bullet™ class l time-delay fuses bullet™ class l fast

BULLET™ CLASS L TIME-DELAY FUSES
BULLET™ CLASS L FAST-ACTING FUSES
Catalog Number LCL (300 - 6000A) Time-Delay 600 Volts AC or Less
Catalog Number LCU (601 - 6000A) Fast-Acting 600 Volts AC or Less
300*
400*
500*
601
650
700
750
800
601
650
700
800
1000
1200
AMPERE RATINGS
LCL 600V
801
1350
900
1400
1000
1500
1200
1600
LCU 600V
1350
1800
1500
2000
1600
2500
1800
2000
2500
3000
3500
4000
5000
6000
3000
3500
4000
6000
—
—
* Not UL Listed (See note below).
LCL:Time-delay of 5 seconds minimum at 500% rated current allows
closer sizing.
LCU:Pure (over 99%) silver links insures maximum current limitation
capability.
NOTE: LCL 300 - 600 amp fuses are physically the same as 800
amp size; Use in 800 amp switch where load current is not
fully utilized and a smaller fuse amp size is desired. Also
useful in new installations to allow for future upgrades in
service.
BENEFITS:
• “O-ring” construction insures maximum current limiting
ability.
• Silver plated micro-peened terminals.
• High strength melamine fuse tubes.
APPLICATIONS:
• LCL: Recommended for AC power distribution system
mains and large feeders.
• LCU: Recommended for non-inductive heating and lighting loads. Also suitable for protection of low interrupting
rating circuit breakers.
14
LCL/LCU SPECIFICATIONS
LCL: Time-Delay
LCU: Fast-Acting
Voltage Rating:
LCL - 600VAC, LCU - 600VAC
Ampere Rating:
LCL: 300 - 6000 Amps
LCU: 601 - 6000 Amps
Interrupting Rating:
200,000 RMS Symmetrical Amps
Current Limiting:
Class L Fuse
Agency Approvals:
UL Listed, Class L, Guide JDDZ, File E162363
CSA Certified HRC-L per C22.2, No. 248.10
Self-Certified DC Ratings:
Voltage Rating: LCL and LCU (601-1600) 340 VDC
Interrupting Rating: 50,000 Amperes DC
RECOMMENDED SIZING:
LCL: 150% or more of motor full load current.
RECOMMENDED UPGRADE:
None Available.
EDISON
LCL
LCU
CROSS REFERENCE
BUSSMANN
GOULD
KLU
A4BY
KTU
None
LITTELFUSE
KLP-C, KLLU
None
BULLET™ CLASS L TIME-DELAY FUSES
BULLET™ CLASS L FAST-ACTING FUSES
AVERAGE TIME/CURRENT CURVE
5000A
6000A
4000A
3000A
2000A
AMPERE
RATING
1200A
1350A
1600A
Cat. No. LCU (Amp) 600 VAC
800A
4000A
1200A
1600A
2000A
3000A
300
800A
Cat. No.LCL (Amp) 600 VAC
AMPERE
RATING
300
200
100
100
80
60
40
30
20
10
10
8
6
TIME IN SECONDS
TIME IN SECONDS
4
1
3
2
1
.8
.6
.4
.3
.2
.1
.1
.08
.06
.04
.03
80,000
100,000
60,000
40,000
30,000
20,000
8,000
10,000
6,000
4,000
3,000
1,000
100,000
.01
10,000
1,000
.01
2,000
.02
RMS SYMMETRICAL CURRENT IN AMPERES
RMS SYMMETRICAL CURRENT IN AMPERES
15
BULLET™ CLASS L TIME-DELAY FUSES
BULLET™ CLASS L FAST-ACTING FUSES
PEAK LET-THROUGH CURRENT CURVES*
LCL (600V)
LCU (600V)
B
400,000
B
400,000
6,000
5,000
4,000
3,000
2,500
2,000
1,600
1,200
800
601
RMS SYMMETRICAL CURRENTS IN AMPERES
A-B= ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)
60,000
AMPERE
RATING
40,000
30,000
20,000
10,000
8,000
6,000
4,000
3,000
A
200,000
80,000
100,000
60,000
40,000
30,000
20,000
8,000
10,000
6,000
4,000
1,000
3,000
2,000
2,000
200,000
1,000
1,000
100,000
A
100,000
80,000
1,000
10,000
200,000
INSTANTENOUS PEAK LET THRU CURRENT AMPERES
AMPERE
RATING
100,000
10,000
INSTANTENOUS PEAK LET THRU CURRENT AMPERES
300,000
4,000
3,000
2,500
2,000
1,600
1,200
800
RMS SYMMETRICAL CURRENTS IN AMPERES
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)
CURRENT LIMITATION TABLES**
LCL (600V)
LCU (600V)
Current-Limiting Effects
*Prosp.
Let-Thru Current (Apparent RMS Symmetrical)
S.C.C.
Versus Fuse Ratings
800A
1200A
1600A
2000A
3000A
5,000
5,000
5,000
5,000
5,000
5,000
10,000
10,000 10,000
10,000
10,000
10,000
15,000
13,000 15,000
15,000
15,000
15,000
20,000
14,000 18,000
20,000
20,000
20,000
25,000
16,000 21,000
25,000
25,000
25,000
30,000
16,500 22,500
26,000
30,000
30,000
40,000
18,000 25,500
29,000
34,000
40,000
50,000
19,000 27,000
32,000
37,000
42,000
60,000
21,000 29,000
35,000
41,000
45,000
80,000
24,000 32,000
39,000
45,000
51,000
100,000
26,000 36,000
41,000
51,000
55,000
150,000
30,000 40,000
48,000
58,000
66,000
200,000
34,000 45,000
52,000
65,000
76,000
Current-Limiting Effects
*Prosp.
Let-Thru Current (Apparent RMS Symmetrical)
S.C.C.
Versus Fuse Ratings
800A
1200A 1600A 2000A 3000A 4000A
5,000
5,000
5,000
5,000 5,000
5,000 5,000
10,000
9,700
10,000 10,000 10,000 10,000 10,000
15,000
11,500 13,000 15,000 15,000 15,000 15,000
20,000
12,500 15,400 18,000 20,000 20,000 20,000
25,000
14,000 16,000 21,000 25,000 25,000 25,000
30,000
14,500 17,500 22,000 27,000 30,000 30,000
35,000
15,000 18,000 24,000 28,000 35,000 35,000
40,000
15,500 19,000 25,000 29,000 40,000 40,000
50,000
16,000 21,000 26,000 32,000 44,000 48,000
60,000
19,000 24,000 28,000 34,000 48,000 51,000
80,000
20,000 26,000 31,000 36,000 52,000 60,000
100,000
23,000 29,000 39,000 40,000 57,000 68,000
150,000
27,000 34,000 40,000 47,000 70,000 79,000
200,000
29,000 39,000 43,000 50,000 78,000 93,000
* RMS Symmetrical Amperes Short-Circuit Current.
NOTE: Data derived from Current Limiting Curves.
4000A
5,000
10,000
15,000
20,000
25,000
30,000
40,000
45,000
50,000
57,000
64,000
78,000
92,000
6000A
5,000
10,000
15,000
20,000
25,000
30,000
40,000
50,000
60,000
80,000
90,000
110,000
140,000
5000A 6000A
5,000 5,000
10,000 10,000
15,000 15,000
20,000 20,000
25,000 25,000
30,000 30,000
35,000 35,000
40,000 40,000
50,000 50,000
60,000 60,000
72,000 80,000
81,000 95,000
98,000 115,000
110,000 141,000
*RMS Symmetrical Amperes Short-Circuit Current.
NOTE: Data derived from Current Limiting Curves.
*Curves test data obtained at 15% short-circuit power factor when possible.
**"Apparent Let-Thru Amperes" values are read from "Peak Let-Through Current Curves" and the peak current value divided by 2.3
Asymmetry Factor.
16
BULLET™ CLASS L TIME-DELAY FUSES
BULLET™ CLASS L FAST-ACTING FUSES
GENERAL APPLICATION:
Edison Class L fuses, Catalog Numbers LCL time-delay or
LCU fast acting are recommended for high capacity main,
feeder or branch circuits in power distribution systems and
for special applications such as system upgrading, install
ahead of network protectors, etc. The choice of LCL or LCU
depends on the extent of mixed inductive and non-inductive
loads diversity. Apply LCL fuses for protection of large individual motor circuits. Size LCL fuses at 150% or more of the
motor nameplate current rating by checking starting characteristics against minimum melt Time/Current Curve.
CLASS L FUSES SPECIFICATION:
INSTALL CLASS L FUSES (600VAC) in switches rated
800-6000 amperes and in AMPERE RATINGS and “timedelay” or “fast-acting” types as shown on the plans. Installed
and spare “time-delay” fuses shall be Catalog Number LCL
and “fast-acting” fuses shall have silver links and be Catalog
Number LCU. Fuses shall be manufactured by Edison
Fusegear or equivalent submitted to the design engineer for
approval 10 days prior to the project bid date.
MOUNTING OF “BOLT-ON” FUSES shall be made by
installing stainless steel bolts of correct number, diameter
and length+, stainless steel spring washers on each side of
the bolt and stainless steel nuts. The nuts shall be tightened
to the torque recommended by ASTM Standards for the bolt
size used.
+Bolts shall have the largest diameter to fit fuse bolt holes and length to allow
full nut thread engagement. Bolts shall be installed in each fuse mounting
hole.
CLASS L FUSES
MOUNTING DIMENSIONS IN INCHES*
OVERALL DIMENSIONS IN INCHES*
17