SPD Catalogue - Cooper Bussmann

SPD Catalogue
SPD Catalogue
for AC applications
Eaton and Cooper united.
Energizing a world
that demands more.
We deliver:
s
s
Electrical solutions that use less energy, improve power reliability
and make the places we live and work safer and more comfortable
Hydraulic and electrical solutions that enable machines to deliver
more productivity without wasting power
s
Aerospace solutions that make aircraft lighter, safer and less costly
to operate, and help airports operate more efficiently
s
Vehicle drivetrain and powertrain solutions that deliver more power
to cars, trucks and buses, while reducing fuel consumption and emissions
Discover today’s Eaton.
Powering business worldwide
!SAGLOBALDIVERSIFIEDPOWERMANAGEMENTCOMPANYWE
HELPCUSTOMERSWORLDWIDEMANAGETHEPOWERNEEDEDFOR
BUILDINGSAIRCRAFTTRUCKSCARSMACHINERYANDBUSINESSES
%ATONSINNOVATIVETECHNOLOGIESHELPCUSTOMERSMANAGE
ELECTRICALHYDRAULICANDMECHANICALPOWERMORERELIABLY
EFFICIENTLYSAFELYANDSUSTAINABLY
2
EATON
SPD Catalogue
7EPROVIDEINTEGRATEDSOLUTIONSTHATHELPMAKEENERGY
INALLITSFORMSMOREPRACTICALANDACCESSIBLE
7ITHSALESOFBILLION%ATONHASAPPROXIMATELY
EMPLOYEESAROUNDTHEWORLDANDSELLSPRODUCTS
INMORETHANCOUNTRIES
Eaton.com
The need for
Surge Protection
Overvoltage surges can cause irreparable
damage to electrical equipment that
our infrastructure, industry and homes
are becoming increasingly reliant
upon. These transient events can
lead to corrupted software, industrial
downtime and PCB damage which
can be catastrophic due to the loss of
information, loss of output and high
replacement cost.
Surges can be caused by a
variety of different sources; such
as lightning strikes, industrial
machinery and power switching.
It is essential to protect electrical
equipment against these events to
ensure power quality and maximise the
lifetime of the electrical devices.
After extensive research and
development has been conducted,
Bussmann is able to offer a
comprehensive protective solution
for your equipment, eliminating the
disruptive and damaging effects that
surge and overvoltage conditions
can cause.
Causes of transients and surges
t
Lightning strikes:
t
t
Large scale impact with high current and voltage but the least common occurrence.
Power switching:
t
Utility and customer load switching such as motors, large loads, capacitor banks, fuse
and circuit breaker operation.
Damaging effects of transients and surges
1. Disruptive—a voltage transient enters an electronic
component and it is interpreted as a valid logic command
resulting in system lock-up, malfunction, faults or
corrupted files.
2. Dissipative—associated with short duration, low level
energy surges, resulting in equipment failure over time
including electronic components, ballasts, motors and
controllers, service entrance equipment, panelboards and
switchgear.
3. Destructive—associated with high level energy surges,
resulting in immediate equipment failure including
electronic components, motors and controllers, service
entrance equipment, panelboards and switchgear.
EATON
SPD Catalogue
3
Earthing system protection
International standard, IEC 60364 defines the three families of
Earthing System protection that uses two letter codes to signify the
protection that it provides, TN, TT and IT. The configuration of surge
protection will depend on the Earthing System used.
TN
Within TN systems there is a direct connection point with
Earth and a direct connection to neutral at the origin of the
installation, usually the start point of the three-phase system.
TN-S
Separate Protective Earth (PE) and Neutral (N) conductors from
transformer to consuming device, which are not connected
together at any point after the building distribution point.
Figure 1: TN-S wiring diagram.
Typical Applications:
t
Residential
t
Industrial
TN-C
Combined PE and N conductor from the transformer to
the consuming element. This system is not permitted for
conductors of less than 10mm² or for portable equipment.
The PEN conductor must be connected to a number of Earth
electrodes in the installation.
Figure 2: TN-C wiring diagram.
TT
In a TT earthing system the customer must provide their own
connection to Earth, independent of any Earth connection at
the generator.
Typical Applications:
t
Telecommunications
Figure 3: TT wiring diagram.
IT
In an IT network the electrical distribution system has
no connection to Earth or it only has a high impedance
connection. In an IT system, an insulation monitoring device is
used to monitor the impedance.
Figure 4: IT wiring diagram.
4
EATON
SPD Catalogue
Degrees of protection
SPDs are divided into three different levels of protection , Type
1, Type 2 and Type 3, depending on their function application,
as determined by IEC 61643-1.
SPD Type 1
A Type 1 SPD protects electrical installations to the lightning
grid or rod. It can discharge the surge current from the effect
of lightning spreading from the Earth conductor to the network
conductors.
Figure 5 characterises the current wave from a direct
lightning strike.
SPD Type 2
Figure 5: 10/350μs current wave.
A Type 2 SPD is the secondary protection system for all low
voltage electric installations. This is installed into each electrical
switchboard and prevents the spread of overvoltage’s in the
electrical systems, protecting the loads.
Figure 6 characterises the current wave from the effects of an
indirect lightning strike.
SPD Type 3
A Type 3 SPD has a low discharge current capacity. They must
therefore be installed as a supplement to a Type 2 SPD in the
vicinity of sensitive loads.
Figure 6: 8/20μs current wave
Type 3 SPDs are characterised by the wave form shown in
Figure 7.
Figure 7: 1.2/ 50μs voltage wave
EATON
SPD Catalogue
5
Plug-in modules
Description
When an SPD reaches the end of its life and indicates that it
needs to replaced, Bussmann is able to provide replacement
modules for the entire voltage range on offer.
These thermoplastic modules are IEC certified to IEC61643 and
save both time and money by simply clipping into the place of
the operated module. This swift exchange of parts ensures that
the system is protected which prevents industrial downtime
or periods when the electrical equipment is left vulnerable to
voltage surges.
SPCT2-335
Ordering information
Part numbers
SPCT2-075
SPCT2-135
SPCT2-175
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
SPCT2-580
System voltage
75 V
135 V
175 V
280 V
335 V
385 V
460 V
580 V
260V
Article numbers
167577
167582
167587
167592
167597
167602
167607
167612
167617
SPCT2-NPE60
Specifications
Max.continuous operating AC voltage [UC]
75 VAC
135 VAC
175 VAC
280 VAC
335 VAC
385 VAC
460 VAC
580 VAC
260 VAC
Voltage protection level [UP]
< 550 V
< 800 V
< 1.0 kV
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
< 2.6 kV
1.0 Kv
-
Voltage protection level at 5kA [UP]
400 V
550 V
700 V
1000 V
1200 V
1350 V
1700 V
2000 V
Max. mains-side overcurrent protection
125 A gL/gG -
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-
Short circuit withstand capability for max.
mains-side overcurrent protection
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
-
Temporary overvoltage (TOV) UT
75 VAC
135 VAC
175 VAC
350 VAC
415 VAC
415 VAC
580 VAC
580 VAC
-
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 100 ns
Temporary overvoltage NPE
1200 VAC (200 ms)
Response time [tA]
6
Follow current extinguishing capability [Ifi]
-
-
-
-
-
-
-
-
100 A rms
Nominal discharge current (8/20μs) In
15 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
Max discharge current [Imax]
30 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
IEC 61643
Standards information
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
SPD according to IEC 61643-1
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Operating temperature range
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40°C to + 70°C
Operating state/Fault indication
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
Blue, good.
Cross sectional area (min.)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4mm²
Cross sectional area (max.)
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25mm²
Mounting
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening
on DIN rail according to IEC/
EN 60715
Quick fastening on
DIN rail according
to IEC/ EN 60715
Enclosure material
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic UL
94 V2
Location category
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Rated frequency
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50/ 60 Hz
Degree of protection
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
EATON
SPD Catalogue
Single pole T1 and T1/T2
Description
Bussmann is able to provide SPDs to meet a variety of
applications and requirements. This range is specifically
designed and manufactured for customised protective
system solutions.
The modular designs feature integrated fault indication
which turns from green to red, visually alerting the operator
to whether or not the device has reached the end of its life
and needs to be replaced with a new module. Manufactured
from thermoplastic, the SPDs are IEC certified for use in
environments with an operational temperature range from
–40°C to +70°C.
Configurations of SPDs can be customised for the application
or for the installation location, the module locking system
with module release buttons make the replacement easy and
without tools by depressing the buttons and lifting the module
out.
Ordering information
General arrangement
SPBT12-280
T1
T1 / T2
Part numbers
SPI-35-400
SPI-50-NPE
SPI-100-NPE
SPBT12-280-1
SPBT12-280-1-NPE
SPBT12-NPE100
System voltage/poles
440 V / 1
260 V / 1+NPE
260 V / 1+NPE
280 V / 1
280 V /1 + NPE
255 V
Article numbers
267487
263138
263139
158306
158308
158307
Replacement modules
-
-
-
SPBT12-280
SPBT12-280
SPBT12-NPE100
Specifications
Max. continuous operating AC voltage [Uc]
440 VAC
260 VAC
260 VAC
280 VAC
280 VAC / 255 VAC
255 VAC
Voltage protection level [UP]
1.5 kV
1.5 kV
1.5 kV
< 1.5 kV
< 1.5 kV
< 1.5 kV
Voltage protection level at 5 kA [UP]
-
-
-
950 V
950 V
-
Max. mains-side overcurrent protection
125 A gL
-
-
160 A gL/gG
160 A gL/gG
-
Short circuit withstand capability for max. mains-side overcurrent
protection
-
-
-
50 kA rms
50 kA rms
-
-
Temporary overvoltage test value UT (5 s)
25 kA rms
-
-
370 VAC
348 / 370 VAC
Temporary overvoltage NPE
440 VAC
1200 VAC
1200 VAC
-
1200 VAC
1200 VAC (200 ms)
Response time (rate of voltage rise 5 kV/μs)
< 100 ns
< 100 ns
< 100 ns
< 25 ns
< 25 ns/ < 100 ns
< 100 ns
Follow current interrupt rating [Ifi]
3 kA rms
500 A rms
100 A rms
-
100 A rms
100A rms
Lightning impulse current (10/350μs) [limp]
35 kA
50 kA
100 kA
12.5 kA
12.5 kA / 100 kA
100 kA
Nominal discharge current (8/20μs) In
35 kA
50 kA
100 kA
25 kA
25 kA / 100 kA
100 kA
Max discharge current [Imax]
35 kA
50 kA
100 kA
50 kA
50 kA / 100 kA
100 kA
Standards information
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 1
Type 1
Type 1
Type 1 & 2
Type 1 & 2
Type 1 & 2
SPD according to IEC 61643-1
Class I
Class I
Class I
Class I & II
Class I & II
Class I & II
Operating temperature range
-40oC to +85oC
-40oC to +85oC
40oC to +85oC
-40oC to +70oC
-40oC to +70oC
-40oC to + 70oC
Operating state/Fault indication
-
-
-
green (good) /
red (replace)
green (good) /
red (replace)
green (good)/
red (replace)
Cross sectional area (min.)
45 mm2
45 mm2
45 mm2
4 mm2
4 mm2
4 mm2
Cross sectional area (max.)
90 mm
2
2
2
Mounting
25 mm
25 mm2
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
25 mm
2
2
90 mm
90 mm
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Enclosure material
Thermoplastic UL
94 V2
Thermoplastic UL
94 V2
Thermoplastic UL
94 V2
Location category
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Rated frequency
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50/60Hz
Degree of protection
IP40
IP40
IP40
IP40
IP40
IP40
Product warranty
2 Years
2 Years
2 Years
2 Years
2 Years
2 years
Auxiliary switch
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSX-SPM
ASAUXSX-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
7
Single pole T2
Description
Bussmann is able to offer a variety of T2 single pole and
single pole plus neutral SPDs. These devices are suitable
for use within a range of applications, allowing the
customisation of the configuration of SPDs within a specific
system. The neutral and protective earth unit incorporates
a spark gap device, shown by the blue indicator screen
built into the unit, adding extra levels of protection into the
configuration of SPDs.
Additionally, there are local and remote monitoring options
available. The ASAUXC-SPM device clips onto the end of any
configuration of SPDs, providing real time information to the
operator’s computer system on the status of the SPDs.
Ordering information
T2
Part numbers
SPCT2-075-1
SPCT2-135-1
SPCT2-175-1
SPCT2-280-1
SPCT2-335-1
SPCT2-385-1
SPCT2-460-1
System voltage/poles
75 V / 1
135 V / 1
175 V / 1
280 V / 1
335 V / 1
385 V / 1
460 V / 1
Article numbers
167578
167583
167588
167593
167598
167603
167608
Replacement modules
SPCT2-075
SPCT2-135
SPCT2-175
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
Specifications
8
Max. continuous operating AC voltage [Uc]
75 VAC
135 VAC
175 VAC
280 VAC
335 VAC
385 VAC
460 VAC
Voltage protection level [UP]
< 550 V
< 800 V
< 1.0 kV
< 1.4 kV
< 1.6 kV
<1.8 kV
< 2.2 kV
Voltage protection level at 5 kA [UP]
400 V
550 V
700 V
1000 V
1200 V
1350 V
1700 V
Max. mains-side overcurrent protection
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
Short circuit withstand capability for max.
mains-side overcurrent protection
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
Temporary overvoltage test value UT (5 s)
75 VAC
135 VAC
175 VAC
350 VAC
415 VAC
415 VAC
580 VAC
Temporary overvoltage NPE
-
-
-
-
-
-
-
Response time (rate of voltage rise 5 kV/μs)
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
Follow current interrupt rating [Ifi]
-
-
-
-
-
-
-
Lightning impulse current (10/350μs) [limp]
-
-
-
-
-
-
-
Nominal discharge current (8/20μs) In
15 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
Max discharge current [Imax]
30 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
Standards information
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
SPD according to IEC 61643-1
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Operating temperature range
-40oC to +70oC
-40oC to +70oC
-40oC to + 70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
Operating state/Fault indication
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
Cross sectional area (min.)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
Cross sectional area (max.)
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
Mounting
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Enclosure material
Thermoplastic
UL 94 V2
Thermoplastic
UL 94V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Location category
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Rated frequency
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
Degree of protection
IP40
IP40
IP40
IP40
IP40
IP40
IP40
Product warranty
2 Years
2 Years
2 years
2 years
2 years
2 years
2 years
Auxiliary switch
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
SPCT2-280-1
General arrangement
SPCT2-580-1
SPCT2-NPE60-1
SPCT2-280-1-NPE
SPCT2-335-1-NPE
SPCT2-385-1-NPE
SPCT2-460-1-NPE
SPCT2-580-1-NPE
580 V / 1
260V/ 1
280 V / 1 + NPE
335 V / 1 + NPE
385 V / 1 + NPE
460 V / 1 + NPE
580 V / 1 + NPE
167613
167618
167619
167621
167623
167625
167627
SPCT2-580
SPCT2-NPE60
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
SPCT2-580
580 VAC
260 VAC
280 VAC
335 VAC
385 VAC
460 VAC
580 VAC
< 2.6 kV
1.0 Kv
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
< 2.6 kV
2000 V
-
1000 V
1200 V
1350 V
1700 V
2000 V
125 A gL/gG
-
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
50 kA rms
-
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
580 VAC
-
350 VAC
415 VAC
415 VAC
580 VAC
580 VAC
-
1200 VAC (200 ms)
1200 VAC
1200 VAC
1200 VAC
1200 VAC
1200 VAC
< 25 ns
<100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
-
100 A rms
100 A rms
100 A rms
100 A rms
100 A rms
100 A rms
-
-
-
-
-
-
-
20 kA
20 kA
20 kA / 100 kA
20 kA / 100 kA
20 kA / 100 kA
20 kA / 100 kA
20 kA / 100 kA
40 kA
40 kA
40 kA / 100 kA
40 kA / 100 kA
40 kA / 100 kA
40 kA / 100 kA
40 kA / 100 kA
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Class II
Class II
Class II
Class II
Class II
Class II
Class II
-40oC to +70oC
-40°C to + 70°C
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
green (good) /
red (replace)
Blue, good
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
green (good) /
red (replace)
.
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Thermoplastic
UL 94 V2
Thermoplastic UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
50 / 60 Hz
50/ 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
IP40
IP40
IP40
IP40
IP40
IP40
IP40
2 years
2 Years
2 years
2 years
2 years
2 years
2 years
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
9
TN-S protection systems
Description
Bussmann is able to provide a range of SPDs that are certified
for use within TN-S protection systems. The TN-S system is
appropriate within the many residential and industrial electric
systems, especially in Europe. This is because the PE and N
are separate conductors which are connected together only
near a power source.
The modular designs feature integrated fault indication which
turns from green to red, visually alerting the operator to whether
or not the device has reached the end of its life and needs to be
replaced with a new module. Manufactured from thermoplastic,
the SPDs are IEC certified for use in environments with an
operational temperature range from –40°C to +70°C
Configurations of SPDs can be customised for the application or for
the installation location, the module locking system with module
release buttons make the replacement easy and without tools by
depressing the buttons and lifting the module out.
Ordering information
T1/T2
Part numbers
SPBT12-280-4
SPBT12-280-3-NPE
SPCT2-280-3-NPE
SPCT2-335-3-NPE
SPCT2-385-3-NPE
SPCT2-460-3-NPE
System voltage/poles
280 V / 4
280 V / 3 + NPE
280 V / 3 + NPE
335 V / 3 + NPE
385 V / 3 + NPE
460 V / 3 + NPE
Article numbers
158331
158332
167620
167622
167624
167626
Replacement modules
SPBT12-280
SPBT12-280
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
Specifications
Line system type
Max.continuous operating AC voltage [UC]
280 VAC
280 VAC / 255 VAC
280 VAC
335 VAC
385 VAC
460 VAC
Voltage protection level [UP]
< 1.5 kV
< 1.5 kV
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
Voltage protection level at 5 kA [UP]
950 V
950 V
1000 V
1200 V
1350 V
1700 V
Max. mains-side overcurrent protection
160A gL/gG
160 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
Short circuit withstand capability for max. mains-side overcurrent
protection
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
Temporary overvoltage test value UT (5 s)
370 VAC
348 /370 VAC
350 VAC
415 VAC
415 VAC
580 VAC
Temporary overvoltage NPE
-
1200 VAC
1200 VAC
1200 VAC
1200 VAC
1200 VAC
Response time (rate of voltage rise 5 kV/μs)
< 25 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
< 25 ns / < 100 ns
Follow current extinguishing capability [Ifi]
-
100 A rms
100 A rms
100 A rms
100 A rms
100 A rms
Lightning impulse current (10/350μs) [limp]
12.5 kA
3 x 12.5 kA / 100 kA
-
-
-
-
Nominal discharge current (8/20μs) In
25 kA
3 x 25 kA / 100 kA
3 x 20 kA / 100 kA
3 x 20 kA / 100 kA
3 x 20 kA / 100 kA
3 x 20 kA / 100 kA
Max discharge current [Imax]
50 kA
3 x 50 kA / 100 kA
3 x 40 kA / 100 kA
3 x 40 kA / 100 kA
3 x 40 kA / 100 kA
3 x 40 kA / 100 kA
Standards information
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 1 & 2
Type 1 & 2
Type 2
Type 2
Type 2
Type 2
SPD according to IEC 61643-1
Class I & II
Class I & II
Class II
Class II
Class II
Class II
Operating temperature range
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
Operating state/Fault indication
green (good) / red
green (good) / red
green (good) / red
green (good) / red
green (good) / red
green (good) / red (replace)
(replace)
(replace)
(replace)
(replace)
(replace)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
Cross sectional area (min.)
10
Cross sectional area (max.)
25 mm
Mounting
2
2
2
25 mm2
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/EN
60715
Thermoplastic UL 94 V2
Thermoplastic UL94 V2
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Indoor
Indoor
Indoor
Indoor
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
IP40
IP40
IP40
IP40
IP40
2 Years
2 Years
2 Years
2 Years
2 Years
ASAUXSX-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSX-SPM
ASAUXSX-SPM
25 mm
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Enclosure material
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Location category
Indoor
Indoor
Rated frequency
50 / 60 Hz
Degree of protection
IP40
Product warranty
2 Years
Auxiliary switch
ASAUXSX-SPM
EATON
SPD Catalogue
4 mm2
25 mm
25 mm
25 mm
2
2
SPCT2-280-3+NPE
General arrangement
T2
SPCT2-580-3-NPE
SPCT2-135-4
SPCT2-175-4
SPCT2-280-4
SPCT2-335-4
SPCT2-385-4
SPCT2-460-4
SPCT2-580-4
580 V / 3 + NPE
135 V
175 V
280 V
335 V
385 V
460 V
580 V / 4
167628
167586
167591
167596
167601
167606
167611
167616
SPCT2-580
SPCT2-135
SPCT2-175
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
SPCT2-580
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
580 VAC
135 VAC
175 VAC
280 VAC
335 VAC
385 VAC
460 VAC
580 VAC
< 2.6 kV
< 800 V
< 1.0 kV
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
< 2.6 kV
2000 V
550 V
700 V
1000 V
1200 V
1350 V
1700 V
2000 V
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
580 VAC
580 VAC
135 VAC
175 VAC
350 VAC
415 VAC
415 VAC
580 VAC
1200 VAC
-
-
-
-
-
-
-
< 25 ns / < 100 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
100 A rms
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 x 20 kA / 100 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
3 x 40 kA / 100 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Class II
-40oC to +70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
green (good) / red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
2
2
2
2
25 mm
25 mm
25 mm
25 mm
25 mm
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Thermoplastic UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Indoor
Indoor
50 / 60 Hz
IP40
2
2
2
25 mm2
25 mm
25 mm
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Quick fastening on DIN
rail according to IEC/
EN 60715
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
IP40
IP40
IP40
IP40
IP40
IP40
IP40
2 Years
2 years
2 years
2 years
2 years
2 years
2 years
2 years
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
11
TN-C protection systems
Description
Bussmann is able to offer a range of SPDs for use within
a TN-C system. This is where there is a combined PEN
conductor which fulfils the role of the separate PE & N
conductors.
The modular designs feature integrated fault indication
which turns from red to green, visually alerting the operator
to whether or not the device has reached the end of its life
and needs to be replaced with a new module. Manufactured
from thermoplastic, the SPDs are IEC certified for use in
environments with an operational temperature range from
–40°C to +70°C.
Configurations of SPDs can be customised for the application
or for the installation location, the module locking system
with module release buttons make the replacement easy and
without tools by depressing the buttons and lifting the module
out.
Ordering information
T1
T1 / T2
Part numbers
SPI-35-440-3
SPBT12-280-3
SPCT2-075-3
SPCT2-135-3
SPCT2-175-3
System voltage/poles
440 V / 3
280/3
75 V/3
135 V/3
175 V/3
Article numbers
267487
158330
167580
167585
167590
Replacement modules
-
SPBT12-280
SPCT2-075
SPCT2-135
SPCT2-175
Line system type
TN-C
TN-C
TN-C
TN-C
TN-C
Max.continuous operating AC voltage [UC]
440 VAC
280 VAC
75 VAC
135 VAC
175 VAC
< 1.0 kV
Specifications
12
Voltage protection level [UP]
1.5 kV
< 1.5 kV
< 550 V
< 800 V
Voltage protection level at 5kA [UP]
-
950 V
400 V
550 V
700 V
Max. mains-side overcurrent protection
125 A gL
160 A gL/gG
125A gL/gG
125A gL/gG
125A gL/gG
Short circuit withstand capability for max. mains-side overcurrent
protection
25 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
Temporary overvoltage test value UT (5 s)
440 VAC
370 VAC
75 VAC
135 VAC
175 VAC
Response time (rate of voltage rise 5 kV/ μs)
< 100 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
Follow current extinguishing capability [Ifi]
3 kA rms
-
-
-
-
Lightning impulse current (10/350μs) [limp]
35 kA
12.5 kA
-
-
-
Nominal discharge current (8/20μs) In
35 kA
25 kA
15 kA
20 kA
20 kA
Max discharge current [Imax]
35 kA
50 kA
30 kA
40 kA
40 kA
Standards information
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 1
Type 1 & 2
Type 2
Type 2
Type 2
SPD according to IEC 61643-1
Class I
Class I & II
Class II
Class II
Class II
Operating temperature range
-40oC to +85oC
40oC to +70oC
-40oC to + 70oC
-40oC to +70oC
-40oC to +70oC
Operating state/Fault indication
-
green (good) / red (replace)
green (good) / red (replace)
green (good) / red (replace)
green (good) / red (replace)
Cross sectional area (min.)
45 mm2
4 mm2
4 mm2
4 mm2
4 mm2
Cross sectional area (max.)
90 mm
2
Mounting
2
2
2
25 mm
25 mm2
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
25 mm
25 mm
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Enclosure material
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Location category
Indoor
Indoor
Indoor
Indoor
Indoor
Rated frequency
50 / 60 Hz
50 / 60 Hz
50/60 Hz
50 / 60 Hz
50 / 60 Hz
Degree of protection
IP40
IP40
IP40
IP40
IP40
Product warranty
2 Years
2 Years
2 years
2 years
2 years
Auxiliary switch
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
52.5
General arrangement
SPCT2-280-3
T2
SPCT2-280-3
SPCT2-335-3
SPCT2-385-3
SPCT2-460-3
SPCT2-580-3
280 V/3
335 V/3
385 V/3
460 V/3
580 V/3
167595
167600
167605
167610
167615
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
SPCT2-580
TN-C
TN-C
TN-C
TN-C
TN-C
280 VAC
335 VAC
385 VAC
460 VAC
580 VAC
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
< 2.6 kV
1000 V
1200 V
1350 V
1700 V
2000 V
125A gL/gG
125A gL/gG
125A gL/gG
125A gL/gG
125A gL/gG
50 kA rms
50 kA rms
50 kA rms
50kA rms
50kA rms
350 VAC
415 VAC
415 VAC
580 VAC
580 VAC
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25ns
-
-
-
-
-
-
-
-
-
-
20 kA
20 kA
20 kA
20 kA
20 kA
40 kA
40 kA
40 kA
40 kA
40 kA
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
Type 2
Type 2
Type 2
Type 2
Type 2
Class II
Class II
Class II
Class II
Class II
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
-40oC to +70oC
green (good) / red (replace)
green (good) / red (replace)
green (good) / red (replace)
green (good) / red (replace)
green (good) / red (replace)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
2
2
2
2
25 mm2
25 mm
25 mm
25 mm
25 mm
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Thermoplastic UL 94 V2
Indoor
Indoor
Indoor
Indoor
Indoor
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 /60 Hz
IP40
IP40
IP40
IP40
IP40
2 years
2 years
2 years
2 years
2 years
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
13
TT protection systems
Description
Bussmann is able to offer a selection of IEC certified
thermoplastic SPDs for the TT earthing system. The TT
system is often used in the telecommunication industry
where interference-free earthing is required. One of the
main advantages of the TT earthing system is that it is clear
of both high and low frequency noises that come through
the neutral wire of connected electrical equipment.
The modular designs feature integrated fault indication
which turns from green to red, visually alerting the operator
to whether or not the device has reached the end of its life
and needs to be replaced with a new module. Manufactured
from thermoplastic, the SPDs are IEC certified for use in
environments with an operational temperature range from
–40°C to +70°C
Ordering information
T1 & T2
Part numbers
SPBT12-280-2
SPCT2-075-2
SPCT2-135-2
SPCT2-175-2
SPCT2-280-2
SPCT2-335-2
SPCT2-385-2
SPCT2-460-2
System voltage
280 V / 2
75 V
135 V
175 V
280 V
335 V
385 V
460 V
Article numbers
158309
167579
167584
167589
167594
167599
167604
167609
Replacement modules
SPBT12-280
SPCT2-075
SPCT2-135
SPCT2-175
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
Line system type
TT
TT
TT
TT
TT
TT
TT
TT
Max.continuous operating AC voltage [UC]
280 VAC
75 VAC
135 VAC
175 VAC
280 VAC
335 VAC
385 VAC
460 VAC
Specifications
14
Voltage protection level [UP]
< 1.5 kV
< 550 V
< 800 V
< 1.0 kV
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
Voltage protection level at 5kA [UP]
950 V
400 V
550 V
700 V
1000 V
1200 V
1350 V
1700 V
Max. mains-side overcurrent protection
160 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
Short circuit withstand capability for max.
mains-side overcurrent protection
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
Temporary overvoltage (TOV) UT
370 VAC
75 VAC
135 VAC
175 VAC
350 VAC
415 VAC
415 VAC
580 VAC
Response time [tA]
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
Lightning impulse current (10/350μs) [limp]
12.5 kA
-
-
-
-
-
-
-
Nominal discharge current (8/20μs) In
25 kA
15 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
Max discharge current [Imax]
50 kA
30 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
Standards information
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 1 & 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
SPD according to IEC 61643-11
Class I & II
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Operating temperature range
-40oC to +70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
Operating state/Fault indication
green (good) /
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
Cross sectional area (min.)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
Cross sectional area (max.)
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
Mounting
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Enclosure material
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Location category
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Rated frequency
50 / 60 Hz
50/60Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
Degree of protection
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
Product warranty
2 Years
2 years
2 years
2 years
2 years
2 years
2 years
2 years
Auxiliary switch
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
SPCT2-280-2
General arrangement
T2
SPCT2-580-2
SPCT2-075-4
SPCT2-135-4
SPCT2-175-4
SPCT2-280-4
SPCT2-335-4
SPCT2-385-4
SPCT2-460-4
SPCT2-580-4
580 V
75 V
135 V
175 V
280 V
335 V
385 V
460 V
580 V / 4
167614
167581
167586
167591
167596
167601
167606
167611
167616
SPCT2-580
SPCT2-075
SPCT2-135
SPCT2-175
SPCT2-280
SPCT2-335
SPCT2-385
SPCT2-460
SPCT2-580
TT
TT
TT
TT
TT
TT
TT
TT
TT
580 VAC
75 VAC
135 VAC
175 VAC
280 VAC
335 VAC
385 VAC
460 VAC
580 VAC
< 2.6 kV
< 550 V
< 800 V
< 1.0 kV
< 1.4 kV
< 1.6 kV
< 1.8 kV
< 2.2 kV
< 2.6 kV
2000 V
400 V
550 V
700 V
1000 V
1200 V
1350 V
1700 V
2000 V
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
50 kA rms
580 VAC
75 VAC
135 VAC
175 VAC
350 VAC
415 VAC
415 VAC
580 VAC
580 VAC
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
< 25 ns
-
-
-
-
-
-
-
-
-
20 kA
15 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
20 kA
40 kA
30 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
IEC 61643
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Type 2
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Class II
Class II
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
-40oC to + 70oC
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
green (good)/
red (replace)
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
4 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Quick fastening on
DIN rail according to
IEC/EN 60715
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Thermoplastic
UL 94 V2
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
2 years
2 years
2 years
2 years
2 years
2 years
2 years
2 years
2 years
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
ASAUXSC-SPM
EATON
SPD Catalogue
15
Remote signalling contact
Description
5.5
Bussmann is also able to offer an additional plug
in Auxiliary Switch which is designed to be easily
installed within each configuration of SPDs on
offer. When SPDs are located in different areas of
a facility or in hard to reach places, the Auxiliary
Switch transmits a signal into the operators
computer system to clearly indicate that the
specific device needs to be changed when visual
identification is not practical. The signalling occurs
instantaneously when the device has functioned,
providing an up to date status of the system
to ensure that the equipment is secure against
future strikes.
80
Part numbers
ASAUXSC-SPM
Article number
131785
Specifications
Rated insulation voltage
16
250 VAC
Rated frequency
50 / 60 Hz
Switching contact
1 CO
Minimum voltage per contact
24 VAC
Rated operational current AC12
2 A / 250 VAC
Maximum back up fuse
2A gL
Overvoltage category
IV
Pollution degree
2
Frame size
45 mm
Device height
80 mm
Device width
8.8 mm
Weight
41 g
Mounting
DIN rail mounting with
screw fixing
Degree of protection
IP 40
Finger and hand touch safe acc. to
BGV A3, ÖVE-EN 6
Upper and lower terminals
Lift terminals
Terminal capacity
2 x 2.5 mm2
Tightening torque of terminal screws
0.8 - 1 Nm
EATON
SPD Catalogue
45
44
8.8
60
ASAUXSC-SPM
Ordering information
23
General arrangement
Lead through terminals
Description
There are two different Lead Through Terminals available for
the range of SPDs (excluding 690 VAC). They permit the orderly
wiring of the SPDs and serve to act as a lead through for
circuits which require vertical connections from the upper to
the lower SPD connection level.
The ASLTT-63 is suitable for use alongside all T2 devices and the
SPB-D-125 is suitable alongside all T1 devices.
Ordering information
Part numbers
SPB-D-125
ASLTT-63
Article number
248145
131784
Specifications
Rated voltage Uc
500 V AC/DC
500 V AC/DC
O
Rated current IN
125 A / 30 C
63A
Peak impulse current (10/350) μs
100 kA
-
Overvoltage category
III
-
Frame size
45 mm
45 mm
Device height
90 mm
90 mm
Device width
17.5 mm
17.5 mm
Mounting
Quick fastening on DIN rail IEC /
EN 60715
Quick fastening on DIN rail IEC /
EN 60715
Degree of protection
IP 40
IP 40
Upper and lower terminals
Lift and open-mouthed terminals
Lift and open-mouthed terminals
Terminal capacity
1 - 25 mm2 (flexible)
1 - 35 mm2 (rigid)
1 - 25 mm2
Tightening torque of terminals screws
4 - 4.5 Nm
2.4 - 3 Nm
5.5
90
17.5
45
43.5
23
80
8.8
45
44
60
58
SPB-D-125
ASLTT-63
EATON
SPD Catalogue
17
690 VAC wind and industrial
applications
Description
Bussmann range of 690 VAC surge protection devices
are designed specifically for higher voltage industrial
applications and installation into wind power
applications.
Specifically designed for the higher system voltage of
wind and industrial applications the 690 VAC SPDs have
a high surge discharge capability due to heavy-duty zinc
oxide varistor and spark-gap technology; and includes both
Type 1 and Type 2 devices for protection against lightning
strikes and voltage surges.
As well as meeting the requirements of the EN 6164311 standard for low voltage Surge Protection Devices,
the 690 VAC SPDs are also vibration and shock resistant
according to the EN60068-2 standard making them
especially suitable for industrial and wind applications.
Ordering information
BSPS1690WER
T1
T2
Part numbers without remote signaliing
BSPS1690WE
BSPM1690WE
Part numbers with remote signalling
BSPS1690WER
BSPM1690WER
BSPM3690WE
BSPM3690WER
System voltage/poles
690 V / 1
690 V / 1
690 V / 3
Replacement modules
-
BPM750WE
BPM750WE
Line system type
TNS, TNC, IT
TN, TT
TNC
Max.continuous operating AC voltage [UC]
760 VAC
600 VAC
600 VAC
Voltage protection level [UP]
≤ 4 kV
≤ 3 kV
≤ 3 kV
Specifications
Voltage protection level at 5kA [UP]
-
≤ 2.5 kV
≤ 2.5 kV
Max. mains-side overcurrent protection
125 A gL/gG (L-L)
100 A gL/gG
100 A gL/gG
Temporary overvoltage test value (TOV) [UT]
1000 V / 5 sec
900 V / 5 sec
900 V / 5 sec
Follow current extinguishing capability [Ifi]
25 kA rms
25 kA rms
25 kA rms
Lightning impulse current (10/350μs) [limp]
25 kA
-
-
Nominal discharge current (8/20μs) In
25 kA
15 kA
15 kA
25 kA
25 kA
IEC 61643
Max discharge current [Imax]
18
Standards information
IEC 61643
IEC 61643
SPD according to EN 61643-11
Type 1
Type 2
Type 2
SPD according to IEC 61643-1
Class I
Class II
Class II
Number of poles
1
1
3
Operating temperature range
-40oC to +80oC (parallel)
-40oC to +60oC (series)
-40oC to +80oC
-40oC to +80oC
Operating state/Fault indication
green (good) / red (replace)
green (good) / red (replace)
green (good) / red (replace)
Cross sectional area (min.)
10 mm2 solid / flexible
1.5 mm2 solid / flexible
1.5 mm2 solid / flexible
Cross sectional area (max.)
50 mm2 stranded /
35 mm2 flexible
35 mm2 stranded
25 mm2 flexible
35 mm2 stranded
25 mm2 flexible
Mounting
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Quick fastening on DIN rail
according to IEC/EN 60715
Enclosure material
Thermoplastic UL 94 V0
Thermoplastic UL 94 V0
Thermoplastic UL 94 V0
Location category
Indoor
Indoor
Indoor
Degree of protection
IP 20
IP 20
IP 20
Product warranty
2 Years
2 Years
2 Years
EATON
SPD Catalogue
Frequently asked questions (FAQs)
What is a surge protector?
What is an MOV?
A surge protector is a device that limits
transient overvoltage’s to a safe level, thus
protecting equipment it is connected to
from damage.
A Metal Oxide Varistor is a variable resistor
typically made of a large block of zinc oxide
grains. They act like semiconductors, an
insulator below the conduction voltage and a
low value resistor above it.
How does an SPD work?
In conduction mode, the MOV diverts and
dissipates the transient to earth. MOVs
generally connect from the line conductors to
earth. The thickness of the MOV determines
the clamping voltage and diameter determines
the current capacity.
A surge protector works by momentarily
“switching” from an open circuit mode into a
low impedance mode and shunting the surge
energy to the ground and in doing so, it limits
the overvoltage to a safe level.
When the surge event is over, the protector
returns to its open circuit mode, ready for
the next event or if it has reached the end of
life then it remains open circuit safely until
it is replaced. The visual indicator or remote
signalling unit will clearly alert the operator
when the SPD has reached the end of life
How long does an SPD last?
How long an MOV based SPD lasts
usually depends upon how often the MOV
experiences an overvoltage event and for how
long. Every time an MOV switches, its life is
degraded. The greater the transient hit, the
greater the degradation of the MOV.
What is shunting?
Shunting is the term used to describe the
process by which an SPD redirects voltage
transient energy to the ground through a low
impedance path.
How to size an SPD
An SPD size is determined by a variety
of factors including geography, electrical
environment, cost of downtime and the
importance of equipment in operation,
amongst others.
Call Bussmann to discuss your requirements
on +44 (0)1509 882699
EATON
SPD Catalogue
19
Eaton is dedicated to ensuring that reliable, efficient and safe
power is available when it’s needed most. With unparalleled
knowledge of electrical power management across industries,
experts at Eaton deliver customized, integrated solutions to solve
our customers’ most critical challenges.
Our focus is on delivering the right solution for the application.
But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal
support that makes customer success a top priority. For more
information, visit www.eaton.com/electrical.
Contact your local Eaton Office
Cooper Bussmann (UK) Ltd
Melton Road
Burton-on-the-Wolds
LE12 5TH
United Kingdom
Tel: +44 (0)1509 882 600
www.bussmann.com
Eaton Industries Manufacturing GmbH
Electrical Sector EMEA
Route de la Longeraie
71110 Morges, Switzerland
Eaton.eu
© 2014 Eaton
All Rights Reserved
Printed in the United Kingdom
Publication No. BR024003EN
February 2014
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.