SPD Wind 2095 - Cooper Bussmann

Surge Protection Made Simple™ for Wind Power Applications
IEC Class II Surge Arresters for 230/400 Volt, TNS & TT Systems
Description
The Cooper Bussmann® IEC Class II 230/400 volt, four-pole,
modular surge arresters feature local, easy ID™ visual
indication and optional remote contact signaling. The unique
module locking system fixes the protection module to the
base part. Modules can be easily replaced without tools by
simply depressing the release buttons. Integrated mechanical
coding between the base and protection module ensures
against installing an incorrect replacement module.
BSPM4230WE(R)
BSPH4230WE(R)
These 230 Volt models are offered with MCOV ratings of 275
volts.
TNS System Arrester
The features of these four-pole devices are for use in TNS
230/400 volt systems (“4-0” circuit) against surges.
TT System Arrester
The features of these four-pole devices are for use in TT and
TN-S 230/400 volt systems (“3+1” circuit) against surges.
Remote Signal
Visual Status Indication
Remote Signaling Contact
Contact Available
The three-pole terminal remote signaling contact versions
have a floating changeover contact for use as a break or make
contact, according to circuit concept.
Dimensions - mm
Circuit Diagrams - Shown with
optional remote contact signaling
BSPM4230WE(R)
MOV
Thermal Disconnecter
Gas Discharge Tube (single)
BSPH4230WE(R)
www.cooperbussmann.com/Surge
0211 BU-SB11187
Page 1 of 2
Data Sheet 2095
Ordering Information
System Voltage/Poles
230/400V/4
Max. Continuous Operating AC Voltage (MCOV) [Uc]
Max. Continuous Operating AC Voltage (MCOV) [L-N] [Uc]
Max. Continuous Operating AC Voltage [N-PE] [Uc]
Without Remote Signaling
With Remote Signaling
MOV Technology
Spark Gap Technology
Catalogue Numbers
(Base + Modules)
Replacement Modules
230/400V/4
275V
--
--
275V
--
255V
BSPM4230WE
BSPM4230WER
BPM275WE
--
BSPH4230WE
BSPH4230WER
BPM275WE
BPSNPEWE*
TNS
230/400V
TT/TNS
230/400V
--
12kA
≤1.25kV
--
Specifications
Line System Type
Nominal AC Voltage [UN]
Lightning Impulse Current (10/350µs) [N-PE] [Iimp]
Voltage Protection Level [Up]
Voltage Protection Level at 5kA [Up]
≤1kV
--
Voltage Protection Level [L-N] [Up]
--
≤1.25kV
Voltage Protection Level [L-N] at 5kA [Up]
--
≤1kV
Voltage Protection Level [N-PE] [Up]
--
≤1.5kV
Follow Current Extinguishing Capability [N-PE] [Ifi]
100Arms
Response Time [tA]
Response Time [L-N] [tA]
Response Time [N-PE] [tA]
Temporary Overvoltage (TOV) [UT]
≤25ns
--
--
≤25ns
--
≤100ns
335V/5sec.
--
Temporary Overvoltage (TOV) [L-N] [UT]
--
335V/5sec.
Temporary Overvoltage (TOV) [N-PE] [UT]
--
1200V/200ms
SPD According to EN 61643-11
Type 2
SPD According to IEC 61643-1
Class II
Nominal Discharge Current (8/20µs) [In]
20kA
Max. Discharge Current (8/20µs) [Imax]
40kA
Max. Mains-side Overcurrent Protection
125A gL/gG
Short-circuit Withstand Capability for Max. Mains-side Overcurrent Protection
50kA rms
TOV Characteristics
Withstand
Operating Temperature Range [TU]
-40oC to +80oC
Operating State/Fault Indication
Green (good)/Red (replace)
Number of Ports
1
Cross-Sectional Area (min.)
1.5mm2/14AWG solid/flexible
Cross-Sectional Area (max.)
35mm2/2AWG stranded-25mm2/4AWG flexible
Mounting
35mm DIN rail per EN 60715
Enclosure Material
Thermoplastic, UL94V0
Location Category
Indoor
Degree of Protection
IP20
Capacity
4 Mods., DIN 43880
Standards Information
KEMA
Product Warranty
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
60/75oC Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalogue Numbers Above
Recommended Cooper Bussmann Back Up Fuse Link
DIN Fuse Size
NH Fuse Part Number
00
125NHG00B
* N-PE Surge arrester module for location between neutral conductor and protective conductor in TT systems.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to
discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2 0 1 1 C o o p e r B u ssmann
w w w. c o o p e r b u s s m ann.com
0211 BU-SB11187
Page 2 of 2
Data Sheet 2095