Liebert Npower, 30-130, 208 or 600VAC, 60Hz; Site Planning Data; (R11/04) (SL-24546)

Liebert has reinvented the
double-conversion
UPS. The Npower is
the result of an
international design
collaboration and
more than a decade
of advanced
research.
Every aspect of the
Npower shows
careful design and
attention to detail. The rugged
powertrain and advanced
ActiveStar™ controls were
subjected to computer simulations
and thermal analysis to ensure
reliable performance in every
environment.
Even the physical packaging is
uniquely efficient, to make fully
configured systems more compact
than other products on the market.
Best of all, it’s a Liebert product—
designed to give the same millionhour critical bus MTBF as its older
brothers.
• Unmatched heritage of
reliability and availability
• Smallest system footprint
• Excellent efficiency with nonlinear loads and partial loads
• Outstanding dynamic response
• All-digital ActiveStar™ controls
and graphical user interface
LIEBERT NPOWER™ 3-PHASE UPS: 30-130KVA, 60 HZ, 600VAC
General Specifications
Npower Matching Battery Cabinet
Run Time (minutes) for kVA:
INPUT
Voltage
Voltage Range
Frequency Range
Current Distortion
Current Limit
Current Walk-in
Power Factor
Surge Protection
ENVIRONMENTAL
Operating
Temperature
Non-Operating Temp.
Relative Humidity
Operating Altitude
Acoustical Noise
600VAC, 60 Hz
3-phase, 3- or 4-wire plus ground
+10, -15%
(no battery discharge at -20%)
60 Hz, ±5
10% maximum reflected THD at full load with
optional input filter; 30% THD without filter
115% of full load input current
20 seconds to full load
0.80 lagging minimum at full load; up to 0.96
lagging at full load with optional input filter
Sustains input surges without damage, per
criteria listed in ANSI C62.41-1980 (IEEE 587)
UPS: 32° to 104°F (0-40°C)
Battery: 68° to 86°F (20-30°C)
-4° to 158°F (-20° to 70°C)
0-95% non-condensing
Up to 6,600 ft. (2000m) without derating
Less than 65 dBA typical, measured
3.3 ft. (1m) from the unit
OUTPUT
Voltage
208 or 600VAC
3-phase, 4-wire plus ground
Voltage Adjustment
Range
±5%
±0.5% for balanced load
±1.0% for 100% unbalanced load
±5% deviation for 100% load step
Dynamic Regulation ±1% for loss or return of AC input
Transient Response Recover to ±1% of steady state within 1 cycle
Time
For linear loads, 1% THD; less than 2.5% THD
Voltage Distortion
for 100% nonlinear loads w/o kVA/kW derating
120° ±0.5° for balanced load.
Phasing Balance
120° ±1° for 100% unbalanced load
Frequency
±0.1%
Regulation
Load Power
1.0 to 0.7 lagging without derating
Factor Range
125% of full load for 10 minutes
Overload
150% for 1 minute w/ true sinusoidal waveform
STANDARDS
ETL Listed to UL 1778 and UL 924 UPS standards, and CSA certified.
Meets current requirements for safe high performance UPS operation.
Voltage Regulation
Model
1FJ
1HJ
1LJ
1MJ
1PJ
1PJ(130)
1RJ
1UJ
1WJ
2PJ
Dimensions
30 40 50 65 80 100 130 WxDxH, in. (mm)
12
21
28
36
53
62
72
104
7
14
20
25
38
45
52
74
10
14
18
28
34
39
55
7
8
12
20
25
30
40
5
5
8
15
19
23
33
5
10 7
13 9
17 12
25 16
126 83 67 50 38 28
25x32.5x71
(635x825x1800)
49x32.5x71
(1250x825x1800)
204 145 108 78 63 48
3PJ(130) 3RJ
223 161 129 94 72 54
3UJ
265 187 142 105 81 65
3WJ
421 302 217 157 124 94
4PJ
301 206 154 111 90 68
4PJ(130) 4RJ
329 224 182 134 102 77
4UJ
377 266 201 147 111 91
4WJ
480 423 320 222 180 135
lb. (kg)
1,600 (725)
1,800 (815)
2,350 (1,065)
2,350 (1,065)
3,000 (1,360)
3,350 (1,520)
3,700 (1,680)
4,000 (1,815)
5,050 (2,290)
(2) 25x32.5x71
635x825x1800)
6,000 (2,720)
(2) 49x32.5x71
(1250x825x1800)
6,700 (3,040)
7,400 (3,360)
8,000 (3,630)
10,100 (4,580)
(3) 25x32.5x71
635x825x1800)
9,000 (4,080)
35
39
48
69
(3) 49x32.5x71
(1250x825x1800)
10,050 (4,560)
11,100 (5,040)
12,000 (5,445)
15,150 (6,870)
-
(4) 25x32.5x71
(635x825x1800)
12,000 (5,440)
50
55
67
97
(4) 49x32.5x71
1250x825x1800
13,400 (6,080)
14,800 (6,720)
16,000 (7,260)
20,200 (9,160)
-
2PJ(130) - 20
2RJ
144 104 76 55 45 35 25
2UJ
156 111 90 67 52 40 30
2WJ
- 97 74 55 40
3PJ
Weight
-
Maintenance Bypass Cabinets
Dimensions
Model
L or N
P or Q
WxDxH, in. (mm)
25x32.5x71
(635x825x1800)
31.7x32.5x71
(805x825x1800)
Weight, lb. (kg) for kVA:
30-50
65-80
100-130
660 (299)
750 (340)
800 (363)
1,210 (549)
1,320 (599)
1,540 (699)
Slim-Line Distribution Cabinet
Dimensions
Weight
kVA
WxDxH, in. (mm)
lb. (kg)
All
10x32.5x71
(254x825x1800)
250 (113)
Site Planning Data, Liebert Npower: 30-130kVA, 60 Hz, 600VAC
UPS
Rating
kVA
kW
Standard AC Input
Voltage
Input
Output
30
24
600
208
30
24
600
600
40
32
600
208
40
32
600
600
50
40
600
208
50
40
600
600
65
52
600
208
65
52
600
600
80
64
600
208
80
64
600
600
100
80
600
208
100
80
600
600
130 104
600
208
130 104
600
600
See Notes for Table (below):
Current (A)
Nom.
Max.
32
40
32
40
42
53
42
53
53
66
53
66
67
84
67
84
83
103
83
103
103
128
103
128
133
167
133
167
1 2,3,8,12
AC Input w/Filter Opt.
Current (A)
Rec.
OCPD Nom.
50
50
70
70
80
80
100
100
125
125
175
175
200
200
6
28
28
37
37
46
46
59
59
73
73
90
90
118
118
1
Max.
34
34
46
46
57
57
74
74
91
91
113
113
147
147
2,3,8,12
Battery
Rec. Nom. Battery
Max.
OCPD VDC
kW
Discharge
50
50
60
60
70
70
100
100
125
125
150
150
200
200
6
480
480
480
480
480
480
480
480
480
480
480
480
480
480
4
26
26
34
34
43
43
55
55
68
68
85
85
111
111
—
Notes for Table
1.
2.
3.
4.
5.
6.
7.
8.
9.
AC Output
Nominal (Nom) current is based on full rated output load.
Maximum (Max) current (125% of nominal) is short duration for battery recharge
conditions.
UPS input and bypass cables must be run in separate conduit from output cables.
Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
Power cables from UPS DC link to batteries should be sized for a total maximum 2.0V
line drop (measured at the UPS) at maximum discharge current.
OCPD=Overcurrent Protection Device. Recommended AC input and AC output
overcurrent protection represents 125% of nominal full load current (continuous) per
NEC 215.
Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground
conductors are recommended. Neutral conductors to be sized for full capacity per
NEC 310-15(b)(4). References are per NEC 1999.
Wiring requirements:
AC Input and Output: 3-phase, 3- or-4-wire plus ground, depending on UPS
configuration. See Installation Manual and submittal drawings for specific
instructions.
DC Input: 2-wire (positive and negative), plus ground.
All wiring is to be in accordance with national and local electrical codes.
Mechanical Data
Current
Nom.
66A
83
66A
29
88A
111
88A
38
109A
139
109A
48
141A
180
141A
63
174A
222
174A
77
218A
278
218A
96
283A
361
283A
125
1,3,5,8,12 1,3,8,12
Dimensions
Weight Floor Loading
Heat Dis.
Cooling Air
OCPD WxDxH, in. (mm) lb. (kg) lb./ft.2(kg/m2) BTU/h (kWH) CFM (m3/h)
125
50
150
50
175
60
225
80
300
100
350
125
450
175
6
2,050
(930)
31.7x32.5x71
(805x825x1800)
39.4x32.5x71
(1001x825x1800)
2,400
(1089)
49.2x32.5x71
(1250x825x1800)
3,150
(1429)
13
13, 14
8,500 (2.5)
720 (1223)
301 (1470)
11,000 (3.2)
720 (1223)
301 (1470)
14,000 (4.1)
720 (1223)
270 (1318)
18,000 (5.3)
960 (1631)
270 (1318)
22,000 (6.4)
960 (1631)
284 (1387)
26,000 (7.6)
1440 (2447)
284 (1387)
33,000 (9.7)
1440 (2447)
—
—
—
10. Minimum access clearance is 3 ft. (0.9m) front and 1 ft. (0.3m) above UPS.
11. Top or bottom cable entry through removable access plates. Punch plate to suit
conduit size, then replace.
12. Control wiring and power wiring must be run in separate conduit.
13. Weights and dimensions shown do not include battery cabinet, Slim-Line distribution
cabinet or other options.
14. Add 560 lb. (254kg) for 100-130kVA unit with dual input and isolated 208VAC output.
15. Backup emergency generator must be properly sized and equipped with an
isochronous governor (generator frequency regulation) and a UPS-compatible voltage
regulator.
16. An on-site automatic transfer switch should be equipped with auxiliary contacts for
UPS “on generator” current limit. Refer to Liebert publication 91K-PLT-48-02.
17. An external isolated maintenance bypass circuit might cause utility AC input to be
out of phase with the UPS AC output.
© 2004 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names
referred to are trademarks or registered trademarks of their respective owners.
SL-24546 (11/04) Rev. 4
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
2,150
(975)
287 (1401)
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com