MA- Series Three Phase Adjustable Trip Miniature Circuit

MA- Series
Three Phase Adjustable Trip
Miniature Circuit Breakers/
Manual Motor Controllers
UL508 listed
E137938
CAN/CSA-C22.2 No.14 certified
The MA was designed to handle the high
inrush loads of 3 phase transformers,
power supplies, motors, etc. The MA
protects wiring and equipment from
damage caused by the three major
classes of over-current, yet greatly reduces the number of nuisance trips in high
Type Designation
starting and inrush current circuits.
16
U
M
MA
__
__
__
An IEC device with excellent ratings under ____
(a)
(b) (c) (d)
a UL listing at 480Y/277V (including group
ratings) and at 500V under international
(a) = MA - Manual Motor Controller
standards, the Altech/ABL Sursum MA
provides short and long term cost effective (b) = Rated Current
circuit protection for USA and/or export (c) = U - US Housing
applications. The short term advantages
= R - US Housing + Ring Tongue
include: (1) adjustable thermal trip allows (d) = M - Part No. Designation
finalization of initial designs before
procurement of the load equipment is Voltage Rating
480Y/277V AC
complete; (2) snap-on mounting for readily
AIC
(Interrupt
Capacity)
0.16A-2.5A:
42kA; 4.0A-16A: 14kA; 20A-40A: 10kA
available, internationally standardized DIN
Rail saves panel layout design time as well Standard Short Circuit Withstand Rating 0.16A-2.5A: 42kA; 4.0A-16A: 14kA
as installation and change labor; (3) large (UL/CSA Ratings)
cage-clamp terminals with screws suitable Group Short Circuit Ratings
see above
to power screwdrivers, simplifies and (UL/CSA Ratings)
speeds wiring; (4) convenient switched
6000 on/off operations with 2xRC
disconnect during factory testing and/or Typical Life
initial start-up saves time and aggravation. Calibration Temperature
25°C, +0°, -5° (77°F, +0° -9°)
The key long term advantage is customer Standard Pack and Weight
1/450g (1.0 lb.)
satisfaction and proven over-current proTerminal
Size
Acceptability
Top/Bottom:
18-3 AWG
tection of wiring and equipment (and the
lack of rework/repair costs).
Terminal Torque (min/max)
2 Nm (17.7 lb.in.) / 2.5Nm (22.2 lb.in)
FLA Dial
Adjustment
Markings
Cat. No.
Rated
Current
MA016UM
0.16A
0.1/ 0.12/0.14/0.16
MA025UM
0.25A
0.16/0.19/0.22/0.25
MA040UM
0.40A
0.25/0.30/0.35/0.40
MA063UM
0.63A
0.40/0.48/0.56/0.63
0.63/0.75/0.87/1.0
MA1.0UM
1.0A
MA1.6UM
1.6A
1.0/1.2/1.4/1.6
MA2.5UM
2.5A
1.6/1.9/2.2/2.5
MA4.0UM
4.0A
2.5/3.0/3.5/4.0
MA6.3UM
6.3A
4.0/4.8/5.6/6.3
MA10UM
10A
6.3/7.5/8.7/10
MA16UM
16A
10/12/14/16
MA20UM
20A
16/17/18.5/20
MA25UM
25A
20/21.5/23/25
MA32UM
32A
25/27/30/32
MA40UM
40A
32/34/37/40
GROUP SHORT
CIRCUIT RATING
AT 480VACa
(and BCP size)
42kARMS
symmetrical
(max. 1200A
MCCB
or RK5)
14kARMS
symmetrical
(max. 350A
MCCB
or RK5)
10kARMS
symmetrical
(max. 350A
MCCB
or RK5)
3Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE
(See Note for HEA Definition)
110-120V
HP (HEA)
200V
HP (HEA)
208V
HP (HEA)
220-240V
HP (HEA)
460-480V
HP (HEA)
Through MA2.5U, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA’s general purpose
rated current (RC, equals maximum dial setting) and a locked
rotor current not exceeding 6 times the MA’s RC.
1/2 (4.0)
3/4 (3.2)
3/4
(3.1)
1
(3.6)
2
(3.42)
3/4 (5.6)
11/2 (6.0)
11/2
(5.7)
11/2
(5.2)
3
(4.8)
1
2
2
(7.5)
3
(9.6)
5
(7.6)
(7.2)
(7.8)
2
(13.6)
3 (11.0)
3
(10.6)
5
(15.2)
10
(14.0)
3
(19.2)
5 (17.5)
5
(16.7)
5
(15.2)
10
(14.0)
3
(19.2)
5 (17.5)
71/2
(24.2)
71/2
(22.0)
15
(21.0)
5
(30.4)
71/2 (25.0)
71/2
(24.2)
10
(28.0)
20
(27.0)
5
(30.4)
10 (32.0)
10
(31.0)
10
(28.0)
25
(34.0)
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as
NFPA-70 Tables 430-248, 430-249, 430-250; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc. Multiply
HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.
a The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher
standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
30
Dimensions in mm
43.8 mm
37.5 mm
25.5 mm
7
52.5 mm
45 mm
35 mm
89.5 mm
44.5 mm
6
7
17.2 mm
3
30.2 mm
43.8 mm
70.1 mm
MA- Series Trip Curves
MA/USA Manual Motor Controller
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
31
V-EA and MA Accessories
C
For mounting instructions please refer to page 43.
US
UL Listed
17.7 mm
E137938
Auxiliary Contact, Alarm Switch
Contacts Type
Std Pk
H10UM
1 Auxiliary Contact
1NO
H11UM
2 Auxiliary Contacts
1NO + 1NC
H12UM
3 Auxiliary Contacts
1NO + 2NC
H21UM
3 Auxiliary Contacts
2NO + 1NC
HLS11M* 1 Auxiliary/1 Signal Contacts 1CO + 1CO (Signal)
6
6
6
6
6
45 mm
Description
87 mm
52.7 mm
6 mm
63.8 mm
8.8 mm
Rated Operating
Currents
10A@240V AC
3A@110V AC
1A@220V AC
1mA @ 24V DC
max. 0.8Nm (7 lb.in)
Minimum Contact Load
Torque
Wire Range:
Single Wire
Stranded Wire
Stranded Wire
with Ferrule
Dimensions HxxUM.
68.4 mm
9 mm
43.8 mm
Shunt Trip
Type/ Cat No.
Description
FA12UM
FA24UM
FA48UM
12V AC/DC
24V AC/DC
48 - 72V AC/DC
FA110UM
110 - 240V AC/DC,
277V AC
Max. Operating
Current @ Un
45 mm
88 mm
1.0mm² - 2.5mm² (18-14 AWG)
1.0mm² - 1.5mm² (18-16 AWG)
1.0mm² - 1.5mm² (18-16 AWG)
Std Pk
1.3A
0.6A
0.2A
0.25A @ 110V
0.5A @ 240V
0.58A @ 277V
63.8 mm
5
5
5
12.4 mm
6 mm
Dimensions HLS11M.
21.8 mm
5
AWG 23
ca. 180-200
Type/ Cat No.
Undervoltage Trip*
Line Voltage VE
Std Pk
UA120UM
120V AC, 60Hz
5
45 mm
Reset-Hold Voltage = 0.85 x VE
Drop-Out Voltage = 0.35 ~ 0.7 x VE
45 mm
89.5 mm
Type/ Cat No.
VE = Rated Voltage
6 mm
17.5 mm
Neutral Pole
Type/ Cat No.
Rated Current In
Rated Voltage
Std Pk
N63UM
0.3 - 63A
480Y/277V AC
6
43.6 mm
68.4 mm
Dimensions UA120UM.
44 mm
37.5 mm
25.5 mm
6 mm
BS.UL
100
34.5 mm
Std Pk
44.5 mm
Type/ Cat No.
89.3 mm
to cover the terminal screw holes on
the switching devices, neutral Poles
and shunt trips for increased touch
protection.
7 mm
45 mm
Touch Protection Caps
Mounting Screw 34mm
to connect the auxiliary contact and shunt
trip or neutral Pole to the circuit breaker.
Lock-out Adapter
Type/ Cat No.
Std Pk
Type/ Cat No.
Std Pk
E983419
10
EASS
10
8 mm
14.5 mm
17.5 mm
4 mm
30.5 mm
44 mm
68.4 mm
Dimensions N63UM, FAxxUM.
* UL Pending
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
32
Cooling Spacer
Cat. No. 15.960
TEMPERATURE CORRECTION CURVE
Ambient Temperature and Adjacent Mounting/Loading Adjustment
(V-EA/MA Ambient Temperature - 25°C to 55°C, Storage Temperature -40°C to 70°C)
Calibration Temperature
160
150
140
130
Adjacent Mounting Temperature
Adjustment 3% of RC for every
additional pole above 3.
Maximum 20% off RC for a total
of 10 poles or more.*
110
20
%
Rated Current (%)
120
Ambient Temperature Adjustment
5% of RC for every 10°C (18°F).
100
up
to
90
3p
ole
s
adj
ace
nt m
oun
80
ted
ma
or ximum
mo
re, 20%
adj
ace off R
nt m C fo
oun r a t
ted otal
*
o
70
60
* Cooling spacer (Part #15.960)
between each group of 3 poles
will eliminate these adjustments.
50
ff 1
0
pol
es
40
-40
-40
-30
-22
-20
-4
-10
14
0
32
10
50
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90 (°C)
194 (°F)
Ambient Temperature