HEX080QA series Roof Mounting type

Roof Mounting type
HEX080QA series
Dimension drawing
Main feature
Unit
Specification
Dimension (H x W x D)
mm
555 x 500 x 265
Cooling capacity*Note
W/K
80
Rated voltage
Vdc
48 (TYP.)
Operating voltage range
Vdc
40 ~ 60
Rated current
A
2.0 max.
Power consumption
W
96 max.
Operating temperature range
°C
-10 ~ +65
◆ Air to air heat exchange
Internal airflow
CFM
270
◆ Door mounted
External airflow
CFM
200
1.5M sound pressure noise
dB-A
64.0
Weight
Kg
15.0
Features
◆ IP55 waterproof at external side
◆ "One touch" dry run test and dust cleaning
◆ Optional communication function design
◆ Clear LED status indicator
◆ High efficiency and reliable fan modules
Design
◆ Rated voltage at 48V
◆ Complete airtight design for outdoor
application
◆ Reduntant fan quantity design
* Note : The cooling capacity (W/K OR W/°C) is defi ned as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet
TI : Return temperature of internal air circuit (K OR °C)
TA : Ambient temperature of external air circuit (K OR °C)