here - Chinfa

WRA240 SERIES
3PH AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧3 PHASE AC INPUT VOLTAGE
‧SELV COMPONENTS DESIGN
‧SHORT CIRCUIT PROTECTION
‧INTERNAL INPUT FILTER
‧OVER TEMPERATURE PROTECTION
‧PARALLEL FUNCTION AVAILABLE (SWITCH)
‧3 YEARS WARRANTY
R
R
H H
EN 61558-1
EN 61558-2-16
UL 60950-1
Class I, Div 2
IND. CONT. EQ.
UL 508
a
EN 60950-1
SELECTION CHART
WRA 240 - 24
24 : 24V OUT
Wattage
48 : 48V OUT
MODEL LIST
INPUT
VOLTAGE
MODEL NO.
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
WRA240-24
3o 340~575 VAC
240 WATTS
+ 24 VDC
10 A
88%
90%
WRA240-48
3o 340~575 VAC
240 WATTS
+ 48 VDC
5A
89%
91%
max.
max.
unit
unit
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Conditions
Conditions
Characteristics
Switching frequency
Isolation voltage
Isolation resistance
Ambient temperature
Derating (see derating curve)
Storage temperature
Relative humidity
Temperature coefficient
MTBF
Altitude during operation
Dimension
Cooling
Installation position
Pollution degree
Vi nom, Io nom
Input-Output
Input-FG
Output-FG
Input-Output, @ 500VDC
Operating at Vi nom
Vi nom, from +61 to +71 oC
Non operational
Vi nom, Io nom
Vi nom, Io min
Bellcore Issue 6 @40 oC, GB
min.
min.
typ.
typ.
25
3,000 / 4,242
1,500 / 2,121
500 / 710
100
-40
KHz
VAC / VDC
VAC / VDC
VAC / VDC
MΩ
o
C
% / oC
o
C
% RH
% / oC
Hours
Hours
m
mm
+ 71
2.5
+ 85
95
± 0.03
-40
20
520,000
560,000
24V
48V
5,000
EN 60950-1
Screw terminal type
Free air convection
Vertical ( other direction may derating using )
L124 x W89 x D118.8
2
INPUT SPECIFICATIONS
Characteristics
Nominal voltage *1
Rated input voltage
Absolute input max. range
Input current
min.
Conditions
typ.
max.
unit
1o or 3 o 380 / 480 VAC
Io nom
Ta min ... Ta max,
Io nom
Vi : 400 / 500 VAC, Io nom
AC in
DC in
400
340
480
500
575
820
0.65 / 0.55
VAC
VAC
VDC
A
*1. Single phase input is permissible, but output load is derated to 75%
www.chinfa.com
2014.08.11
[email protected]
P1
WRA240 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Conditions
Rated input current
Vi : 340 VAC, Io nom
Line frequency
Vi nom, Io nom
Inrush current
Power dissipation
Vi nom, Io nom
Vi : 400 VAC, Io nom
Leakage current
Input-Output
min.
typ.
max.
47
24V model
20
30
48V model
24
Vi nom, Io nom
A
63
Hz
25
A
W
W
0.25
mA
3.5
mA
max.
unit
+1
%
Input-FG
Power factor (Passive)
unit
0.85
0.55
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
0
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
Vi nom, Io min ...Io nom
0
Load regulation
%
single mode
±1
%
parallel mode
±5
28.5
VDC
Vi nom,
0.8 Io nom
24V model
22.5
48V model
47
Rated continuous loading
Vi nom
24V model
Hold up time
Vi nom , Io nom
Turn on time
Vi nom, Io nom
Vi nom, Io nom
%
VDC
56
10 A @ 24Vdc / 8.4 A @ 28.5Vdc
5 A @ 48Vdc / 4.2 A @ 56Vdc
48V model
Vi nom, Io nom
Vi nom, Io nom
%
±1
Voltage trim range
Rise time
typ.
ms
20
with 7000 μF CAP
1,000
ms
1,500
ms
150
ms
500
ms
with 7000 μF CAP
Fall time
Transient recovery time
Vi nom, Io nom
150
ms
Vi nom, 1~0.5 Io nom
Ripple & noise
Vi nom, Io nom, BW = 20MHz
2
100
mV
Power back immunity
Vi nom, Io nom
24V model
35
48V model
63
VDC
7,000
VDC
μF
17.6
19.4
VDC
37
43
VDC
24V model
17.6
19.4
VDC
48V model
37
43
Capacitor load
Vi nom, Io nom
24V model
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
24V model
48V model
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
Parallel operation
0.1 Io min ~ 0.9 Io max
Vi nom, Io nom, Po / Pi
Efficiency
ms
VDC
unit
2
Up to 91%, See model list and typ efficiency curve
CONTROL AND PROTECTION
Characteristics
min.
Conditions
Input fuse
Internal surge voltage protection
Rated over load protection
Power Rdy
(for 24V model only)
typ.
max.
Varistor
IEC 61000-4-5
Vi nom (see typ current limited curve)
120
140
%
Threshold voltage of contact closed(at start up)
17.6
19.4
VDC
Electrical isolation
500
VDC
Contact rating at 60VDC
Over voltage protection
Vi nom, 0.8 Io nom
(Auto Recovery)
Degree of protection
www.chinfa.com
2014.08.11
0.3
A
24V model
30
33
VDC
48V model
60
66
VDC
Output short circuit
Over temperature
unit
2 A / 600 VAC internal / phase
Hiccup mode
Detect on heat sink, shut down O/P
voltage, recovers automatically after
temperature goes down.
100
110
o
C
IP20
[email protected]
P2
WRA240 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1 Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1
EN 61558-1, EN 61558-2-16 (meet EN 60204-1)
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
CQC
GB4943.1, GB9254, GB17625.1
Vibration resistance
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
Screw terminal type 124 x 89 x 118.8 mm (4.88 x 3.5 x 4.68 inches)
Case material
Weight
Metal
1100g
1.18kg ; 16
Packing
/ 20kg / 2.01CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safeIy and
firmly on the rail.
111.90 [4.41]
6.90 [0.27]
9
10
124.00 [4.88]
IND.CONT.EQ.
E196362
2JF4
CHINFA
Chinfa Electronics ind. Co., Ltd.
ISO 9001 Certified
DC LO
DC ON
3PH 400-500VAC
0.85 A phase 47-63 Hz
L1
L2
L3
+ +
INSTALLATION
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
AWG24-10 (0.2~4mm2 ) flexible / solid cable,
-Input connector can withstand torque at
maximum 9 pound-inches.
-Output connector can withstand torque at
maximum 5.5 pound-inches.
8 m/m stripping at cable end recommends
Use copper conductors only, 60 / 75oC
WRA240
Rdy
GENERAL TOLERANCE
89.00 [3.50]
8 7 6 5
4321
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
120.00[4.72] - 400.00[15.75]
±0.80[0.03]
PIN ASSIGNMENT
Designation
PIN NO.
Description
Negative output terminal
V+
Positive output terminal
5
L3
Input terminals
6
7
L2
L1
Input terminals
IN
3, 4
OUT
V -
1, 2
10
OUT
9
www.chinfa.com
2014.08.11
Input terminals
Ground this terminal to minimize high-frequency emissions
8
OTHER
DIN Rail Mountable
Power supply
106.50 [4.20]
RDY
A normal open relay contact for DC ON level control
(Never connect except 24V model)
DC ON
Operation indicator LED
DC LO
Vout ADJ.
DC LOW voltage indicator LED
S/P
Single / Parallel select switch
Trimmer-potentiometer for Vout adjustment
[email protected]
P3
WRA240 SERIES
CIRCUIT SCHEMATIC
‧Block diagram for WRA240 series
L1
Fuse1
L2
Fuse2
L3
Fuse3
Vo +
X
Filter
X
X
Bridge
Rectifier
Filter
PFC
Circuit
Switching
Rectifier
Device
PWM
Controller
Y
Current
Detection
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vo Single / Parallel
Select
Vout
ADJ.
DC ON
(Green LED)
DC LOW
(Red LED)
RDY 1)
(Relay Contact)
Output
Level
Detection
Note: 1) For 24V Model Only
TYP. CURRENT LIMITED CURVE
WRA240-24 / 500Vac
100
75
Hiccup mode
50
25
Output Voltage [ % ]
Output Voltage [ % ]
WRA240-24 / 400Vac
100
0
75
Hiccup mode
50
25
0
110
120
130
140
150
160
170
110
120
Output Current [ % ]
130
140
150
160
170
Output Current [ % ]
DERATING CURVE
TYP. EFFICIENCY CURVE
WRA240-24
95
EFFICIENCY [ % ]
Power out [ % ]
100
75
Safe Operating Area
0
-40
www.chinfa.com
2014.08.11
90
85
80
500 Vac
400 Vac
75
70
61
Temperature [ oC ]
71
10
25
50
75
100
Power out [ % ]
[email protected]
P4