MEANWELL PSC-60

60W Single Output with Battery Charger(UPS Function)
PSC-60
series
Features :
Universal AC input / Full range
Optional L-Bracket and cover (PSC-60x-C, x=A,B)
Protections: Short circuit / Overload / Over voltage
Battery low protection / Battery polarity protection by fuse
Alarm signal for AC OK and Battery low
Cooling by free air convection
100% full load burn-in test
2 years warranty
SPECIFICATION
OUTPUT
OUTPUT NUMBER
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
13.8V
27.6V
27.6V
RATED CURRENT
2.8A
1.5A
1.4A
0.75A
CURRENT RANGE
0 ~ 4.3A
--------
0 ~ 2.15A
--------
RATED POWER
59.34W
RIPPLE & NOISE (max.) Note.2 120mVp-p
CH1: 12 ~ 15V
VOLTAGE TOLERANCE Note.3 1.0%
---------------
LOAD REGULATION
0.5%
--------
0.5%
--------
Note.5 800ms, 50ms/230VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC
90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
1600ms, 50ms/115VAC at full load
10ms/115VAC at full load
127 ~ 370VDC
84%
EFFICIENCY (Typ.)
84%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.6A/115VAC
1A/230VAC
COLD START 30A/115VAC
60A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
BATTERY CUT OFF
Protection type : Hiccup mode, recovers automatically after fault condition is removed
21 1V
10.5 0.5V
AC OK
TTL open collector output, ON : AC OK ; OFF : AC Fail ; Ice : max. 30mA@ 50VDC
BATTERY LOW
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
NOTE
--------
0.5%
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
OTHERS
--------
CH1: 24 ~ 29V
1.0%
--------
WORKING TEMP.
(Note 4)
240mVp-p
0.5%
OVER VOLTAGE
EMC
--------
LINE REGULATION
PROTECTION
FUNCTION
59.34W
VOLTAGE ADJ. RANGE
SETUP, RISE TIME
INPUT
PSC-60B
PSC-60A
MODEL
TTL open collector output, ON : Battery Low ; OFF : Battery OK ; Ice : max. 30mA@ 50VDC
Battery low voltage : < 11V
-20 ~ +70 (Refer to "Derating Curve")
Battery low voltage : < 22V
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0~50 ) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
DIMENSION
PACKING
589.7K hrs min. MIL-HDBK-217F (25 )
PCB:101.6*50.8*29mm (L*W*H) ; with optional CASE:103.4*62*37mm (L*W*H)
PCB:0.13Kg; 96pcs/13.5Kg/0.89CUFT ; with optional CASE:0.29Kg; 45pcs/14Kg/0.67CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Heat sink HS1,HS2 can not be shorted.
7. Heat sink HS1 must have safety isolation distance with system case.
File Name:PSC-60-SPEC 2011-08-18
PSC-60
60W Single Output with Battery Charger(UPS Function)
Mechanical Specification
series
Unit:mm
101.6
3.175
95.25
Optional cover:
No.998A -T
3.175
HS2
50.8
44.45
FS1
3
2
1
AC FUSE
T2.5A/250V
SVR1
1
2
3
4
5
6
CN1
CN2
HS1
3 max.
29
4- 3.3
Mylar film
1.HS1,HS2 can not be shorted.
2.HS1 must have safety isolation distance with system case.
Assignment
AC/N
No Pin
AC/L
Mating Housing
Terminal
JST VHR
or equivalent
JST SVH-21T-P1.1
or equivalent
4.2
Optional L-Bracket:
No.998A -D
12.
DC Output Connector (CN2) : JST B6P-VH or equivalent
Pin No.
1
2
3
Assignment
Bat. Low
AC OK
Battery -
Pin No. Assignment
Battery +
4
DC Output +
5
6
DC Output COM
7
Mating Housing
Terminal
JST VHR
or equivalent
JST SVH-21T-P1.1
or equivalent
2-M
2-M
95
3L
=4
3
78
2-
2-M
10
3.4
3L
3.5
37
Pin No.
1
2
3
18
14.5
AC Input Connector (CN1) : JST B3P-VH or equivalent
=4
55
24
30.8
.2
5
62
Block Diagram
AC OK
Bat. Low
ALARM
CIRCUIT
I/P
EMI
FILTER
RECTIFIERS
&
FILTER
POWER
SWITCHING
RECTIFIERS
&
FILTER
DETECTION
CIRCUIT
FG
O.L.P.
CONTROL
O.V.P.
+V
-V
Bat. +
Bat. Battery Charger
&
Back Up Control
File Name:PSC-60-SPEC 2011-08-18
PSC-60
60W Single Output with Battery Charger(UPS Function)
series
Output Derating VS Input Voltage
Output Derating
100
100
PCB only
90
80
For PCB with
L-Bracket+cover option
80
70
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30 35 40
50
60
60
50
40
70 (HORIZONTAL)
90
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
AMBIENT TEMPERATURE ( )
Suggested Application
1.Back up connection for AC interruption
(1) Please refer to the Fig1.1 for suggested connection.
The power supply charge the battery and provide energy to the load in the same time when the AC main is OK.
The battery start to supply power to the load when the AC main fails.
+
A : 12V
B : 24V
Battery
BatBat+
DC+
DC-
+
-
Load
Fig 1.1 Suggested system connection
2.Alarm Signal for AC OK and Battery Low
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins.
(2) An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA.
(3) Table2.1 explain the alarm function built-in the power supply
Function
AC OK
Battery
Low
Output of alarm
Description
The signal is "Low" when the power supply
turns on
Low
(0.3V max. at 30mA)
The signal turns to be "High" when the power
supply turns OFF
High or open(External applied
voltage 50V max.)
The signal is "Low" when the voltage of
battery is under A:11V, B:22V
Low
(0.3V max. at 30mA)
The signal is "High" when the voltage of
battery is above A:11V, B:22V
High or open(External applied
voltage 50V max.)
Table 2.1 Explanation of Alarm Signal
AC OK (Battery low)
R
V
Pin6 DC output com
External voltage and R
(The max. Sink is 30mA and 50V)
Fig 2.2 Internal circuit of AC OK (Battery Low)
File Name:PSC-60-SPEC 2011-08-18