Click Here to download this file: /data/acdcsupplies/cps_s1u-3x.pdf

*LAST TIME BUY: 9/30/2016. CLICK HERE FOR OBSOLESCENCE NOTICE OF 3/31/2016.
S1U-3X
www.murata-ps.com
1U 19 inch Power Shelf for D1U Power Supplies
SELECTION GUIDE
Part Number
Description
S1U-3X-16-A-12-RC
S1U-3X-16-A-48-RC
Power shelf for 12V D1U
Power shelf for 48V D1U
OUTPUT AND PROTECTION CHARACTERISTICS
FEATURES
n
RoHS compliant
n
1U height, 18.3” width, 16” depth powershelf
n
Holds 3 D1U series power supplies
n
Hot insertion / removal
Standby output Main output
set point
set point
Parameter
Output total regulation
Please Refer to Appropriate D1U Datasheet on www.murata-ps.com
Output ripple voltage & noise
12V 1200W: CPS_D1U-W-1200-12.pdf
Output current operating range
12V 1600W: CPS_D1U-W-1600-12.pdf
Output total regulation
48V 1200W: CPS_D1U-W-1200-48.pdf
Efficiency
D1U Family Part Numbering
Start-up time
D1U-W-1200-12-HA1C
Transient response main output
n
Lug DC output connection for 2 AWG cables
Transient response standby output
n
I2C interface
Current sharing accuracy
(up to 3 in parallel with 5A total
minimum current)
n
Optional shelf to shelf signal connector (up
to 2 shelves in parallel)
48V 2000W: CPS_D1U-W-2000-48.pdf
Output current operating range
n
Blind-docking connection
n
Signal connector
48V 1600W: CPS_D1U-W-1600-48.pdf
Output ripple voltage & noise
D = Distributed
Power
C = RoHS compliant
1U = 1U
1 = Airflow front to back,
2 = Airflow back to front
Standby Output Voltage
A=5V, B=12V, C=3.3V,
0=no standby
W = Wide AC input
Hold-up time
Over-temperature (Auto-restart)
Over voltage main output (Latching)
DESCRIPTION
Over voltage standby output (Latching)
The S1U-X3 is a 1U x 19” EIA Rack Mount Power
Shelf designed for holding three 12V or 48V D1U
Front End Power Supplies in current sharing
applications. It is intended for distributed power
architecture applications in the Servers, Storage
Networking and Data Communications markets. There
are two lug terminal connections for #2 AWG cabling
for the DC output. System connection through the
I2C bus reports the performance status of the power
supplies within the power shelf. Two Power Shelves
can operate in parallel by an optional Shelf-to-Shelf
cable, doubling the power output to the maximum
capability of 9.6kW for two 12V power shelves or
12kW for two 48V power shelves.
Over current main output (Latching)
1200 = 1200 Watts
1600 = 1600 Watts
2000 = 2000 Watts (only
H = Hotplug connector
available in 48V output model)
12 = Main output 12V
48 = Main output 48V
Over current standby output (Latching)
EMISSIONS & IMMUNITY (with power supplies inserted)1
Conditions
Description
Harmonics
Voltage fluctuation & flicker
Emission conducted
Emission radiated
IEC/EN 61000-3-2
IEC/EN 61000-3-3
FCC 47 CFR Parts 15 / CISPR 22 / EN 55022
FCC 47 CFR Parts 15 / CISPR 22 / EN 55022
ESD
IEC/EN 61000-4-2
Electromagnetic field
Electrical fast transients/burst
Surge
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
RF Conducted immunity
IEC/EN 61000-4-6
Magnetic immunity
Voltage dips, interruptions
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Criteria
Class A, 6dB margin
Class A, 6dB margin
4kV contact discharge
8kV operational air discharge
15kV non-operational air discharge
1kV/2kV, performance criteria B
3 Vac, 80% AM, 1kHz,
Performance criteria A
3A/m
SAFETY
For full details go to
www.murata-ps.com/rohs
Parameter
Condition
Agency approvals
Material flammability
c-CSA-us (CSA 60950-1-03/UL 60950-1,first edition)
UL 94V-0
1 Product is designed to meet the referenced standards.
www.murata-ps.com/support
CPS_S1U-3X.D01 Page 1 of 4
S1U-3X
1U 19 inch Power Shelf for D1U Power Supplies
GENERAL CHARACTERISTICS
Parameter
Conditions
Min.
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Shock
Sinusoidal Vibration
Non-condensing
-40
0
10
5
Non-condensing
30G non operating
0.5G, 5 – 500 Hz
Calculated per Bellcore at Ta=30°C
Demonstrated
MTBF
Typ.
Max.
70
50
90
90
200
200
Units
°C
%
x105 hrs
x105 hrs
CONNECTOR TO CUSTOMER SYSTEM
Signal Connector: MOLEX # 39-28-5204 OR TYCO # 281282-1
Pin Assignment
Signal Name
Description
High Level
Low Level
I Max
1
AC_OK11
Input AC Voltage ‘OK’ signal output for the shelf
open drain
< 0.7V
- 2 mA
+ 4 mA
2
P_Good12
Power good signal output for the shelf
open drain
< 0.7V
- 2 mA
+ 4 mA
3
PS_On13
Power enable for the shelf
> 2.1V (open, or Vsb)
< 0.7V (active, PS:On)
- 1 mA
- 4 mA
4
NOT USED
5
AC_OK01
Input AC Voltage “OK” signal output for the shelf
open drain
< 0.7V
- 2 mA
+ 4 mA
6
P_Good02
Power good signal output for the shelf
open drain
< 0.7V
- 2 mA
+ 4 mA
7
PS_OnO3
Power enable for the shelf
> 2.1V (open, or Vsb)
< 0.7V (active, PS:On)
- 1 mA
- 4 mA
8
NOT USED
9
I2C Adr2
Address input 2
> 2.1V, < Vsb
< 0.8V
± 1 mA
10
11
12
13
14
15
16
17
18
19
20
I C Clock
I2C Data4
I_SHARE
SENSE +5
SENSE -5
Vsb
Vsb
Vsb
GND
GND
GND
I C serial clock bus
I2C serial data bus
Vsb
Vsb
2
4
2
Standby voltage output
Standby voltage output
Standby voltage output
GROUND
GROUND
GROUND
All control signals are with respect to Ground. Negative currents exit the power supply.
Signal goes low when any one of the three power supplies loses AC
Signal goes low when any one of the three power supplies fail
Pull this pin to GND to turn on three power supplies at the same time. Use I2C to turn on one power supply at a time.
4
Recomended 10KOhm pull up resistor to host 3.3 or 5V rail
5
Short Sense+ to +Vout and Sens- to GND at the point of load
1
2
3
www.murata-ps.com/support
CPS_S1U-3X.D01 Page 2 of 4
S1U-3X
1U 19 inch Power Shelf for D1U Power Supplies
SHELF TO SHELF CONNECTION
Signal Connector: MOLEX # 39-28-5164 OR TYCO # 281281-1
Pin Assignment
Signal Name
Description
High Level
Low Level
I Max
1
AC_OK11
Input AC Voltage ‘OK’ signal output for the shelf
open drain
< 0.7V
- 2 mA
+ 4 mA
2
P_Good12
Power good signal output for the shelf
open drain
< 0.7V
- 2 mA
+ 4 mA
3
PS_On13
Power enable for the shelf
> 2.1V (open, or Vsb)
< 0.7V (active, PS:On)
- 1 mA
- 4 mA
4
5
6
7
8
9
10
11
12
13
14
15
16
NOT USED
NOT USED
I2C Clock4
I2C Data4
I_SHARE
SENSE +5
SENSE -5
Vsb
Vsb
Vsb
GND
GND
GND
I2C serial clock bus
I2C serial data bus
Vsb
Vsb
Standby voltage output
Standby voltage output
Standby voltage output
GROUND
GROUND
GROUND
All control signals are with respect to Ground. Negative currents exit the power supply.
Signal goes low when any one of the three power supplies loses AC
Signal goes low when any one of the three power supplies fail
Pull this pin to GND to turn on three power supplies at the same time. Use I2C to turn on one power supply at a time.
4
Recomended 10KOhm pull up resistor to host 3.3 or 5V rail
5
Short Sense+ to +Vout and Sens- to GND at the point of load
1
2
3
OPTIONAL ACCESSORIES
Description
Murata-PS Part Number
Shelf to Shelf Cable
535-413-1537-1
www.murata-ps.com/support
CPS_S1U-3X.D01 Page 3 of 4
S1U-3X
1U 19 inch Power Shelf for D1U Power Supplies
MECHANICAL DIMENSIONS
1.252
(31.80)
15.937
(404.80)
17.315
(439.80)
1.709
(43.40)
0.228
(5.80)
18.307
(465.00)
18.992
(482.40)
NOTES:
1. The DC output terminals are of terminal block style that will allow connection using crimp
type right-angle lugs accepting up to AWG#2 wire, Panduit lug LCC2-14AWF-Q or equivalent is
recommended.
2. Two M6 studs at 15.88 mm centre spacing are provided for connection to each pole. Hardware is
provided for fastening the lugs/wires as well as terminal block covers
PRODUCT LABEL INFORMATION
S1U-3X-16-A-xx-RC v
v = factory control character
(not required for ordering)
S = Shelf
1U =1U height
3X = 3 unit per shelf
16 = 16” depth
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
C = RoHS
R = Reserve
xx = 12V
xx = 48V
A = AC input
D = DC input
This product is subject to the following operating requirements
and the Life and Safety Critical Application Sales Policy:
Refer to: http://www.murata-ps.com/requirements/
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
notice. © 2016 Murata Power Solutions, Inc.
www.murata-ps.com/support
CPS_S1U-3X.D01 Page 4 of 4