Selective Coordination

Selective Coordination
Open
Fault
Figure 11
Figure 12
A non-selectively designed system of overcurrent protection
devices is shown in Figure 11. When a building power distribution system is designed without selectivity, potential safety
hazards and costly power outages may result. A system with
designed selectivity will assure that only the overcurrent protection device for a faulted circuit will open to limit a power
outage to the faulted circuit.
“I2t Melting Energy” is a reference to the value of “I2t Energy”
required to melt the link(s) of Fuse A. “I2t” is not an energy
value, but a convenient reference used for comparison purposes. Actual energy would be “I2Rt” where “R” is resistance.
The value of resistance is so low compared to the other two
values that it is ignored for convenience.
Selectivity
Refer to Figure 12 for an illustration of the use of
determine fuse selectivity for short-circuit conditions.
“I2t”
to
Energy from fault current flow builds up heat inside fuses,
breakers and conductors as the current flows to a fault loca-
“I2t Clearing Energy” is a reference to the amount of energy
that Fuse B allows to build up in the form of heat during Fuse
B “Total Clearing Time.”
Figure 12 shows an obvious conclusion that if the “I2t
Clearing Energy” of Fuse B is less than the “I2t Melting
Energy” of the link(s) of Fuse A then Fuse A will not open
when a fault on the load side of Fuse B occurs.
“Selectivity Ratio Guide” For Current Limiting Fuses*
Divide the amps rating of a load-side fuse into the amps rating of the line-side fuse. If the ratio is "Equal to or larger than"
the table ratio, then a fault on the load side of the load-side
Circuit
Current Rating
Type
Class
Line-Side Fuse
601 to Time6000A Delay
0
to
600A
Dual
Element
L
Edison
Symbol
LCL
Load-Side Fuse
A
0-600A
TimeDual-Element
Delay
Time-Delay
L
RK1
J**
LCL
LENRK
JDL
LESRK
2:1
2:1
2:1
fuse will cause the load-side fuse ONLY to open to provide
selectivity.
601-6000A
Fast-Acting
0-600A
Fast-Acting
0-1200A
0-600A
RK5
ECNR
ECSR
4:1
L
LCU
T
TJN
TJS
2:1
J
JFL
2:1
RK1
NCLR
SCLR
2:1
0-60A
TimeDelay
G
SEC
2:1
N/A
RK1
LENRK
LESRK
–
2:1
2:1
8:1
–
3:1
3:1
3:1
4:1
J
RK5
JDL**
ECNR
ECSR
LCU
–
–
2:1
1.5:1
2:1
1.5:1
8:1
2:1
–
–
3:1
1.5:1
3:1
1.5:1
3:1
1.5:1
4:1
1.5:1
2:1
N/A
3:1
4:1
3:1
4:1
3:1
4:1
2:1
2:1
601 to
L
2:1
2:1
2:1
6:1
2:1
2:1
2:1
6000A
0 to
Fast- RK1
NCLR
–
3:1
3:1
8:1
–
3:1
3:1
600A Acting
SCLR
0 to
T
TJN
–
3:1
3:1
8:1
–
3:1
3:1
1200A
TJS
0 to
J
JFL
–
2:1
2:1
8:1
–
3:1
3:1
600A
0 to
Time- G
SEC
–
3:1
3:1
4:1
–
2:1
2:1
60A
Delay
Note: At some values of fault current, specified ratios may be lowered to permit closer fuse sizing. Plot fuse curves or consult with Edison Fusegear.
**General Notes: Ratios given in this Table apply only to Edison fuses. When fuses are within the same case size, consult Edison Fusegear.
*Consult Edison Fusegear for latest data.