Manual Motor Controllers

MA Three Phase
Adjustable Trip
Miniature Circuit Breakers/
Manual Motor Controllers
The MA was designed to handle the high
inrush loads of 3 phase transformers, power
supplies, motors, etc. The MA protects wiring
and equipment from damage caused by the
three major classes of over-current, yet
greatly reduces the number of nuisance trips
in high starting and inrush current circuits.
An IEC device with excellent ratings under a
UL listing at 480Y/277V (including group
ratings) and at 500V under international
standards, the Altech/ Sursum MA provides
short and long term cost effective circuit
protection for USA and/or export
applications. The short term advantages
include: (1) adjustable thermal trip allows
finalization of initial designs before
procurement of the load equipment is
complete; (2) snap-on mounting for readily
available, internationally standardized DIN
Rail saves panel layout design time as well
as installation and change labor; (3) large
cage-clamp terminals with screws suitable to
power screwdrivers, simplifies and speeds
wiring; (4) convenient switched disconnect
during factory testing and/or initial start-up
saves time and aggravation. The key long
term advantage is customer satisfaction and
proven over-current protection of wiring and
equipment (and the lack of rework/repair
costs).
Type and
Rated
Current
UL508 listed
CAN/CSA-C22.2 No.14 certified
Type Designation
MA
__
(a)
__
(b)
__
(c)
RT
__
(d)
(a) = MA - Manual Motor Controller
(b) = Rated Current
(c) = U - US Housing
(d) = Blank - Standard Terminal
RT - Ring-tongue Terminal
Voltage Rating
480Y/277VAC
AIC (Interrupt Capacity)
0.16A-2.5A: 42kA; 4.0A-16A: 14kA; 20A-40A: 10kA
Standard Short Circuit Withstand Rating 0.16A-2.5A: 42kA; 4.0A-16A: 14kA
(UL/CSA Ratings)
Group Short Circuit Ratings
(UL/CSA Ratings)
see above
Typical Life
6000 on/off operations with 2xRC
Calibration Temperature
25°C, +0°, -5° (77°F, +0° -9°)
Standard Pack and Weight
1/450g (1.0 lb.)
Terminal Size Acceptability
Top/Bottom: 18-3 AWG
Cat. No.
FLA Dial
Adjustment
Markings
MA0.16U
15.901U
0.1/ 0.12/0.14/0.16
MA0.25U
15.902U
0.16/0.19/0.22/0.25
MA0.40U
15.903U
0.25/0.30/0.35/0.40
MA0.63U
15.904U
0.40/0.48/0.56/0.63
MA1.0U
15.905U
0.63/0.75/0.87/1.0
MA1.6U
15.906U
1.0/1.2/1.4/1.6
MA2.5U
15.907U
1.6//1.9/2.2/2.5
MA4.0U
15.908U
2.5/3.0/3.5/4.0
MA6.3U
15.909U
4.0/4.8/5.6/6.3
MA10U
15.910U
6.3/7.5/8.7/10
MA16U
15.911U
10/12/14/16
MA20U
15.912U
16/17/18.5/20
MA25U
15.913U
20/21.5/23/25
MA32U
15.914U
25/27/30/32
MA40U
15.915U
32/34/37/40
GROUP SHORT
CIRCUIT RATING
AT 480VACa
(and BCP size)
42kARMS
symmetrical
(max. 1200A
MCCB
or RK5)
14kARMS
symmetrical
(max. 350A
MCCB
or RK5)
10kARMS
symmetrical
(max. 350A
MCCB
or RK5)
3Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE
(See Note for HEA Definition)
110-120V
HP (HEA)
200V
HP (HEA)
208V
HP (HEA)
220-240V
HP (HEA)
460-480V
HP (HEA)
Through MA2.5U, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA’s general purpose
rated current (RC, equals maximum dial setting) and a locked
rotor current not exceeding 6 times the MA’s RC.
1/2 (4.0)
3/4 (3.2)
3/4
(3.1)
1
(3.6)
2
3/4 (5.6)
11/2 (6.0)
11/2
(5.7)
11/2
(5.2)
3
(4.8)
1
(7.2)
2
2
(7.5)
3
(9.6)
5
(7.6)
2
(13.6)
3 (11.0)
3
(10.6)
5
(15.2)
10
(14.0)
3
(19.2)
5 (17.5)
5
(16.7)
5
(15.2)
10
(14.0)
3
(19.2)
5 (17.5)
71/2
(24.2)
71/2
(22.0)
15
(21.0)
5
(30.4)
71/2 (25.0)
71/2
(24.2)
10
(28.0)
20
(27.0)
5
(30.4)
10 (32.0)
10
(31.0)
10
(28.0)
25
(34.0)
(7.8)
(3.42)
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as
NFPA-70 Tables 430-148, 430-149, 430-150; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc.
Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.
a The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher
standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
26
DIMENSIONS
TRIP CHARACTERISTICS MA/U
120
44mm (1.73 in.)
60
40
37.5mm (1.48 in.)
20
25.5mm (1.0 in.)
10
Tripping time t
Minutes
7mm
(.28 in.)
6
4
2
1
40
20
10
45mm (1.77 in.)
35mm (1.38 in.)
6
4
2
1
Seconds
45mm (1.77 in.)
89.5mm (3.52 in.)
6mm (.24 in.)
MA0.16U-MA16U
MA 3 Phase Controller
Thermal Overload (B, C, D)
“Must Trip” Current = 115% of Dial Setting
“Must Not Trip” > 1 hr = 105% of Dial Setting
0.6
0.4
Magnetic Trip
Nominal 1100% of Rated Current
0.2
0.1
7mm (.28 in.)
1 1.15 1.5
2 2.3 3
4 5 6 6.9 8 10 12
16 19
Multiple of Dial Setting (Thermal)
Multiple of Rated Current (Magnetic Trip)
Rated Current = Max. Dial Setting
17.5mm (1.28 in.)
120
30.5mm
(1.20 in.)
3mm
(.12 in.)
60
40
44mm (1.73 in.)
20
68mm (2.68 in.)
MA20U-MA40U
MA 3 Phase Controller
Thermal Overload (B, C, D)
“Must Trip” Current = 115% of Dial Setting
“Must Not Trip” > 1 hr = 105% of Dial Setting
1
3
L2
L1
5
L3
Tripping time t
Minutes
10
6
4
2
1
40
20
10
6
4
MA.16
VDE 0660 AC-3
500V
50-60Mz
12A
10A
14A
16A
40°C
20°C
2
1
T1
T2
2
Seconds
ABL SURSUM
T3
4
0.6
0.4
0.2
6
0.1
52.5mm (2.07 in.)
Magnetic Trip
Nominal 1100% of Rated Current
11.15 1.5
2 2.3
3
4
5 6 6.9 8 1012 15
12.5
Multiple of Dial Setting (Thermal)
Multiple of Rated Current (Magnetic Trip)
Rated Current = Max. Dial Setting
MA/USA Manual Motor Controller
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com