DRA-CN Assemblies DIN Rail mountable assemblies of Solid State Relays and Sockets The DRA-CN assemblies provide a convenient and easy way to select and use Crydom CN series Solid State Relays on a standard 35mm DIN rail. For additional information visit www.crydom.com. DERATING CURVES DRA-CN024Dxx FEATURES Factory assembled ready to use assemblies for AC and DC input 24VDC @ 3.5A, 48VDC @ 100mA and 240VAC @ 2A Operating Voltage Rating 6.2mm wide socket LED input status indicator Socket clip fits all standard 35mm DIN rails INSTALLATION INSTRUCTIONS Load Current (Amperes) 40 35 30 ;4 AB9; :< :; 89 Please read all installation instructions before using the assemblies. 00 Mount the assembly on the DIN rail Wire the socket to the control side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) Wire the socket to the load side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) If multiple units are installed be sure to follow derating curves for assemblies 0 10 ;0 30 40 50 90 50 90 50 90 Ambient Temperature (°C) DRA-CN048Dxx (B) PART NUMBER NOMENCLATURE (A) Assembly Input Voltage 05: 05 VDC 24: 24 VDC 120: 120 V AC/DC 240: 240 V AC/DC Series DRA-CN 024D 24 Load Current (Amperes) 01; R 010 00< 009 004 00; 000 0 10 ;0 30 40 Ambient Temperature (°C) Switching Mode Blank: Zero Cross Turn-On (AC Output Only) R: Random Turn-On WIRING DIAGRAM For DRA-CN assembly wiring diagram see DRSCN wiring diagram shown in installation sheet (reverse side of this sheet). DRA-CN240Axx ;3 Load Current (Amperes) Load Voltage 024D: 24 VDC, 3.5 A 048D: 48 VDC, 0.1 A 240A: 240 VAC, 2 A ;0 1C :D AB9; :8 8C 03 00 0 10 ;0 30 40 Ambient Temperature (°C) (A) Assembly part number is marked on the opposite side of the socket from the socket's labeling. (B) For 100 mA output SSRs, no airgap is required for full output current rating. Rev: 021910 WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告 RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE ! "#$ # %$ &$ #' RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG &($)*+,(- *#*. #(#. /(0$ %.(*%.*%*+- * Failure to follow these instructions can result in serious injury, or equipment damage. Le non-respect de cette directive peut entraîner, des lésions corporelles graves ou des dommages matériels. Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben. RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD 4 5 '" ' 5 6 Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales. RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO 1 2 ( 3 La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature. RELAY/SOCKET COMPATIBILITY (A, B) DRSCN Series SSR PN DIN rail mountable sockets The DRSCN sockets provide a convenient and easy way to install Crydom CN series Solid State Relays on a standard 35mm DIN rail. For additional information visit www.crydom.com. FEATURES Sockets are fully compatible with CN series SSRs 6.2mm wide socket LED input status indicator Socket clip fits all standard 35mm DIN rails INSTALLATION INSTRUCTIONS Please read all installation instructions before using the sockets and relays. Match CN series SSR to appropriate DRSCN socket part number to create an Assembly Insert the CN SSR on the socket Mount the socket on the DIN rail Wire the socket to the control side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) Wire the socket to the load side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) If multiple units are installed be sure to follow derating curves for assemblies DR Socket PN CN024D05 CN048D05 CN240A05 DRSCN05 CN024D24 CN048D24 CN240A24 DRSCN24 CN024D60 CN048D60 CN240A60 DRSCN120 CN024D60 CN048D60 CN240A60 DRSCN240 (A) Installing a CN series solid state relay in a socket that does not have matching input/output specifications may result in damage to either the relay, socket, or both, and/or in non-operation. (B) Maximum output rating for DRSCN Series sockets is 250V / 6 Amps regardless of chosen SSR. WIRING DIAGRAM (C, D, E, F) PART NUMBER NOMENCLATURE Series DRSCN 120 R Socket Input Voltage 05: 05 VDC 24: 24 VDC 120: 120 V AC/DC 240: 240 V AC/DC NC Socket Part Number DRSCN24 Maximum Socket Rating: Input: UN = 24VDC Output: max. 250V/6A A1+ Control 14 Load Plug in Relay Options: Solid State Relay: CN024D24 CN048D24 CN240A24 SSR Ratings should not exceed socket rating A2- A1+ 13+ 14 (13+)11 A2- MECHANICAL DIMENSIONS DC Output A2- A1+ 3.15 in [80.0 mm] 0.24 in [6.1 mm] 11 14 AC Output A2- A1+ 11 14 CN240A24 A1+ 11 R 14 A2- 24 VDC R (C) For sockets intended for AC input control voltage, the AC line can be wired to either DRS socket Socket Part Number DRSCN24 Maximum Socket Rating: Input: UN = 24VDC Output: max. 250V/6A A1+ terminal A1+ or terminal A2-. Proper polarity must be observed for DC input control voltage sockets being terminal A1+ positive with respect to terminal A2-. 14 Plug in Relay Options: Solid State Relay: CN024D24 CN048D24 CN240A24 3.64 in [92.6 mm] (D) For AC loads, the AC line can be wired to either DRS socket terminal 11 or terminal 14. The AC load may also be wired on either the line or neutral side of the SSR. For DC loads, the proper polarity must be observed for the power supply, load and DRS socket with terminal 13 being positive with respect to terminal 14. SSR Ratings should not exceed socket rating A2- A1+ 13+ 14 (13+)11 A2DC Output A2- A1+ 2A/240VAC NC 11 14 AC Output (E) DC inductive loads must be diode suppressed. (F) All terminals feature screw M3 Slotted Drive. Rev: 021910 DANGER / DANGER / GEFARH / PELIGRO / PERICOLO / STROMSCHLAG-, EXPLOSIONS- ODER LICHTBOGENGEFAHR HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH RISQUE D'ELECTROCUTION, D'EXPLOSION OU D'ARC ELECTRIQUE Turn off power supply before working on this equipment. Coupez l'alimentation avant de travailler sur cet appareil. Vor dem Arbeiten an dem Gerät dessen Stromversorgung abschalten. Failure to follow these instructions will result in death or serious injury. Le non-respect de ces instructions provoquera la mort ou des blessures graves. Die Nichtbeachtung dieser Anweisungen führt zu Tod oder schwerer Körperverletzung. RIESGO DE ELECTROCUCIÓN, EXPLOSIÓN O ARCO ELÉCTRICO RISCHIO DI SCOSSA ELETTRICA, DI ESPLOSIONE O DI OFTALMIA DA FLASH ٪ሞۉऍĂԖቊईࢷۉຮླ၃ Desconecte toda alimentación antes de realizar el servicio. Si no se siguen estas instrucciones provocará lesiones graves o incluso la muerte. Scollegare l'apparecchio dalla presa di corrente prima di qualsiasi intervento. Il mancato rispetto di queste istruzioni provocherà morte o gravi infortuni. ሞ֡ፕُยԢኮമ൩ံ࠲Կۉᇸă ැփፏኄၵຫLjీࣷڞዂჹዘڦටวฅ࡞ฯຶྨă