Door Mounting type HEX080PB series Dimension drawing Internal External Benefit for customer Main feature Unit Specification Dimension (H x W x D) mm 850 x 500 x 160 * Optional communication function design Cooling capacity*Note W/K 60 * Easy installation and maintenance from Rated voltage Vdc 48 (TYP.) Operating voltage range Vdc 40 ~ 60 Rated current A 1.8 max. Power consumption W 87 max. Operating temperature range °C -10 ~ +65 Internal airflow CFM 180 230 External airflow CFM 140 170 1.5M sound pressure noise dB-A 65.0 68.0 Weight Kg * Low power consumption * "One touch" dry run test and dust cleaning internal side * Simply LED status indicator * High efficiency and reliable fan selection Competitive Design * Air to air circulation of heat exchange * Door mounted * Lightweight * Rated voltage at 48V 70 14.0 * Note : The cooling capacity (W/K OR W/°C) is defi ned as Q/ (TI-TA) * IP55 waterproof at external side Q : Heat dissipation (W) from inside of cabinet * Drainage hole in the bottom TI : Return temperature of internal air circuit (K OR °C) * Safety approval TA : Ambient temperature of external air circuit (K OR °C)