(13) SCHEDULE (14) to EC-Type Examination Certificate DEKRA 11ATEX0039 X (15) Description Issue No. 1 The Magnetostrictive Level Transmitter Jupiter Model 2..-E…-…..-… is used for level detection. Using the principle of magnetostriction and the effect of a magnetic field on the magnetostrictive wire, a fluid level is converted into a 4 - 20 mA current signal with Hart communication or into a digital fieldbus signal. The maximum probe length is 9,75 m. The transmitter enclosure provides a degree of protection IP66 as per EN 60529. Ambient temperature range -40 °C to +70 °C. Electrical data Level Transmitter Jupiter Model 24.-E…-…..-… and Model 26.-E…-…..-… and Model 27.-E…-…..-…: Output/supply circuit (terminals + and -): in type of protection intrinsic safety Ex ia IIC, only for connection to a certified intrinsically safe circuit, with the following maximum values: Ui = 28,4 V; Ii = 120 mA; Pi = 0,84 W; Ci = 2,2 nF; Li = 3 µH. Level Transmitter Jupiter Model 25.-E…-…..-… and Model 28.-E…-…..-…: Output/supply circuit (terminals + and -): in type of protection intrinsic safety Ex ia IIC, suitable for connection to a FISCO fieldbus system in accordance with EN 60079-27, with the following maximum values: Ui = 17,5 V; Ii = 380 mA; Pi = 5,32 W; Ci = 3 nF; Li = 3 µH. or in type of protection intrinsic safety Ex ia IIC, only for connection to a certified intrinsically safe circuit, with the following maximum values: Ui = 28,4 V; Ii = 120 mA; Pi = 0,84 W; Ci = 3 nF; Li = 3 µH. (16) Test Report NL/KEM/ExTR08.0014/**. (17) Special conditions for safe use Because the enclosure of the Magnetostrictive Level Transmitter Jupiter Model 2.1-E…-…..-… or Model 2.2-E…-…..-… is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded. Page 2/3 Form 100 Version 1 (2010-12) (13) SCHEDULE (14) to EC-Type Examination Certificate DEKRA 11ATEX0039 X (18) Essential Health and Safety Requirements Issue No. 1 Covered by the standards listed at (9). (19) Test documentation As listed in Test Report NL/KEM/ExTR08.0014/**. Page 3/3 Form 100 Version 1 (2010-12)