100W 2 & 3 Output with battery Charger function QE-100 series Features: Universal AC input / Full range Auto switch when power off (UPS function) Built-in constant current limit circuit Alarm signal for AC OK and Battery low (TTL open collector output or relay contact output) Protection: SCP, OLP, OVP Brown-out (Low AC Input Voltage) Battery low protection Battery polarity protection (by Resettable Fuses) Withstand 2G vibration test 3 years warranty QE-100-G MODEL Output Input Output Number DC Voltage Range Rated Current Max. Output Current Rated Power Ripple & Noise (Max.) Voltage Adj. Range Voltage Tolerance Line Regulation Load Regulation Setup, Rise Time Hold up Time (Typ.) Voltage Range Frequency Range Efficiency (Typ.) at 230VAC AC Current (Typ.) Inrush Current (Typ.) Leakage Current QE-100-GB QE-100-L QE-100-LB CH1 CH2 CH1 CH2 CH3 CH1 CH2 CH1 CH2 CH3 13.8V 13.8V 13.8V 13.8V 5V 27.6V 27.6V 27.6V 27.6V 5V 4.8A 2.5A 3.7A 2.5A 3A 2.15A 1.5A 1.6A 1.5A 3A 2.875A 6.2A 2.875A 3A 3.65A 1.725A 3.1A 1.725A 3A Note.8 7.3A 100.74W 100.56W 100.74W 100.56W Note.2 100mVp-p 150mVp-p 100mVp-p 150mVp-p 100mVp-p 100mVp-p 150mVp-p 100mVp-p 150mVp-p 100mVp-p CH1: ±10% CH1: ±10% Note.3 ±2% — ±2% — ±3% ±2% — ±2% — ±3% Note.4 ±0.5% — ±0.5% — ±0.5% ±0.5% — ±0.5% — ±0.5% Note.5 ±0.5% — ±0.5% — ±1.5% ±0.5% — ±0.5% — ±1.5% 800ms, 30ms / 230VAC, 800ms, 30ms / 115VAC at full load 50ms / 230VAC, 8ms / 115VAC at full load 90 ~ 264VAC, 127 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage) 47 ~ 63Hz 86% 85% 87% 85% 2A / 115VAC, 1.2A / 230VAC Cold Start 35A / 115VAC, 70A / 230VAC For earth < 1mA / 264VAC Above 110% rated output power CH1 / CH3 (GB / LB only) Over Load Protection Over Voltage Function Battery cut off AC OK Battery Low Working Temp. Working Humidity Environment Storage Temp. & Humidity Temp. Coefficient Vibration Safety Standards Withstand Voltage Isolation Resistance Safety & EMC EMI Conduction & Radiation Harmonic Current EMS Immunity MTBF Dimension (WxHxD) Others Packing Note Above 100% rated output current for CH2 Protection type: Hiccup mode, recovers automatically after fault condition is remove CH1: 115 ~ 150% rated output voltage Protection type: latch-off mode 10V ±5% 20V ±5% TTL open collector output Relay contact output TTL open collector output Relay contact output Battery low voltage < 12V ±3% Battery low voltage < 22V ±3% -20 ~ +70°C (Refer to output load de-rating curve) 20 ~ 90% RH non-condensing -40 ~ +85°C, 20 ~ 90% RH ±0.03% / °C (0 ~ 50°C) on CH1 10 ~ 500Hz, 2G 10min. / 1cycle, period for 60min. each along X, Y, Z axes Certified UL 60950-1; EN 60950-1 I/P-O/P: 3KVAC, I/P-FG: 1.5KVAC, O/P-FG: 0.5KVAC I/P-O/P: 100M Ohms / 500VDC Certified EN 55022; EN 61000-6-3 Certified EN 61000-3-2; EN 61000-3-3 Certified IEC 61000-4-2, 3, 4, 5, 6, 8, 11; ENV 50204; EN 55024; EN 61204-3; EN 61000-6-1 103.4K HRS Certified MIL-HDBK-217F 92.1K HRS Certified MIL-HDBK-217F 97.5x37.5x129.5 mm / 3.839x1.476x5.098 inch 0.46kg; 21pcs / 10.66kg / 0.64CUFT 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uF & 47uF parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. Line regulation is measured from low line to high line at rated load. 5. Load regulation is measured from 10% to 100% rated load. 6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 7. Length of set up time is measured first cold start. Turning ON/OFF the power supply continuously may increase the set up time. 8. The total power output must not exceed the rated power. 9. CH2: Battery discharge current must not exceed 50% of the rated power. 10. Do not connect the GND port with B- port in your application to prevent product damage. REV. B2 12/11/21 1 100W 2 & 3 Output with battery Charger function QE-100 series Mechanical Specification: Unit:mm QE-100-G/L Alarm output Connector (CN2): JST B3B-XH or equivalent Terminal Pin No. Assignment (CN1) Assignment Pin No. Assignment Pin No. 1 AC/L 5 DC output VO+ 2 AC/N 6 BAT+ 3 FG 7 BAT- 8 DC/DC Output +5V (GB/LB only) DC Output GND 4 Assignment Pin No. 1 2 BAT LOW G (13.8V/20mA) L (27.6V/20mA) 3 Mating Housing Terminal JST XHP-3 or equivalent JST SXH-001 T-P0.6 or equivalent AC OK QE-100-GB/LB Alarm output Connector (CN2): JST B4B-XH or equivalent Assignment Pin No. 1 2 Mating Housing Terminal JST XHP-4 or equivalent JST SXH-001 T-P0.6 or equivalent AC OK 3 4 Bat. Low De-rating Curve: Load V.S Temp. Load V.S I/P Voltage QE-100-G/L 80 QE-100-GB/LB 60 40 20 -20 100 LOAD (%) LOAD (%) 100 Ta=25°C 80 60 40 20 0 10 20 30 40 50 60 AMBIENT TEMPERATURE (°C) 70 (HORIZONTAL) 90 95 100 105 110 115 120 264 INPUT VOLTAGE (VAC) 60Hz REV. B2 12/11/21 2 QE-100 series 100W 2 & 3 Output with battery Charger function For QE-100-G/L: Block Diagram AC OK ALARM CIRCUIT I/P EMI FILTER RECTIFIER & FILTER Bat. Low VO+ RECTIFIERS & FILTER POWER SWITCHING GND BAT+ FG DETECTION CIRCUIT BAT- PWM CONTROL O.L.P. Battery Charger & Back up Control O.V.P. Alarm Signal for AC OK and Battery Low (1)Alarm Signal is sent out through "AC OK" & "Battery Low" pins. (2)An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA. (3)Table 3.1 explain the alarm function built-in the power supply. Function Description Output of alarm The signal is "Low" when the power supply turns on Low (0.3V max. at 30mA) The signal turns to be "High" when the power supply turns OFF High or open (External applied voltage 50V max.) The signal is "Low" when the voltage of battery is under G:12V, L:22V Low (0.3V max. at 30mA) The signal is "High" when the voltage of battery is above G:12V, L: 22V High or open (External applied voltage 50V max.) AC OK Battery Low Table 3.1 Explanation of Alarm Signal AC OK (Battery low) V+ CN2 Pin3 G: 13.8V/20mA L: 27.6V/20mA CN2 Pin1(Pin2) CN2 Pin3 R V or CN1 Pin4 DC output GND Internal circuit of AC OK (Battery Low) CN2 Pin1(Pin2) External voltage and R (The max. Sink is 30mA and 50V) REV. B2 12/11/21 3 100W 2 & 3 Output with battery Charger function QE-100 series For QE-100-GB/LB: Block Diagram AC OK ALARM CIRCUIT Bat. Low DC/DC Power Supple I/P EMI FILTER RECTIFIER & FILTER +5V VO+ RECTIFIERS & FILTER POWER SWITCHING GND BAT+ FG DETECTION CIRCUIT O.L.P. PWM CONTROL O.V.P. BAT- Battery Charger & Back up Control Alarm Signal for AC OK and Battery Low (1)Alarm Signal is sent out through "AC OK" & "Battery Low" pins. (relay contact type) (2)An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. (3)Table 4.1 explain the alarm function built-in the power supply. AC OK (Battery low) Function Description Output of alarm The signal is “Low” when the power supply turns on Low or short The signal turns to be “High” when the power supply turns OFF High or open (External applied voltage 30V max.) The signal is “Low” when the voltage of battery is under GB:12V, LB:22V Low or short The signal is “High” when the voltage of battery is above GB:12V, LB:22V High or open (External applied voltage 30V max.) CN2 Pin1 (Pin3) AC OK Battery Low Table 4.1 Explanation ofAlarm Signal External voltage source (V) and resistor (R) (The max. Sinkis 1A and 30V) Internal circuit of AC OK (Battery Low) CN2 Pin2 (Pin4) REV. B2 12/11/21 4