SPD Telecom 2057 - Cooper Bussmann

Surge Protection Made Simple™ for Telecom Applications
IEC Class III Surge Arresters for 24Vac/dc to 230Vac/dc LV Systems
Description
The Cooper Bussmann® IEC Class III 24Vac/dc, 48Vac/dc,
60Vac/dc, 120Vac/dc and 230Vac/dc, two-pole, modular surge
arresters feature local, easy ID™ visual indication and optional
remote contact signaling. The unique module locking system fixes
the protection module to the base part. Modules can be easily
replaced without tools by simply depressing the release buttons.
Integrated mechanical coding between the base and protection
module ensures against installing an incorrect replacement module.
BSPH2A24D24LV(R)
BSPH2A48D48LV(R)
BSPH2A60D60LV(R)
BSPH2A150D150LV(R)
BSPH2A230D230LV(R)
LV System Arresters
The features of these two-pole devices are for use in combination
with other devices for AC and DC voltage systems.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a
floating changeover contact for use as a break or make contact,
according to circuit concept.
Visual Status
Indication
Remote Signal
Contact Available
Module Circuit Diagrams ›
Shown with optional remote contact signaling
Dimensions - mm
MOV
BPHA24D24LV
BPHA150D150LV
Shown with optional remote contact signaling
Gas Discharge Tube (single)
BPHA48D48LV
BPHA60D60LV
BPHA230D230LV
www.cooperbussmann.com/surge
0411
BU-SB11304
Page 1 of 2
Data Sheet 2057
Ordering Information
System Voltage
Max Continuous operating AC voltage (MCOV) [Uc]
Catalogue Numbers:
(Base + Modules)
24Vac/dc - 2
48Vac/dc - 2
60Vac/dc - 2
120Vac/dc - 2
30Vac/dc
60Vac/dc
75Vac/dc
150Vac/dc
255Vac/dc
BSPH2A48D48LV
BSPH2A60D60LV
BSPH2A150D150LV
BSPH2A230D230LV
Without Remote Signaling BSPH2A24D24LV
With Remote Signaling
Replacement Modules
230Vac/dc - 2
BSPH2A24D24LVR BSPH2A48D48LVR BSPH2A60D60LVR BSPH2A150D150LVR BSPH2A230D230LVR
BPHA24D24LV
BPHA48D48LV
BPHA60D60LV
BPHA150D150LV
BPHA230D230LV
Specifications
Line System Type
LV
LV
LV
LV
LV
Nominal AC voltage [UN]
Max continuous operating AC Voltage [Uc]
24V
48V
60V
120V
230V
30V
60V
75V
150V
255V
Max continuous operating DC Voltage [Uc]
Nominal load current AC [IL]
30V
60V
75V
150V
255V
25A
25A
25A
25A
25A
Nominal discharge current (8/20 µs) [In]
Total discharge current (8/20 µs) [L+N+PE] [Itotal]
Combined impulse [Uoc]
1kA
1kA
2kA
2kA
3kA
2kA
2kA
4kA
4kA
5kA
2kV
2kV
4kV
4kV
6kV
Combined impulse [L+N+PE] [Uoc total]
Voltage protection level [L-N] [UP]
4kV
4kV
8kV
8kV
10kV
<_ 180V
<_ 350V
<_ 400V
<_ 640V
<_ 1250V
<_ 630V
<_ 730V
<_ 730V
<_ 800V
<_ 1500V
--
--
--
--
335V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] [UT]
Temporary overvoltage (TOV) [L+N-PE] [UT]
--
--
--
--
400V / 5 sec.
--
--
--
--
TOV characteristics [L-N]
--
--
--
--
1200V + U0 / 20
Withstand
TOV characteristics [L/N-PE]
--
--
--
--
Withstand
TOV characteristics [L+N-PE]
--
--
--
--
Failure
Voltage protection level [L/N-PE] [UP]
Temporary overvoltage (TOV) [L-N] [UT]
SPD according to EN 61643-11
Type 3
SPD according to IEC 61643-1
Response time [L-N] [tA]
Class III
Response time [L-N-PE] [tA]
<_ 100 ns
<_ 25 ns
Max. mains-side overcurrent protection
25A gL/gG or C 25A
Short-circuit withstand capability for mains-side
overcurrent protection with 25A gL/gG
6kArms
-40oC to +80oC
Operating temperature range [TU]
Operating state/fault indication
Green (good)/Red (replace)
Number of ports
1
Cross-sectional area (min.)
0.5mm2/18AWG solid/flexible
Cross-sectional area (max.)
4mm2/10AWG solid/2.5mm2/12AWG flexible
For mounting on
35mm DIN rail per EN 60715
Enclosure material
Thermoplastic, UL 94V0
Location category
Indoor
Degree of protection
IP20
Capacity
1 Mod, DIN 43880
Standards Information*
KEMA
Product Warranty
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
Changeover Contact
AC Switching Capacity (Volts/Amps)
250V/0.5A
DC Switching Capacity (Volts/Amps)
250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area
for Remote Contact Signals Terminals
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Ordering Information
Order from Catalogue Numbers Above
* Standards information not applicable to DC ratings.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at
www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back-Up Fuses
DIN Fuse Size
NH Fuse Part Number
000
25NHG000B
00
125NHG00B
0
125NHG0B
01
125NHG01B
02
125NHG02B
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help
the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to
discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2011 Cooper Bussmann
w w w. c o o p e r b u s s m a n n . c o m
0411
BU-SB11304
Page 2 of 2
Data Sheet 2057