A ltech U L 508

Altech UL508
V-EA and MA
Manual Motor
Controllers
Accessories
E137938
UL508 Listed
Accessories can be factory or field mounted on V-EA and MA manual motor controllers for enhanced
control and monitoring capabilities. Field mounting kits include all necessary parts and instructions.
Accessories can be gang mounted on a single controller (the Auxiliary Switch in the outside
position). The mounting arrangement links the internal latch-pins for the tripping mechanisms,
ensuring simultaneous trips. Handles are linked to simplify manual resetting.
FA - Shunt Trip
Trip/Coil
Voltage
AC or DC
Type/
Cat. No.
FA12UM
FA24UM
FA48UM
FA110UM
Standard Pack: 5
Weight: 525 grams (1.16 lb.)
Width: 17.5mm (.689in.)
Max. Coil
Current
12V
24V
48-72V
110V/220V
Approvals
1.3A
0.6A
0.2A
0.25A/0.5A
UA - Undervoltage Trip (not UL listed)
Type/
Cat. No.
Line Voltage
60Hz*
UA120UM
UA220UM
120VAC
220VAC
Standard Pack: 5
Weight: 750 grams (1.65 lb.)
Width: 17.5mm (.689in.)
H - Auxiliary Switch
Type/
No. of
Cat. No. Contacts
H10UM
H11UM
H12UM
H21UM
Contact
Type
1
2
3
3
1NO
1NO + 1NC
1NO + 2NC
2NO + 1NC
Standard Pack: 10
Weight: 450 grams (0.99 lb.)
Width: 9mm (.354in.)
Add-on Neutral Pole
Type/
Cat. No.
N63UM
Rating
0.3-63A/
480Y/277V
For further Busbar information please see our comprehensive
Altech Universal Power Distribution catalog.
Contact
Rating
Wire
Size
For Use
with:
10A / 220V AC
3A / 110V DC or pulsed
1A / 220V DC or pulsed
4mm2 (12 AWG)
V-EA, MA
Approvals
Approvals
Standard Pack: 5
Weight: 0.775kg (1.71lb.)
Width: 17.5mm (.689in.)
* Please consult Altech for other voltages and your 50Hz application needs.
20
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
Lock-out **
Cat. No. EASS
Cooling Spacer
Cat. No. 15.960
Prevent inadvertent
resetting of the V-EA or MA
during maintenance.
Fits 1/4” pad lock.
TEMPERATURE CORRECTION CURVE
Ambient Temperature and Adjacent Mounting/Loading Adjustment
(V-EA/MA Ambient Temperature - 25°C to 55°C, Storage Temperature -40°C to 70°C)
160
Calibration Temperature
150
140
130
110
80
* Cooling spacer (Part #15.960)
between each group of 3 poles
will eliminate these adjustments.
50
-40
-40
-30
-22
-20
-4
-10
14
0
32
10
50
pol
es
adj
ace
nt m
oun
ted
ma
or ximum
mo
re , 2 0 %
adj
ace off R
nt m C fo
oun r a t
ted otal
*
off
70
60
to 3
20
68
30
86
40
104
Ambient Temperature
50
122
60
140
70
158
10
pol
es
80
176
Altech UL508
up
90
40
Adjacent Mounting Temperature
Adjustment 3% of RC for every
additional pole above 3.
Maximum 20% off RC for a total
of 10 poles or more.*
%
100
20
Rated Current (%)
120
Ambient Temperature Adjustment
5% of RC for every 10°C (18°F).
90 (°C)
194 (°F)
** V-EA and MA can also be locked in the on and off position by simply using a common lead or meter seal, which gets fed through the hole in the handle and a
corresponding hole in the housing.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
21