SPD IEC 1167

Surge Protection Made Simple™ for IEC Applications
IEC Class II Surge Arresters for 230 Volt, 2-Pole TN & TT Systems
Description
The Cooper Bussmann® IEC Class II 230 volt, two-pole, modular
surge arresters feature local, easy ID™ visual indication and optional
remote contact signaling. The unique module locking system fixes the
protection module to the base part. Modules can be easily replaced
without tools by simply depressing the release buttons. Integrated
mechanical coding between the base and protection module ensures
against installing an incorrect
replacement module.
BSPM2275TN(R)
BSPH2275TT(R)
230 Volt models are offered with MCOV ratings of 255 and 275 volts.
TN System Arresters
The features of these single-pole devices are for use in single-phase
230 volt TN systems (“2-0” circuit).
TT System Arrester
The features of these single-pole devices are for use in single-phase
230 volt TT and TNS systems (“1-1” circuit).
Remote Signaling Contact
Visual Status Indication
The three-pole terminal remote signaling contact versions have a
floating changeover contact for use as a break or make contact,
according to circuit concept.
Remote Signal
Contact Available
MOV
Thermal Disconnector
Gas Discharge Tube (single)
Circuit Diagrams
Dimensions - mm
BSPM2275TN(R)
BSPH2275TT(R)
Shown with optional remote
contact signaling
Shown with optional remote
contact signaling
Shown with optional remote contact signaling
www.cooperbussmann.com/Surge
0211 BU-SB101433
Page 1 of 2
Data Sheet 1167_A4
Ordering Information
System Voltage/Poles
Max. continuous operating AC voltage (MCOV) [UC]
Max. Continuous operating AC voltage (MCOV) [L-N] [UC]
Max. Continuous operating AC voltage (MCOV) [N-PE] [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Modules:
MOV Technology
Spark Gap technology
230V/2
275V
--BSPM2275TN
BSPM2275TNR
BPM275IEC
--
230V/2
-275V
255V
BSPH2275TT
BSPH2275TTR
BPM275IEC
BPSNPEIEC*
-_< 1.25kV
_< 1kV
----_< 25 ns
--335V/5 sec.
---
12kA
--_< 1.25kV
_< 1kV
_< 1.5kV
100A rms
-_< 25 ns
_< 100 ns
-335V/5 sec.
1200V/200 ms
Specifications
Lightning impulse current (10/350 µs) [N-PE] [Iimp]
Voltage protection level [UP]
Voltage protection level at 5kA [UP]
Voltage protection level [L-N] [UP]
Voltage protection level [L-N] at 5kA [UP]
Voltage protection level [N-PE] [UP]
Follow current extinguishing capability [N-PE] [Ifi]
Response time [tA]
Response time [L-N] [tA]
Response time [N-PE] [tA]
Temporary overvoltage (TOV) [UT]
Temporary overvoltage (TOV) [L-N] [UT]
Temporary overvoltage (TOV) [N-PE] [UT]
SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal discharge current (8/20 µs) [In]
Max. discharge current (8/20 µs) [Imax]
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection
Nominal AC voltage [UN]
TOV characteristics
Operating temperature range [TU]
Operating state/fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
Mounting
Enclosure material
Location category
Degree of protection
Capacity
Standards Information
Product Warranty
Type 2
Class II
20kA
40kA
125A gL/gG
50kA rms
230V
withstand
-40°C to +80°C
green (good)/red (replace)
1
1.5mm2/14AWG solid/flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
2 mods., DIN 43880
KEMA
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Ordering Information
Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuses
DIN Fuse Size
NH Fuse Part Number
00
125NHG00B
0
125NHG0B
01
125NHG01B
02
125NHG02B
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user
with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2011 Cooper Bussmann
w w w. c o o p e r b u s s m a n n . c o m
0211 BU-SB101433
Page 2 of 2
Data Sheet 1167_A4