AC-DC Three Phase Power Converter
PRODUCT OVERVIEW
The D2U5T-H3-7000-54-HU4C is a High Efficiency 3500/7000 watt, power factor corrected, three phase power
converter for 230/480VAC lines with a 54VDC main output and a 5V or 3.3V (20W) selectable standby output. The unit is
provided with droop sharing and up to three supplies may be operated in parallel.
The supply is hot pluggable. It recovers from over temperature faults, and has status LEDs on the front panel in addition
to logic and PMBus status signals.
The 2U package and 23.1W/cubic inch power density make them ideal for delivering reliable, efficient power to servers,
workstations, storage systems, broadcast transmitters and many other applications.
ORDERING GUIDE
Model Number
D2U5T-H3-7000-54-HU4C
Power Output
at 480Vac
Main Output
Standby Output
Airflow
7000W
54V
3.3V or 5V
(selectable)
Back to front
FEATURES

7KW (480VAC), 3.5KW (230VAC) Output Power

High Efficiency; 96% @ 50% FL

54VDC Main Output

3.3V or 5V Standby Output

Dims: 5.1"(W) x 18"(L) x 3.3" (2U)

23.1 watts/cubic inch power density
INPUT CHARACTERISTICS
Parameter
Input Frequency
Input Voltage Operating Range
Turn-on Voltage (Ramp-up)

N+1 redundant (including hot docking)
Turn-off Voltage (Ramp-down)

Droop sharing on Main Output
Maximum Input Current
Inrush Current

Over-voltage, over-current, over-temperature
protections

Internal cooling fan
Power Factor, Range 1, 230Vac, 60Hz

I2C Bus Interface with status indicators

RoHS compliant
Power Factor, Range 2, 480Vac, 60Hz

Two-year warranty
Conditions
Range 1
Range 2
Range 1
Range 2
Range 1
Range 2
Min
47
180
320
Typ
50/60
Max
63
264
525
30
Units
Hz
Vac
Vac
Vac
Vac
Vac
Vac
Arms
Apk
Max
Units
176
280
150
260
15
Cold Start
600W
1750W (50% FL)
3500W (100% FL)
600W, 480Vac
3500W (50% FL)
7000W (100% FL)
0.930
0.990
0.995
0.850
0.990
0.995
OVERALL CHARACTERISTICS
Parameter
Conditions
Output Power
Efficiency, Range 1
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Efficiency, Range 2*
Min
Typ
Range 1
3500
Range 2
7000
700W (20%), 230 Vac
89.0
1750W (50%), 230 Vac
93.5
3500W (100%), 230 Vac
94.0
1400W (20%), 480 Vac
94.2
3500W (50%), 480 Vac
96.0
7000W (100%), 480 Vac
95.5
W
%
* See graph on page 8.
Available now at
www.murata-ps.com/en/3d/acdc.html
For full details go to
www.murata-ps.com/rohs
CB
Test Certificate
and Test Report
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 1 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
OUTPUT VOLTAGE CHARACTERISTICS
Output
Parameter
Conditions
Range 1
Range 2
@32.4A Range 1
@64.8A Range 2
Min to Max Current, Range 1
Min to Max Current, Range 2
Output Current
Voltage Set Point
54V
3.3VSB
5VSB
Voltage Droop
Line Regulation
Ripple Voltage & Noise1
Load Capacitance
Voltage Set Point
Line and Load Regulation
Ripple Voltage & Noise2
Output Current
Load Capacitance
Voltage Set Point
Line and Load Regulation
Ripple Voltage & Noise2
Output Current
Load Capacitance
Min
0
0
Typ
Max
64.8
129.6
54
54
1. 5V
3.0V
0.1
0.5
470
5000
3.46
100
6
1000
20MHz Bandwidth
0
20
5.00
4.76
5.24
100
4
1000
20MHz Bandwidth
0
20
Adc
Vdc
3.30
3.14
Units
%
Vp-p
μF
Vdc
mVp-p
A
μF
Vdc
mVp-p
A
μF
1 Ripple and noise are measured with 2.2μF (X7R 100V) ceramic + 180μF (UCC EKY) of electrolytic de-coupling capacitors at the output connector load side. A short coaxial cable
with 50Ω scope termination is used.
2 Ripple and noise are measured with 0.1μF of ceramic capacitance and 10 μF of tantalum capacitance across the power supply outputs at the output connector load side. A short
coaxial cable with 50Ω scope termination is used.
C1
2.2μF X7R 100V
T1
+
COAX
+
C2
180μF 63V UCC EKY
54V Output
RG587U
R1
50Ω
SCOPE
R2
50Ω
SCOPE
–
T2
+
COAX
RG587U
+
VSB
–
C3
100NF X7R 25V
OUTPUT CHARACTERISTICS
Parameter
Startup Time
Transient Response3
Current sharing accuracy (up to 3 in parallel)
Hot Swap Transients
Holdup Time
C4
10μF 10V TANT
Conditions
AC ramp up
54V, 50-100% load step, 0.1A/μs di/dt
5VSB, 50-100% load step, 1A/μs di/dt
3.3VSB, 50-100% load step, 1A/μs di/dt
54V @100% load
All outputs within regulation
54V @100% load
VSB @100% Load
Min
Typ
Max
3
2.4
250
250
+/-10
12
100
Units
s
Vp-p
mVp-p
mVp-p
%
ms
3 Minimum output capacitance to be 470μF (low ESR).
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 2 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
GENERAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (without de-rating at 40°C)
Altitude (without de-rating at 50°C)
Shock
Sinusoidal Vibration
MTBF
Weight
Safety Approvals
Input Fuses
Material Flammability
Airflow Direction
PROTECTION CHARACTERISTICS
Output
Parameter
Over-temperature (intake)
Over Voltage
54V
Over Current Ranges 1 &2
Over Voltage
3.3VSB
Over Current
Over Voltage
5VSB
Over Current
Conditions
Min
-40
0
10
5
Non-condensing
Non-condensing
3000
1800
30G non-operating
0.5G, 5 – 500 Hz
Calculated per Telcordia SR-332 @40°C
Typ
Max
70
50
90
90
Units
°C
°C
%
%
m
250K
hrs
kg
7
c-CSA-us (CSA 60950-1-07/UL 60950-1, Second Edition)
TÜV EN 60950-1:2006+A11+A1+A12
IEC 60950-1:2005 (2nd Ed) + A1:2009, and
EN 60950-1:2006/A11:2009/A1:2010/A12:2011
One internal 16A/500V fast blow fuse on each of the three AC line inputs
UL 94V0
From Back (connector side) to Front. Optional Front to Back.
Conditions
Auto-restart
Latching, toggling ON/OFF switch unlatches
Hiccup mode. Restart every 500msec. Recovers once load drops below OCP level
Latching, AC OFF/ON cycling required to unlatch
Constant Current Limit (Latches if Output drops below 2V). Hiccup is optional
Latching, AC OFF/ON cycling required to unlatch
Constant Current Limit (Latches if Output drops below 3V). Hiccup is optional
Min
52
58
105
3.9
6.3
5.6
4.2
Typ
55
60
Max
63
62
130
4.3
9
6.0
6
Units
°C
V
%
V
A
V
A
EMISSIONS AND IMMUNITY
Characteristic
Standard
Input Current Harmonics
IEC/EN 61000-3-2
Complies
Radiated Emissions (in the application)
FCC 47 CFR Parts 15
CISPR 22 EN55022
Class A, 6dB margin
ESD Immunity
IEC/EN 61000-4-2
Level 3 criteria A
Radiated Field Immunity
IEC/EN 61000-4-3
Level 3 criteria B
Electrical Fast Transients/Burst Immunity
IEC/EN 61000-4-4
Level 3 criteria A
Surge Immunity
IEC/EN 61000-4-5
Level 3 criteria A
RF Conducted Immunity
IEC/EN 61000-4-6
Level 3 criteria A
Magnetic Field Immunity
IEC/EN 61000-4-8
3 A/m criteria B
IEC/EN 61000-4-11
400Vrms Input Voltage
54V & VSB Outputs, Performance a)
100% load, Phase 0°, Dip 100% Duration 10ms
50% load, Phase 0°, Dip 100% Duration 20ms
54V & VSB Outputs, Performance b)
100% load, Phase 0°, Dip 100% Duration >10ms
Any Load, Phase 0°, Dip 100% Duration >100ms
Any valid Input Voltage, any load
54V & VSB Outputs, Performance a)
Dip 30% on single Phase or Line, Duration 100ms
54V & VSB Outputs, Performance b)
Dip 30% on single Phase or Line, Duration >100ms
Conducted Emissions
Voltage Dips & Interruptions
Voltage imbalance
(Circuit will stop when input voltage imbalance exceeds 8% for more
than 100ms. Unit will restart when imbalance returns below 8%)
Compliance
Class A, 6dB margin
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 3 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating/Test Voltage
Conditions
Min
Input to Output – Reinforced
3000
Typ
Max
Vrms
Units
Input to Chassis – Basic
1500
Vrms
Output to Chassis – Functional
500
Vdc
STATUS INDICATORS (LEDs)
Status Indicators
Input OK (Green)
Output OK (Green)
Fault5 (Yellow)
AC present and within the regulation range;
Standby - ON; Main Output – OFF
Solid Green
Blinking
Off
Off
Off
Off
Off
Off
Off
Off
Solid Green
Solid Green
Off
Solid Green
Solid Green
On
No Change
No Change
Blinking 1Hz
Blinking Green at 1Hz rate
(0.5s on, 0.5s off)
Blinking Green at 1Hz rate
(0.5s on, 0.5s off)
AC present, but its level is not within the required regulation range
When hot-unplugging the power supply from a power shelf4
AC input voltage is not present
AC present and within the regulation range;
Standby – ON, Main Output – ON and both within the regulation range
AC present and within the regulation range;
Standby - ON; Main Output - ON; power supply is in a power limit or in an overcurrent condition.
Any warning Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN)
Any Fault Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN)
Depends on PS Status
Depends on PS Status On
4 The Input OK LED blinks to indicate that there is still energy inside the power supply until the input bulk capacitors are completely discharged or the housekeeping circuit is shut
down.
5 The Fault LED and PS Fault signal shall be turned on to indicate that there is one or more of the following internal faults currently detected inside the power supply:
• VSB out of range
• Output stage OT
• Fan fault
• ORING fault (Output voltage less than bus voltage)
• OC shutdown
• OT shutdown
• OV shutdown
• Input stage OT
• Fault induced shutdown occurred
• Thermal sensor fault
• Vout out of range
• PFC Boost Vbulk fault
As soon as all of the above faults are removed and the power supply operates normally, the Fault LED and PS Fault signal shall be turned off.
LED Definition: Three LEDs shall be located on the front faceplate, and these are:
LED
Status
Input OK = ON
Output OK = ON
Fault = ON
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 4 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
Control Signals
Signal (I/O)
Description
PS_ON_H (Input)
Internal 10K pull-up resistor to internal VDD6
• Leaving signal pin open = Main Output ON
• Tying signal pin to GND = Main Output OFF
PS_KILL (Input)
Short pin; internal 10K pull-up resistor to internal VDD6
• Leaving signal pin open = All Outputs off
• Tying signal pin to GND = All Outputs enabled
Internal 10K pull-up resistor to internal VDD6
• PSU Fault Status
Internal 10K pull-up resistor to internal VDD6
• Main Output Status OK
PS_FAULT_L (Output)
PWR_GOOD_H (Output)
I_SHARE (Input/output -bus)
Analog representation of main output current; can be left open if not used
STBY_SEL_IN (Input)
Internal 10K pull-up resistor to internal VDD6
• Leaving signal pin open = +5V STBY
• Tying signal pin to GND = 3V3STBY
Internal 10K pull-up resistor to internal VDD6
• AC OK Status
Internal 10K pull-up resistor to internal VDD6
SMB_ALERT_L (Output)
• SMB Alert signal output
6 VDD depends on Standby Voltage selection of either 3.3V or 5V.
AC_OK_H (Output)
AC POWER CONNECTOR
Header
Positronic PLS5W5F1000
Position
Part Number
1
Positronic: FS612N2
2
Positronic: FS612N2
Contacts
3
4
Positronic: FS612N2
5
Positronic: FS612N2
Function
Safety Ground
AC Line Voltage Ph 1
Not fitted
AC Line Voltage Ph 2
AC Line Voltage Ph 3
1.795
[45.59]
1
2
3
0.802
[20.36]
4
5
0.401
[10.18]
2X Ø0.100 [Ø2.54] THRU
1.295
[32.89]
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 5 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
CUSTOMER AC POWER CONNECTOR
Header
Positronic PLS5W5M1000
Position
Part Number
Function
1
Positronic: MS612N
Safety Ground
2
Positronic: MS612N-228.2
AC Line Voltage Ph 1
3
Not
fitted
Contacts
4
Positronic: MS612N-228.2
AC Line Voltage Ph 2
5
Positronic: MS612N-228.2
AC Line Voltage Ph 3
NOTE: The Safety Ground MUST mate first. The Customer SHALL use the longer pin
specified for position 1 and the shorter pins specified for positions 2, 4 and 5.
1.795±0.020
[45.59±0.51]
3
2 1
5
0.802
[20.36]
4
0.401
[10.18]
2X Ø0.100 [Ø2.54] THRU
1.295
[32.89]
OUTPUT CONNECTOR
Connector: FCI Power Blade. Right Angle Header, 24 Signal Pins & 12 Power Blades. Part # 51939-486LF
Mating connector option #1: FCI Power Blade. Right Angle Connector, 24 Signal Pins & 12 Power Blades.
Part # 51915-132
Mating connector option #2: FCI Power Blade. Straight Connector, 24 Signal Pins & 12 Power Blades.
Part # 51940-323
ROWS
POWER
E1
D
C
B
A
SIGNAL
P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12
PA
1
2
3
4
5
6
E2
UUUUHH
T T T GG
PA T
SSSSFF
RRRRE E
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 6 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
OUTPUT CONNECTOR & SIGNAL PIN ASSIGNMENT
Connector: FCI Power Blade Part # 51939-486LF
Power Blade Number
P12
A2
A3
A4
A5
A6
B1
B2
B3
B4
Signal
+VOUT
+VOUT
+VOUT
-VOUT
-VOUT
-VOUT
-VOUT
-VOUT
-VOUT
+VOUT
+VOUT
+VOUT
Signal
A1
PS_FAULT_L
A0
VSB_RTN
SCL
VOUT_SENSE+
A2
PS_ON_H
+VSB
VSB_RTN
B5
PS_KILL
B6
C1
C2
C3
C4
C5
N/A
STBY_SEL_IN
AC_OK_H
+VSB
VSB_RTN
SDA
VOUT_SENSESMB_ALERT_L
PWR_GOOD_H
+VSB
VSB_RTN
VSB_RTN
VSB_RTN
P11
P10
P9
P8
P7
P6
P5
P4
P3
P2
P1
Signal Pin Number
A1
C6
D1
D2
D3
D4
D5
D6
Function
54Vdc
54Vdc
54Vdc
54Vdc Return
54Vdc Return
54Vdc Return
54Vdc Return
54Vdc Return
54Vdc Return
Signal Direction
Output
Output
Output
Output
Output
Output
Output
Output
54Vdc
Output
Output
54Vdc
54Vdc
Function
I2C Address Bit 1 Signal
PSU Fault Status
I2C Address Bit 0 Signal
VSTBY_RTN
I2C Clock Signal
VOUT_SENSE+
I2C Address Bit 2 Signal
Enable PSU
+3.3V/5V STBY Out
VSTBY_RTN
Enable PSU
Shortest pin of the connector
Reserved No User Connection
Selects +3V3 or +5VSTBY
AC(DC) OK Status
+3.3V/5V STBY Out
VSTBY_RTN
I2C Data Signal
VOUT_SENSESMB Alert signal output
Power OK Status
+3.3V/5V STBY Out
VSTBY_RTN
VSTBY_RTN
VSTBY_RTN
Output
Output
Signal Direction
Input
Output
Input
Output
Bi-Directional
Input
Input
Input
Output
Output
Input
Output
Input
Output
Output
Output
Bi-Directional
Input
Output
Output
Output
Output
Output
Output
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 7 of 8
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
MECHANICAL DIMENSIONS
Dimensions: 5.1" x 18"x 3.3" [129.5mm x 455.9mm x 84.5mm]
EFFICIENCY
97
96
Efficiency (%)
95
94
93
480VAC
92
91
90
0
10
20
30
40
50
60
70
80
90
100
Full Load (%)
OPTIONAL ACCESSORIES
Description
Part Number
54V D2U5T Output Connector Card
D2U5T-54-CONC
APPLICATION NOTES
Document Number
Description
Link
ACAN-55
D2U5T PMBusTM Communication Protocol
http://power.murata.com/datasheet?/data/apnotes/acan-55.pdf
ACAN-56
D2U5T Output Interface Connector Card
http://power.murata.com/datasheet?/data/apnotes/acan-56.pdf
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
This product is subject to the following operating requirements
and the Life and Safety Critical Application Sales Policy:
Refer to: http://www.murata-ps.com/requirements/
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
notice.
© 2015 Murata Power Solutions, Inc.
www.murata-ps.com/support
D2U5T-H3-7000-54-HU4C.A02 Page 8 of 8