGE\SHUVRQQHONQRZOHGJHDEOHRIEDWWHULHV DQGWKHUHTXLUHGSUHFDXWLRQV.HHSXQDXWKRUL]HGSHUVRQQHODZD\IURPEDWWHULHV :KHQUHSODFLQJEDWWHULHVXVHWKHVDPHQXPEHUDQGW\SHRIEDWWHULHV 8 Battery Installation DISCONTINUED PRODUCT Battery Safety Precautions in French Per CSA Requirements Instructions Importantes Concernant La Sécurité Conserver Ces Instructions DISCONTINUED PRODUCT Battery Installation 9 10 Battery Installation DISCONTINUED PRODUCT 6.2 Matching Battery Cabinets DISCONTINUED PRODUCT Battery Installation 11 6.3 Non-Standard Batteries 12 Battery Installation DISCONTINUED PRODUCT 7.0 CONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONS Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT 13 Figure 4 7.1 Grounding Diagram, A/B or G/H UPS Models, Wye Source, 3-Wire Loads Grounding for A/B or G/H UPS Models, Wye Source, 3-Wire Loads 8QJURXQGHGDQGFRUQHUJURXQGHGGHOWDVRXUFHVUHTXLUHWKDWWKH1SRZHUEH IXUQLVKHGIURPWKHIDFWRU\ZLWKDQ,VRODWHG/RDG1HXWUDODVGHVFULEHGLQ ODWHUVHFWLRQV 14 Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT Figure 5 7.2 Grounding Diagram, A/B or G/H UPS Models, Wye Source, 4-Wire Loads Grounding for A/B or G/H UPS Models, Wye Source, 4-Wire Loads 8QJURXQGHGDQGFRUQHUJURXQGHGGHOWDVRXUFHVUHTXLUHWKDWWKH1SRZHUEH IXUQLVKHGIURPWKHIDFWRU\ZLWKDQ,VRODWHG/RDG1HXWUDODVGHVFULEHGLQ ODWHUVHFWLRQV Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT 15 Figure 6 7.3 Grounding Diagram, D/E or K/L UPS Models, Delta or Wye Source, 4-Wire Loads Grounding for D/E or K/L UPS Models, Delta or Wye Source, 3- or 4-Wire Loads *URXQG)DXOW,QWHUUXSWHUVVKRXOGEHVHWWRWROHUDWHDSSUR[LPDWHO\F\FOHV PLOOLVHFRQGVRIUHFLUFXODWLQJFXUUHQWWKDWPD\EHSUHVHQWGXULQJ WUDQVIHUDQGUHWUDQVIHURSHUDWLRQV 16 Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT Figure 7 7.4 Grounding Diagram, R/S or X/Y UPS Model, Delta Source, 3-Wire Loads Grounding for R/S or X/Y UPS Models, Delta Source, 3-Wire Loads Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT 17 Figure 8 Grounding Diagram, A/B or G/H UPS Models, 1+1 Configuration A/B CONFIGURATION 4W+G 3W+G Y N G SYSTEM PARALLELING CABINET 4W+G 3 OR 4W+G CRITICAL LOAD A/B CONFIGURATION 4W+G 4W+G N G 3W+G Y N G 7.5 Grounding for A/B or G/H UPS Models, 1+1 Configuration 18 Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT Figure 9 Grounding Diagram, D/E or K/L UPS Models, 1+1 Configuration D/E or K/L CONFIGURATION 3W+G Y 3W+G N G SYSTEM PARALLELING CABINET 4W+G 3 OR 4W+G CRITICAL LOAD D/E or K/L CONFIGURATION N 4W+G G 3W+G 3W+G Y LOCAL GROUNDING ELECTRODE N G 7.6 Grounding for D/E or K/L UPS Models, 1+1 Configuration Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT 19 Figure 10 Grounding Diagram, R/S or X/Y UPS Models, 1+1 Configuration R/S or X/Y CONFIGURATION 3W+G Y 3W+G N G SYSTEM PARALLELING CABINET 4W+G 3W+G ONLY CRITICAL LOAD R/S or X/Y CONFIGURATION 4W+G 3W+G N G 3W+G Y LOCAL GROUNDING ELECTRODE N G 7.7 Grounding for R/S or X/Y UPS Models, 1+1 Configuration 20 Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT 7.8 Grounding for 2 Npower UPS Modules feeding a Static Transfer Switch 7.9 Grounding Configurations, Battery Systems Configuring Your Neutral and Ground Connections DISCONTINUED PRODUCT 21 8.0 WIRING CONSIDERATIONS 22 Wiring Considerations DISCONTINUED PRODUCT 8.1 Power Wiring DISCONTINUED PRODUCT Wiring Considerations 23 8.2 Control Wiring 24 Wiring Considerations DISCONTINUED PRODUCT 8.3 Battery Wiring $/LHEHUW%DWWHU\6SHFLDOLVWFDQSHUIRUPDGHWDLOHGLQVSHFWLRQRIWKHHQWLUH EDWWHU\V\VWHPWRHQVXUHLWPHHWVFXUUHQW,(((VWDQGDUGV7KLVLQVSHFWLRQ VHUYLFHLVUHFRPPHQGHGEHFDXVHEDWWHULHVDUHDYHU\FULWLFDOSDUWRIWKH836 V\VWHP DISCONTINUED PRODUCT Wiring Considerations 25 9.0 WIRING CONNECTIONS 0DNHVXUHDOOUHTXLUHGZLULQJEHWZHHQWKH836PRGXOHDQGWKHRSWLRQDO FDELQHWVLVFRPSOHWHG2EVHUYHSKDVHURWDWLRQ DC power cables (and ground) from Battery Cabinet to UPS Module, and between Battery Cabinets. 26 Wiring Connections DISCONTINUED PRODUCT Observe polarity. DC power cables should be installed in matched pairs (positive and negative). DISCONTINUED PRODUCT Wiring Connections 27 10.0 WIRING INSPECTION 9HULI\DOOSRZHUFRQQHFWLRQVDUHWLJKW 9HULI\DOOFRQWUROZLUHWHUPLQDWLRQVDUHWLJKW 9HULI\DOOSRZHUZLUHVDQGFRQQHFWLRQVKDYHSURSHUVSDFLQJEHWZHHQH[SRVHGVXUIDFHVSKDVHWR SKDVHDQGSKDVHWRJURXQG 9HULI\WKDWDOOFRQWUROZLUHVDUHUXQLQLQGLYLGXDOVHSDUDWHVWHHOFRQGXLW Table 1 Power Wiring Terminals - Factory Supplied UPS Module Rating Connection Type 30-130 kVA Bus bars. See Outline Drawings for dimensions. Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this manual) and associated notes of the National Electrical Code (NFPA 70). Use commercially available solderless lugs for the wire size required for your application. Connect wire to the lug using tools and procedures specified by the lug manufacturer. Table 2 Torque Specifications Nut and Bolt Combinations Bolt Shaft Size 1/4 5/16 3/8 Grade 2 Standard Electrical Connections with Belleville Washers Lb-in N-m Lb-in 53 6.0 46 192 22 107 12 1/2 428 48 Cable Size or Range Lb-in N-m #6 - #4 100 11 1/0 - 2/0 150 17 250 - 400 MCM 250 Circuit Breakers With Compression Lugs (For Power Wiring) #3 - #1 3/0 - 200 MCM 125 14 200 23 500 - 700 MCM 300 34 AWG Wire Size or Range Lb-in N-m #22 - #14 3.5 to 5.3 0.4 to 0.6 28 Terminal Block Compression Lugs (For Control Wiring) Use the values in this table unless the equipment is labeled with a different torque value. 28 Wiring Inspection DISCONTINUED PRODUCT N-m 5.2 60 6.8 256 29 95 11 Table 3 Table 310-16 Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)1 Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F) Size AWG kcmil Temperature Rating of Conductor. See Table 310-13. Size 60°C (140°F) 75°C (167°F) 90°C (194°F) 60°C (140°F) 75°C (167°F) 90°C (194°F) Types TW* UF* Types FEPW*, RH, RHW*, THHW*, THW*, THWN*, XHHW*, USE*, ZW* Types TBS, SA, SIS FEP*, FEPB*, MI, RHH*, RHW-2, THHN*, THHW*, THW-2, THWN-2, USE-2, XHH, XHHW* XHHW-2, ZW-2 Types TW* UF* Types RH*, RHW*, THHW*, THW*, THWN*, XHHW*, USE* Types TBS, SA, SIS, THHN*, THHW*, THW-2, THWN-2, RHH*, RHW-2, USE-2, XHH, XHHW*, XHHW-2, ZW-2 Copper AWG kcmil Aluminum or Copper-Clad Aluminum 18 16 14 12 10 8 ....... ....... 20† 25† 30 40 ....... ....... 20† 25† 35† 50 14 18 25† 30† 40† 55 ....... ....... ....... 20† 25 30 ....... ....... ....... 20† 30† 40 ....... ....... ....... 25† 35† 45 ....... ....... ....... 12 10 8 6 4 3 2 1 55 70 85 95 110 65 85 100 115 130 75 95 110 130 150 40 55 65 75 85 50 65 75 90 100 60 75 85 100 115 6 4 3 2 1 1/0 2/0 3/0 4/0 125 145 165 195 150 175 200 230 170 195 225 260 100 115 130 150 120 135 155 180 135 150 175 205 1/0 2/0 3/0 4/0 250 300 350 400 500 215 240 260 280 320 255 285 310 335 380 290 320 350 380 430 170 190 210 225 260 205 230 250 270 310 230 255 280 305 350 250 300 350 400 500 600 700 750 800 900 355 385 400 410 435 420 460 475 490 520 475 520 535 555 585 285 310 320 330 355 340 375 385 395 425 385 420 435 450 480 600 700 750 800 900 1000 1250 1500 1750 2000 455 495 520 545 560 545 590 625 650 665 615 665 705 735 750 375 405 435 455 470 445 485 520 545 560 500 545 585 615 630 1000 1250 1500 1750 2000 Correction Factors Ambient Temp °C 21-25 26-30 31-35 36-40 41-45 46-50 51-55 56-60 61-70 71-80 For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor shown below. Ambient Temp °F 1.08 1.00 .91 .82 .71 .58 .41 ....... ....... ....... 70-77 78-86 87-95 96-104 105-113 114-122 123-131 132-140 141-158 159-176 1.05 1.00 .94 .88 .82 .75 .67 .58 .33 ....... 1.04 1.00 .96 .91 .87 .82 .76 .71 .58 .41 1.08 1.00 .91 .82 .71 .58 .41 ....... ....... ....... 1.05 1.00 .94 .88 .82 .75 .67 .58 .33 ....... 1.04 1.00 .96 .91 .87 .82 .76 .71 .58 .41 * Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No.12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. 1 Reprinted with permission from NEC 1999, NFPA 70, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety. DISCONTINUED PRODUCT Wiring Inspection 29 11.0 INSTALLATION DRAWINGS Figure 11 Outline Drawing, 30-50 kVA UPS 30 Installation Drawings DISCONTINUED PRODUCT Figure 12 Outline Drawing, 65-80 kVA UPS DISCONTINUED PRODUCT Installation Drawings 31 Figure 13 Outline Drawing, 100-130 kVA UPS 32 Installation Drawings DISCONTINUED PRODUCT DISCONTINUED PRODUCT Installation Drawings REF. DWG. DRAWN BY V CARMONA CHK BY BIB BOARD ACCESS TOP VIEW FRONT VIEW WITH DOOR CENTER GRAVITY OUTLINE DRAWING 25" BATTERY CABINET NPOWER SUPPORT TRAY & SUPPORT BRACKET (SEE NOTE 15) DC BUS BARS 1/22/03 DATE UBC11001 FILE NAME: Batts\UBC11001-03 3 REV. NO. DWG. NO. SIDE VIEW WITH COVER REMOVED CENTER GRAVITY DETAIL A 2.72 LEVELER DETAIL FOR DC BUS BARS 15. "BEFORE SLIDING OUT BATTERIES ON BATTERY TRAY" POSITION SUPPORT TRAY AND ATTACH TO CABINET. THEN SECURE (2) SUPPORT BRACKETS TO THE SUPPORT TRAY AND TO THE CABINET. REFER TO THE APPROPRIATE USERS MANUAL FOR FURTHER DESCRIPTION & DETAILS. 14. REFER TO DETAIL A FOR DIMENSION TO FRAME WITH SIDE PANEL REMOVED. SIDE PANELS ARE REMOVED BETWEEN ADJACENT UNITS WHICH ARE BOLTED TOGETHER. 13. EACH MOUNTING LOCATION IS SUPPORTED BY (2) 10 GA. (.135") GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP. MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM UNDERNEATH UNIT BASE. 12. THREADED MOUNTING HOLES USED FOR SEISMIC ANCHORING OR FLOORSTAND. NOTE, IF FLOORSTAND IS USED THE WEIGHT OF THE UNIT MUST BE SUPPORTED UNDER ALL CASTERS. 11. APPROX WEIGHT OF CABINET IS 1500 TO 3000 LBS. 10. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING. 9. COLOR - IBM OFF WHITE. 8. RECOMMENDED OPERATING TEMPERATURE RANGE: 68°F-77°F (20°C-25°C). 7. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES. 6. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE NOT RECOMMENDED. 5. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUIT. 4. EXTERIOR CABLE ENTRY AVAILABLE THROUGH REMOVABLE TOP ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE, AND REPLACE. 3. KEEP CABINET WITHIN 15° OF VERTICAL WHILE HANDLING. 2. MIN CLEARANCE 36 INCHES IN FRONT, 12 INCHES AT TOP FOR AIR EXHAUST. 1. ALL DIMENSIONS ARE IN INCHES. NOTES: 1050 DEARBORN DRIVE, COLUMBUS, OHIO 43229 CONTROL AND POWER WIRE SIDE ACCESS APPROX AREA 4.6 x 2.2 (BOTH SIDES) REAR OF UNIT SHOWN WITHOUT SIDE PANEL 12mm DIA. THREADED MOUNTING HOLE (4) TYP. (SEE NOTES 12 & 13) (SEE DETAIL A) 12MM THREADED MOUNTING HOLE CASTER CENTERS CIRCUIT BREAKER NOTE: (10)TRAY SHOWN. (8) TRAY FOR FR200 BATTERY ASSY AND SMALLER BATTERIES DC BUS BARS MOTOR OPERATOR OPTIONAL BOTTOM VIEW 12MM CENTERS FRONT CASTER CENTERS CIRCUIT BREAKER 12MM CENTERS FRONT VIEW WITH DOOR AND BARRIER REMOVED CONDUIT ENTRY 6.5 x 6.0 TOP ONLY 2 PLACES MAX DOOR SWING 120° BATTERY SERVICE ACCESS Figure 14 Outline Drawing, Battery Power Pack, 25-Inch Cabinet 33 34 Installation Drawings DISCONTINUED PRODUCT REF. DWG. DRAWN BY V CARMONA CHK BY TOP VIEW FRONT VIEW CENTER GRAVITY BATTERIES 12MM CENTERS OUTLINE DRAWING 49" BATTERY CABINET NPOWER CENTER GRAVITY 3 1/22/03 DATE UBC11003 FILE NAME: Batts\UBC11003-03 REV. NO. DWG. NO. SIDE VIEW WITH COVER REMOVED SUPPORT TRAY & SUPPORT BRACKET (SEE NOTE 15) BUS BARS CIRCUIT BREAKER LEVELER DETAIL FOR DC BUS BARS 15. "BEFORE SLIDING OUT BATTERIES ON BATTERY TRAY" POSITION SUPPORT TRAY AND ATTACH TO CABINET. THEN SECURE (2) SUPPORT BRACKETS TO THE SUPPORT TRAY AND TO THE CABINET. REFER TO THE APPROPRIATE LIEBERT USERS MANUAL FOR FURTHER DESCRIPTION & DETAILS. 14. REFER TO DETAIL A FOR DIMENSION TO FRAME WITH SIDE PANEL REMOVED. SIDE PANELS ARE REMOVED BETWEEN ADJACENT UNITS WHICH ARE BOLTED TOGETHER. 13. EACH MOUNTING LOCATION IS SUPPORTED BY (2) 10 GA. (.135") GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP. MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM UNDERNEATH UNIT BASE. 12. THREADED MOUNTING HOLES USED FOR SEISMIC ANCHORING OR FLOORSTAND. NOTE, IF FLOORSTAND IS USED THE WEIGHT OF THE UNIT MUST BE SUPPORTED UNDER ALL CASTERS. 11. APPROX WEIGHT OF CABINET IS 3500 TO 5100 LBS. 10. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING. 9. COLOR - IBM OFF WHITE. 8. RECOMMENDED OPERATING TEMPERATURE RANGE: 68°F-77°F (20°C-25°C). 7. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES. 6. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE NOT RECOMMENDED. 5. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUIT. 4. EXTERIOR CABLE ENTRY AVAILABLE THROUGH REMOVABLE TOP AND BOTTOM ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE, AND REPLACE. 3. KEEP CABINET WITHIN 15° OF VERTICAL WHILE HANDLING. 2. MIN CLEARANCE 36 INCHES IN FRONT, 12 INCHES AT TOP FOR AIR EXHAUST. 1. ALL DIMENSIONS ARE IN INCHES. NOTES: 1050 DEARBORN DRIVE, COLUMBUS, OHIO 43229 CONTROL AND POWER WIRE SIDE ACCESS APPROX AREA 4.56 x 2.25 (BOTH SIDES) DETAIL A REAR OF UNIT SHOWN WITHOUT SIDE PANEL 2.72 12mm DIA. THREADED MOUNTING HOLE (6) TYP. (SEE NOTES 12 & 13) (SEE DETAIL A) CASTER CENTERS 12MM THREADED MOUNTING HOLE MOTOR OPERATOR OPTIONAL CIRCUIT BREAKER BOTTOM VIEW 12MM CENTERS FRONT CASTER CENTERS FRONT VIEW WITH DOORS REMOVED DC BUS BARS CONDUIT ENTRY 5.5 X 11.0 TOP AND BOTTOM MAX DOOR SWING 120°- LIFT OFF DOORS AIR EXHAUST CUTOUT 6 PLACES Figure 15 Outline Drawing, Battery Power Pack, 49-Inch Cabinet Figure 16 Outline Drawing, Maintenance Bypass Cabinet, “L” Configuration DISCONTINUED PRODUCT Installation Drawings 35 Figure 17 Outline Drawing, Maintenance Bypass Cabinet, “N” Configuration 36 Installation Drawings DISCONTINUED PRODUCT Figure 18 Outline Drawing, Maintenance Bypass Cabinet, “P” Configuration DISCONTINUED PRODUCT Installation Drawings 37 Figure 19 Outline Drawing, Maintenance Bypass Cabinet, “Q” Configuration 38 Installation Drawings DISCONTINUED PRODUCT Figure 20 Outline Drawing, Slimline Distribution Cabinet, Top Cable Exit, Panelboards Only DISCONTINUED PRODUCT Installation Drawings 39 Figure 21 Outline Drawing, Slimline Distribution Cabinet, Bottom Cable Exit, Panelboards Only 40 Installation Drawings DISCONTINUED PRODUCT Figure 22 Outline Drawing, Slimline Distribution Cabinet, with Panelboard and Subfeed Breakers DISCONTINUED PRODUCT Installation Drawings 41 Figure 23 Outline Drawing, Slimline Distribution Cabinet, with 100-250A Subfeed Breakers Only 42 Installation Drawings DISCONTINUED PRODUCT Figure 24 Outline Drawing, Slimline Distribution Cabinet, with 300-400A Subfeed Breakers Only DISCONTINUED PRODUCT Installation Drawings 43 44 Installation Drawings DISCONTINUED PRODUCT REF. DWG. DRAWN BY M MIERSEN CHK BY OUTLINE DRAWING NPOWER 1+1 SYSTEM PARALLELING PANELBOARD CONFIGURATION "N", COMMON INFORMATION 6/17/03 DATE U3711007 1050 DEARBORN DRIVE, COLUMBUS, OHIO 43229 FILE NAME: I/APPL/NPOWER/DRAWINGS/OUTLINES/1+1SPC/U3711007/(C) REV. NO. DWG. NO. Figure 25 Specifications Table, 1+1 Paralleling Panelboard Configuration “N” DISCONTINUED PRODUCT Installation Drawings REF. DWG. DRAWN BY M MIERSEN CHK BY RIGHT SIDE VIEW OUTLINE DRAWING NPOWER 1+1 SYSTEM PARALLELING PANELBOARD CONFIGURATION "N", SIZE "A" PANELBOARD ENDWALL FRONT VIEW WITH DOOR OPEN AND ACCENT REMOVED 6/17/03 DATE U3711008 9. REFERENCE COMMON INFORMATION DRAWING #U3711007 FOR ADDITIONAL PANELBOARD DETAILS. 8. LUG SIZE RANGES ARE BASED ON COPPER CONDUCTORS. ALUMINUM AND COPPER-CLAD ALUMINUM CONDUCTORS ARE NOT RECOMMENDED. 7. OVERCURRENT PROTECTIVE DEVICES ARE AUTOMATIC MOLDED CASE CIRCUIT BREAKERS. 6. COPPER BUSSING IS STANDARD. 5. FRONT ACCESS ONLY REQUIRED PER NEC ARTICLE 110-16. TOP OR BOTTOM CABLE ENTRY/EXIT. 4. NEMA-1 PANELBOARD CONSTRUCTED FOR WALL-MOUNTING ONLY. 3. PANELBOARD EXTERIOR IS CODE GAUGE GALVANIZED STEEL. BOTH ENDWALLS ARE BLANK. ANSI 49 GRAY BAKED ENAMEL FINISH. LOCK IS FLUSH MOUNTED. 2. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES. 1. SIZE "A" SYSTEM PARALLELING PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA. NOTES: 1050 DEARBORN DRIVE, COLUMBUS, OHIO 43229 FILE NAME: I/APPL/NPOWER/DRAWINGS/OUTLINES/1+1SPC/U3711008/(C) REV. NO. DWG. NO. ONE-LINE LEGEND ONE-LINE DIAGRAM FRONT VIEW WITH DOOR CLOSED Figure 26 Outline Drawing, 1+1 Paralleling Panelboard, Configuration “N,” Size “A” 45 46 Installation Drawings DISCONTINUED PRODUCT REF. DWG. DRAWN BY M MIERSEN CHK BY RIGHT SIDE VIEW OUTLINE DRAWING NPOWER 1+1 SYSTEM PARALLELING PANELBOARD CONFIGURATION "N", SIZE "B" PANELBOARD ENDWALL FRONT VIEW WITH DOOR OPEN AND ACCENT REMOVED 6/17/03 DATE U3711009 9. REFERENCE COMMON INFORMATION DRAWING #U3711007 FOR ADDITIONAL PANELBOARD DETAILS. 8. LUG SIZE RANGES ARE BASED ON COPPER CONDUCTORS. ALUMINUM AND COPPER-CLAD ALUMINUM CONDUCTORS ARE NOT RECOMMENDED. 7. OVERCURRENT PROTECTION DEVICES ARE AUTOMATIC MOLDED CASE CIRCUIT BREAKERS. 6. COPPER BUSSING IS STANDARD. 5. FRONT ACCESS ONLY REQUIRED PER NEC ARTICLE 110-16. TOP OR BOTTOM CABLE ENTRY/EXIT. 4. NEMA-1 PANELBOARD CONSTRUCTED FOR WALL-MOUNTING ONLY. 3. PANELBOARD EXTERIOR IS CODE GAUGE GALVANIZED STEEL. BOTH ENDWALLS ARE BLANK. ANSI 49 GRAY BAKED ENAMEL FINISH. (2) FLUSH MOUNTED LOCKS. 2. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES. 1. SIZE "B" SYSTEM PARALLELING PANELBOARDS ARE UL AND CSA LISTED. NOTES: 1050 DEARBORN DRIVE, COLUMBUS, OHIO 43229 FILE NAME: I/APPL/NPOWER/DRAWINGS/OUTLINES/1+1SPC/U3711009/(C) REV. NO. DWG. NO. ONE-LINE LEGEND ONE-LINE DIAGRAM FRONT VIEW WITH DOOR CLOSED Figure 27 Outline Drawing, 1+1 Paralleling Panelboard, Configuration “N,” Size “B” DISCONTINUED PRODUCT Installation Drawings REF. DWG. DRAWN BY M MIERSEN CHK BY RIGHT SIDE VIEW OUTLINE DRAWING NPOWER 1+1 SYSTEM PARALLELING PANELBOARD CONFIGURATION "N", SIZE "C" PANELBOARD ENDWALL FRONT VIEW WITH DOOR OPEN AND ACCENT REMOVED 6/17/03 DATE U3711011 9. REFERENCE COMMON INFORMATION DRAWING #U3711007 FOR ADDITIONAL PANELBOARD DETAILS. 8. LUG SIZE RANGES ARE BASED ON COPPER CONDUCTORS. ALUMINUM AND COPPER-CLAD ALUMINUM CONDUCTORS ARE NOT RECOMMENDED. 7. OVERCURRENT PROTECTION DEVICES ARE AUTOMATIC MOLDED CASE CIRCUIT BREAKERS. 6. COPPER BUSSING IS STANDARD. 5. FRONT ACCESS ONLY REQUIRED PER NEC ARTICLE 110-16. TOP OR BOTTOM CABLE ENTRY/EXIT. 4. NEMA-1 PANELBOARD CONSTRUCTED FOR WALL-MOUNTING ONLY. 3. PANELBOARD EXTERIOR IS CODE GAUGE GALVANIZED STEEL. BOTH ENDWALLS ARE BLANK. ANSI 49 GRAY BAKED ENAMEL FINISH. (1) FLUSH MOUNTED, 3-POINT LOCK. 2. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES. 1. SIZE "C" SYSTEM PARALLELING PANELBOARDS ARE UL AND CSA LISTED. NOTES: 1050 DEARBORN DRIVE, COLUMBUS, OHIO 43229 FILE NAME: I/APPL/NPOWER/DRAWINGS/OUTLINE/1+1SPC/U3711011/(C) REV. NO. DWG. NO. ONE-LINE LEGEND ONE-LINE DIAGRAM FRONT VIEW WITH DOOR CLOSED Figure 28 Outline Drawing, 1+1 Paralleling Panelboard, Configuration “N,” Size “C” 47 Figure 29 Outline Drawing, Seismic Anchoring, 30-50 kVA UPS 48 Installation Drawings DISCONTINUED PRODUCT Figure 30 Outline Drawing, Seismic Anchoring, 65-80 kVA UPS DISCONTINUED PRODUCT Installation Drawings 49 Figure 31 Outline Drawing, Seismic Anchoring, 100-130 kVA UPS 50 Installation Drawings DISCONTINUED PRODUCT Figure 32 Outline Drawing, Remote Battery Breaker 30 - 130 kVA DISCONTINUED PRODUCT Installation Drawings 51 Figure 33 Outline Drawing, Remote Battery Breaker with Motor Operator, 30 - 130 kVA 52 Installation Drawings DISCONTINUED PRODUCT Figure 34 Outline Drawing, Remote Battery Breaker with BIB Installed DISCONTINUED PRODUCT Installation Drawings 53 Figure 35 Outline Drawing, Remote Alarm Status Panel 54 Installation Drawings DISCONTINUED PRODUCT Figure 36 Outline Drawing, LBS Control Panel DISCONTINUED PRODUCT Installation Drawings 55 Figure 37 Outline Drawing, LBS Alarm Status Contacts 56 Installation Drawings DISCONTINUED PRODUCT Figure 38 Outline Drawing, LBS Transformer Panel DISCONTINUED PRODUCT Installation Drawings 57 Figure 39 Control Wiring, LBS Interconnection Wiring Diagram for Configs A, B, R, S 58 Installation Drawings DISCONTINUED PRODUCT Figure 40 Control Wiring, LBS Interconnection Wiring Diagram for Configs D, E DISCONTINUED PRODUCT Installation Drawings 59 Figure 41 Control Wiring, 30 - 130 kVA UPS 60 Installation Drawings DISCONTINUED PRODUCT DISCONTINUED PRODUCT Installation Drawings REF. DWG. DRAWN BY M MIERSEN CHK BY IFM BOARD UPS #1 1 2 3 4 5 6 7 8 9 10 CONTROL WIRING ILLUSTRATION 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CONTROL WIRING NPOWER 1+1 MODULE CONTROL CONNECTIONS CAT-5 PATCH CABLE CONNECTION NPOWER TB57 J3 J2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 TB57 J3 J2 IFM BOARD DETAIL 6/17/03 DATE U3713027 1050 DEARBORN DRIVE COLUMBUS, OHIO 43229 6. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES. 5. REFER TO UPS MODULE CONNECTION LOCATION DIAGRAM FOR LOCATION OF IFM OPTION BOARD. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT. 4. CONTROL WIRING (BY OTHERS) MUST BE RUN SEPARATE FROM THE POWER WIRING. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT. 3. BOTH UPS MODULES MUST BE CONFIGURED FOR 1+1 OPERATION. SEE OPTIONS MANUAL FOR DETAILS. 2. MAXIMUM CABLE LENGTH FOR CAT-5 PATCH CABLE IS 200 FEET. 1. MODULE TO MODULE INTERCONNECTION CABLE ILLUSTRATED IS A STANDARD CATEGORY-5 ETHERNET PATCH CABLE. UPS SHIPS WITH A 25-FOOT CAT-5 PATCH CABLE FOR CUSTOMER USE. FOR APPLICATION REQUIRING LONGER CABLE LENGTH, A LONGER CAT-5 CABLE IS REQUIRED. PROVIDED BY OTHERS. CONNECTION CAN BE MADE VIA THE CAT-5 PATCH CABLE AS SHOWN, OR BY TWISTED PAIR CONDUCTORS, SHOWN ON DWG# U37016. ONLY ONE CONTROL CABLE GROUP REQUIRED BETWEEN MODULES. NOTES: FILE NAME: Npower\Drawings\Options1+1\U3713027\(D) REV. NO. DWG. NO. IFM BOARD UPS #2 Figure 42 Control Wiring, 1+1 Category 5 Patch Cable Connection 61 62 Installation Drawings DISCONTINUED PRODUCT REF. DWG. DRAWN BY M MIERSEN CHK BY IFM BOARD UPS #1 1 2 3 4 5 6 7 8 9 10 CONTROL WIRING ILLUSTRATION B R B R B R B B R R B R B B R R 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CONTROL WIRING NPOWER 1+1 MODULE CONTROL CONNECTIONS TWISTED PAIR CABLE CONNECTION NPOWER TB57 J3 J2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 TB57 J3 J2 IFM BOARD DETAIL 6/17/03 DATE U3713026 1050 DEARBORN DRIVE COLUMBUS, OHIO 43229 6. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES. 5. REFER TO UPS MODULE CONNECTION LOCATION DIAGRAM FOR LOCATION OF IFM OPTION BOARD. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT. 4. CONTROL WIRING (BY OTHERS) MUST BE RUN SEPARATE FROM THE POWER WIRING. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT. 3. BOTH UPS MODULES MUST BE CONFIGURED FOR 1+1 OPERATION. SEE OPTIONS MANUAL FOR DETAILS. 2. MAXIMUM TWISTED PAIR WIRE LENGTH IS 100 FEET. TERMINAL STRIP ACCOMODATES 18 - 22 AWG STRANDED AND SHIELDED CABLE. 22 AWG CABLE RECOMMENDED. 1. MODULE TO MODULE INTERCONNECTION CABLE ILLUSTRATED IS FOR TWISTED PAIR TERMINAL WIRING. ONLY ONE CONTROL CABLE GROUP REQUIRED BETWEEN MODULES. CONNECTION CAN BE MADE VIA TWISTED PAIR CONDUCTORS AS SHOWN, OR BY CATEGORY-5 ETHERNET PATCH CABLE, SHOWN ON DWG# U37017. UPS SHIPS WITH A 25-FOOT CAT-5 PATCH CABLE FOR CUSTOMER USE. FOR APPLICATIONS REQUIRING LONGER CABLE LENGTH, THE TWISTED PAIR CONDUCTORS OR A LONGER CAT-5 CABLE IS REQUIRED. PROVIDED BY OTHERS. NOTES: FILE NAME: Npower\Drawings\Options1+1\U3713026\(D) REV. NO. DWG. NO. IFM BOARD UPS #2 Figure 43 Control Wiring, 1+1 Twisted-Pair Cable Connection Figure 44 Control Wiring, Remote Alarm Status Panel Option DISCONTINUED PRODUCT Installation Drawings 63 Figure 45 Control Wiring, 2 or 3 Remote Alarm Status Panels 64 Installation Drawings DISCONTINUED PRODUCT Figure 46 Control Wiring, 3 Remote Alarm Status Panels with Stub Connections DISCONTINUED PRODUCT Installation Drawings 65 Figure 47 Control Wiring, Site Scan Interface 66 Installation Drawings DISCONTINUED PRODUCT Figure 48 Control Wiring, Programmable Relay Board Option DISCONTINUED PRODUCT Installation Drawings 67 Figure 49 Control Wiring, Input Contact Isolator Board 68 Installation Drawings DISCONTINUED PRODUCT Figure 50 Control Wiring, NIC Option DISCONTINUED PRODUCT Installation Drawings 69 Figure 51 Control Wiring, Power Supply Option 70 Installation Drawings DISCONTINUED PRODUCT Figure 52 Control Wiring, Internal Modem Option DISCONTINUED PRODUCT Installation Drawings 71 Figure 53 Control Wiring, AS 400 Signal Cable Option 72 Installation Drawings DISCONTINUED PRODUCT Figure 54 Control Wiring, Open Wire Cable Adaptor Option DISCONTINUED PRODUCT Installation Drawings 73 Figure 55 Control Connection Diagram 50 --130 kVA 74 Installation Drawings DISCONTINUED PRODUCT Figure 56 Control Connection Location Diagram, 30-130 kVA UPS DISCONTINUED PRODUCT Installation Drawings 75 Figure 57 Terminal Details, 30 - 50 kVA UPS 76 Installation Drawings DISCONTINUED PRODUCT Figure 58 Terminal Details, 65 - 80 kVA UPS DISCONTINUED PRODUCT Installation Drawings 77 Figure 59 Terminal Details, 100 - 130 kVA UPS 78 Installation Drawings DISCONTINUED PRODUCT Figure 60 Schematic Diagram Maintenance Bypass Interlock System DISCONTINUED PRODUCT Installation Drawings 79 Figure 61 Schematic Diagram Maintenance Bypass Interlock System with EPO 80 Installation Drawings DISCONTINUED PRODUCT Figure 62 Line-Up Detail Maintenance Bypass and Distribution Cabinets DISCONTINUED PRODUCT Installation Drawings 81 Figure 63 Wiring Diagram, UPS with Single Battery Cabinet 82 Installation Drawings DISCONTINUED PRODUCT Figure 64 Interconnection Diagram, UPS Module with Multiple Battery Cabinets DISCONTINUED PRODUCT Installation Drawings 83 Figure 65 Circuit Breaker Schedule, Maintenance Bypass Cabinet, 30 - 130 kVA 84 Installation Drawings DISCONTINUED PRODUCT DISCONTINUED PRODUCT kW 24 24 24 32 32 32 40 40 40 52 52 52 64 64 64 80 80 80 104 104 104 Approx. Unpacked Weight (Pounds) 2,200 2,100 1,900 2,200 2,100 1,900 2,200 2,100 1,900 2,700 2,500 2,300 2,700 2,500 2,300 3,800 3,600 3,400 3,800 3,600 3,400 14 Concentrated Floor Cooling Loading Air (Lb/SqFt) (CFM) 307 720 294 720 265 720 307 720 294 720 265 720 307 720 294 720 265 720 304 960 284 960 262 960 304 960 284 960 262 960 342 1440 324 1440 305 1440 342 1440 324 1440 305 1440 — — 85 1. Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limit are defined in NEC 100. Maximum input current is controlled by current limit setting which is adjustable. Values shown are for maximum setting of 125%. Standard factory setting is 115%. 2. Nominal AC output current (considered continuous) is based on full rated output load. 3. OCPD=Overcurrent Protection Device. 4. Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input is recommended to be provided by separate overcurrent protection devices. 5. UPS output load cables must be run in separate conduit from input cables. 6. Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (measured at the module) at maximum discharge current. 7. Grounding conductors to be sized per NEC 250-122. Neutral conductors to be sized for full capacity for systems with 4-wire loads, 310-15 (b) (4), per NEC, and half capacity for systems with 3wire loads. 8. Rectifier AC Input: 3-phase, 3-wire, plus ground. AC Output to Load: 3-phase, 3 or 4-wire, plus ground. Bypass AC Input: 3-phase, 3 or 4-wire, plus ground. Module DC Input from Battery: 2-wire, (positive and negative). 9. All wiring is to be in accordance with National and Local Electrical Codes. 10. Minimum access clearance is 3 feet front and 1 foot above UPS. 11. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. Conduit or wireway must not obstruct removal of top panels. 12. Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors. 13. 10% maximum input harmonic current and 0.92-0.95 lagging input power factor at full load with optional input filter. 30% maximum input harmonic current and 0.85 lagging input power factor at full load without optional input filter. 14. Dimensions and weights shown do not include Battery Cabinet, Slim-Line Distribution Cabinet or other options. Max. Max. Heat Battery Dissipation Dimensions Disch. BTU/hr WxDxH (Amps) Full Load (Inches) 66 8,500 32x32.5x71 66 7,500 32x32.5x71 66 7,500 32x32.5x71 88 11,000 32x32.5x71 88 10,000 32x32.5x71 88 10,000 32x32.5x71 109 14,000 32x32.5x71 109 12,000 32x32.5x71 109 12,000 32x32.5x71 141 18,000 39x32.5x71 141 15,000 39x32.5x71 141 15,000 39x32.5x71 174 22,000 39x32.5x71 174 18,000 39x32.5x71 174 18,000 39x32.5x71 218 26,000 49x32.5x71 218 21,000 49x32.5x71 218 21,000 49x32.5x71 283 33,000 49x32.5x71 283 27,000 49x32.5x71 283 27,000 49x32.5x71 6,8,9,11,12 14 480 or 208 VAC Input AC Output Standard AC Input AC Input with Filter without Filter Option Current RecomRecomRec. Battery mended mended KW Input Output Nom Max OPCD Nom Max OCPD Nom OPCD 208 208 92 114 150 80 99 125 83 125 26 480 208 38 48 70 33 41 50 83 125 26 480 480 38 48 70 33 41 50 36 50 26 208 208 122 153 200 106 133 175 111 150 34 480 208 51 64 90 44 55 70 111 150 34 480 480 51 64 90 44 55 70 48 60 34 208 208 153 191 250 133 166 200 139 175 43 480 208 64 80 100 55 69 100 139 175 43 480 480 64 80 100 55 69 100 60 80 43 208 208 193 242 350 171 213 300 180 225 55 480 208 80 99 150 70 88 125 180 225 55 480 480 80 99 150 70 88 125 78 100 55 208 208 238 298 400 210 262 350 222 300 68 480 208 98 122 175 87 108 150 222 300 68 480 480 98 122 175 87 108 150 96 125 68 208 208 296 370 500 261 326 400 278 350 85 480 208 122 152 225 108 135 175 278 350 85 480 480 122 152 225 108 135 175 120 150 85 208 208 385 481 700 339 420 500 361 450 111 480 208 158 198 300 140 175 225 361 450 111 480 480 158 198 300 140 175 225 156 200 111 — 1,3,4,5,7,8, 9,11,12, 13 2,3,5,7,8,9,11,12 AC Voltage Notes For Table: kVA 30 30 30 40 40 40 50 50 50 65 65 65 80 80 80 100 100 100 130 130 130 Notes: UPS Rating Appendix A: Site Planning Data DISCONTINUED PRODUCT 86 kVA 30 30 40 40 50 50 65 65 80 80 100 100 130 130 Notes: kW 24 24 32 32 40 40 52 52 64 64 80 80 104 104 UPS Rating Standard AC Input AC Input with Filter without Filter Option RecomRecommended mended OPCD Nom Max OCPD Input Output Nom Max 600 208 32 40 50 28 34 50 600 600 32 40 50 28 34 50 600 208 42 53 60 37 46 60 600 600 42 53 60 37 46 60 600 208 53 66 70 46 57 70 600 600 53 66 70 46 57 70 600 208 67 84 100 59 74 100 600 600 67 84 100 59 74 100 600 208 83 103 125 73 91 125 600 600 83 103 125 73 91 125 600 208 103 128 175 90 113 150 600 600 103 128 175 90 113 150 600 208 133 167 200 118 147 200 600 600 133 167 200 118 147 200 — 1,3,4,5,7,8, 9,11,12, 13 AC Voltage Site Planning Data AC Output Current Recommended Battery OCPD KW Nom 83 125 26 29 50 26 111 150 34 38 50 34 139 175 43 48 60 43 180 225 55 63 80 55 222 300 68 77 100 68 278 350 85 96 125 85 361 450 111 125 175 111 2,3,5,7,8,9,11,12 Max. Max. Heat Battery Dissipation Disch. BTU/hr (Amps) Full Load 66A 8,500 66A 8,500 88A 11,000 88A 11,000 109A 14,000 109A 14,000 141A 18,000 141A 18,000 174A 22,000 174A 22,000 218A 26,000 218A 26,000 283A 33,000 283A 33,000 6,8,9,11,12 600VAC Input Dimensions WxDxH (Inches) 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 14 ConcenApprox. trated Unpacked Floor Cooling Weight Loading Air (Pounds) (Lb/SqFt) (CFM) 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,100 307 720 1,900 307 720 2,200 304 960 2,100 304 960 1,900 304 960 2,700 304 960 2,500 342 1440 2,300 342 1440 2,700 342 1440 2,500 342 1440 14 — — DISCONTINUED PRODUCT 87 kVA 30 30 30 30 40 40 40 40 50 50 50 50 65 65 65 65 80 80 80 80 100 100 100 100 130 130 130 130 Notes: kW 24 24 24 24 32 32 32 32 40 40 40 40 52 52 52 52 64 64 64 64 80 80 80 80 104 104 104 104 UPS Rating Standard AC Input AC Input with Filter without Filter Option RecomRecommended mended OPCD OCPD Input Output Nom Max Nom Max 220 208 87 108 150 75 94 125 220 220 87 108 150 75 94 125 240 208 79 99 125 69 86 125 240 240 79 99 125 69 86 125 220 208 115 144 175 100 125 150 220 220 115 144 175 100 125 150 240 208 106 132 175 92 115 150 240 240 106 132 175 92 115 150 220 208 144 180 225 125 157 200 220 220 144 180 225 125 157 200 240 208 132 165 200 115 144 175 240 240 132 165 200 115 144 175 220 208 183 229 300 161 202 250 220 220 183 229 300 161 202 250 240 208 168 210 250 148 185 225 240 240 168 210 250 148 185 225 220 208 225 281 350 198 248 300 220 220 225 281 350 198 248 300 240 208 206 258 350 182 227 300 240 240 206 258 350 182 227 300 220 208 280 350 450 247 308 400 220 220 280 350 450 247 308 400 240 208 256 321 400 226 283 350 240 240 256 321 400 226 283 350 220 208 364 455 600 321 401 500 220 220 364 455 600 321 401 500 240 208 333 417 500 294 368 450 240 240 333 417 500 294 368 450 — 1,3,4,5,7,8, 9,11,12, 13 AC Voltage Site Planning Data Rec. Battery KW Nom OCPD 125 26 83 79 100 26 83 125 26 100 26 72 111 150 34 105 150 34 111 150 34 96 125 34 139 175 43 131 175 43 139 175 43 120 150 43 180 225 55 171 225 55 180 225 55 156 200 55 222 300 68 210 300 68 222 300 68 192 250 68 278 350 85 262 350 85 278 350 85 241 300 85 361 450 111 341 450 111 361 450 111 313 400 111 2,3,5,7,8,9,11,12 AC Output Current Max. Max. Heat Battery Dissipation Disch. BTU/hr (Amps) Full Load 66A 8,500 66A 8,500 66A 8,500 66A 8,500 88A 11,000 88A 11,000 88A 11,000 88A 11,000 109A 14,000 109A 14,000 109A 14,000 109A 14,000 141A 18,000 141A 18,000 141A 18,000 141A 18,000 174A 22,000 174A 22,000 174A 22,000 174A 22,000 218A 26,000 218A 26,000 218A 26,000 218A 26,000 283A 22,000 283A 22,000 283A 22,000 283A 22,000 6,8,9,11,12 220 OR 240 VAC INPUT Dimensions WxDxH (Inches) 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 31.7x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 39.4x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 49.2x32.5x71 14 ConcenApprox. trated Unpacked Floor Cooling Weight Loading Air (Pounds) (Lb/SqFt) (CFM) 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 720 2,200 307 960 2,200 307 960 2,700 304 960 2,700 304 960 2,700 304 960 2,700 304 960 2,700 304 960 2,700 304 960 2,700 304 960 2,700 304 960 3,800 342 1440 3,800 342 1440 3,800 342 1440 3,800 342 1440 3,800 342 1440 3,800 342 1440 3,800 342 1440 3,800 342 1440 14 — — 88 DISCONTINUED PRODUCT DISCONTINUED PRODUCT POWER PROTECTION ™ The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: • • • • • Environmental systems—close-control air conditioning from 1 to 60 tons Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single, flexible package Monitoring and control—from systems of any size or location, on-site or remote Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2003 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-24532 Revision 4 (July 03) DISCONTINUED PRODUCT INSTALLATION MANUAL Technical Support/Service Web Site www.liebert.com Monitoring 800-222-5877 [email protected] Outside the US: 614-841-6755 Single-Phase UPS 800-222-5877 [email protected] Outside the US: 614-841-6755 Three-Phase UPS 800-543-2378 [email protected] Environmental Systems 800-543-2778 Outside the United States 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax: +39 049 5841 257 Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong +852 2 572 2201 Fax: +852 2 831 0114