www.murata-ps.com D1U86-D-1600-12-HxxDC Series 86mm 1U Front End DC-DC Power Supply Converter PRODUCT OVERVIEW The D1U86P-D-1600-12-HxxDC series are highly efficient 1600 watt, DC input front end supplies with a 12V main output and a 12V (30W) standby. They have current sharing and up to 8 supplies may be operated in parallel. The supplies may be hot plugged, they recover from overtemperature faults, and have logic and PMBus monitoring and control. Their low profile 1U package and >38.6W/cubic inch power density make them ideal for delivering reliable, efficient power to servers, workstations, storage systems and other 12V distributed power systems. ORDERING GUIDE Part Number FEATURES 1600W output power Power Output Main Output Standby Output1 Airflow 1600W 12Vdc 12Vdc Back to front Front to back D1U86P-D-1600-12-HB4DC D1U86P-D-1600-12-HB3DC 93% efficiency at half load 12V main output INPUT CHARACTERISTICS 12V standby output of 30W Parameter Input Voltage Operating Range Turn-on Voltage Turn-off Voltage Maximum Current at Vin = -40Vdc 1U height: 3.4" x 7.75" x 1.59" 38.6 Watts per cubic inch density N+1 redundancy, including hot plugging (up to 8 in parallel) Current sharing on 12V main output, ORing FET Overvoltage, overcurrent, overtemperature protection Internal cooling fan (variable speed) Conditions Min. -40 -43 -38.5 Ramp up Ramp down 1600W DC Line Inrush Peak Current Cold start between 0 to 200msec Efficiency (48V) 20% load 50% load 100% load Nom. -48 -43.5 -39 40 72 Max. -72 -44 -39.5 47 50 100 92 93 89 Units Vdc Vdc Adc Apk % OUTPUT VOLTAGE CHARACTERISTICS PMBus™ / I²C interface monitoring and control Output Voltage RoHS compliant 12V 12VSB 1 Parameter Conditions Min. Typ. Max. Units Voltage Set Point Line and Load Regulation Droop Ripple Voltage & Noise1 Output Current Load Capacitance Voltage Set Point Line and Load Regulation Droop Ripple Voltage & Noise1 Output Current Load Capacitance 50% load 12.17 11.4 12.20 12.23 12.6 Vdc 3.10 20MHz Bandwidth 50% load 0 0 11.97 11.4 12.0 120 133.3 10000 12.03 12.6 120 20MHz Bandwidth 0 0 120 2.5 350 mV/A mV p-p A μF Vdc mV/A mV p-p A μF Ripple and noise are measured with 0.1 μF of ceramic capacitance and 10 μF of tantalum capacitance on each of the power supply outputs. A short coaxial cable with 50Ω scope termination is used. www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html Available now at www.murata-ps.com/en/3d/acdc.html CB Test Certificate and Test Report For full details go to www.murata-ps.com/rohs www.murata-ps.com/support D1U86-D-1600-12-HxxDC.A01 Page 1 of 5 D1U86-D-1600-12-HxxDC Series 86mm 1U Front End DC-DC Power Supply Converter OUTPUT CHARACTERISTICS Parameter Output Rise Monotonicity Startup Time Transient Response Current sharing accuracy (up to 8 in parallel)2 Hot Swap Transients Holdup Time Conditions No voltage excursion DC ramp up 12V, 50% load step, 1.0A/μs di/dt 12VSB, 50% load step, 1.0A/μs di/dt At 100% load All outputs remain in regulation At full load (48V input) Min. Conditions Min. -40 0 5 5 3000 Typ. Max. Units 1.5 600 600 3 s mV ±5 5 % % ms Max. 85 55 90 95 Units 1 ENVIRONMENTAL CHARACTERISTICS Parameter Storage Temperature Range Operating Temperature Range Operating Humidity Storage Humidity Altitude (without derating at 45°C) Shock Operational Vibration MTBF 2 Noncondensing 30G non operating 1G, 10-500Hz, 1.6G (non-operational) Per Telcordia SR-322 M1C1@ 40°C Typ. °C % m 500K hrs Safety Approvals CSA/UL 60950-1-07-2nd Ed. IEC 60950-1:2005 (2nd Edition) w Am. 1:2009 CE Marking per LVD DIRECTIVE 2006/95/EC Input Fuse Weight Power Supply has internal 60A/170VDC fast blow fuse on the DC line input 1.108kg (2.44lbs) The load current of 100% refers to each power module max load connected in an N+1 configuration; therefore the total load will be “N” x 100% load of each module. The share accuracy of ±5% is a fixed percentage irrespective of the total loading and number of units connected in parallel. PROTECTION CHARACTERISTICS Output Voltage Parameter Conditions Min. An OTP warning will be issued via the PMBus interface when the air inlet exceeds 70°C; however the power module shall not shut down until critical internal hotspot temperatures are exceeded. The unit will shut down when internal hot spot exceed the derating guide lines and autoOvertemperature (hotspots) matically recovers when the unit is cooled down. The unit will shut down due to hot spot at ambient temperature between 55°C-60°C with main 12V at full load. Overvoltage Latching For overloads (slow) over current events a 147A nominal constant current will be sustained until the output voltage drops below 3VDC. At this point the unit shall shut down after a 1sec period and remain in that condition for 10secs. The cycle will then repeat. Overcurrent For severe (short circuit) over current events the unit shall shut down within 1ms and remain in this condition for 200ms before attempting a re-start. the unit shall attempt 10 shutdown/re-start cycles before permanently latching off. It will then be necessary to either recycle the DC input or toggle the PSON# input. Overvoltage Latching Overcurrent Autorecovery Overtemperature (intake) 12V 12VSB Typ. Max. Units 70 °C 55-60 13.2 14.4 137 154 13.2 2.75 TBD V 14.4 3.0 V A ISOLATION CHARACTERISTICS Parameter Insulation Safety Rating / Test Voltage Isolation Conditions Input to Output - Basic Input to Chassis - Basic Output to Chassis Min. 1500 1500 500 Typ. Max. Units Vdc Vdc Vdc www.murata-ps.com/support D1U86-D-1600-12-HxxDC.A01 Page 2 of 5 D1U86-D-1600-12-HxxDC Series 86mm 1U Front End DC-DC Power Supply Converter EMISSIONS AND IMMUNITY Characteristic Standard Compliance Conducted Emissions ESD Immunity Radiated Field Immunity Electrical Fast Transient Immunity Surge Immunity Radiated Field Conducted Immunity Magnetic Field Immunity FCC 47 CFR Part 15/CISPR 22/EN55022 IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/EN 61000-4-8 Class A, 6dB margin Level 3 criteria A Level 3 criteria B Level 3 criteria A Level 2 criteria B Level 3 criteria A 3 A/m criteria B STATUS INDICATORS AND CONTROL SIGNALS Signal Description PSON# Low = main output on; PSON# can be permanently tied to GND within the host system. Short pin pulled down on p/s; pulled up to either 3.3V or 12V (max) in the host system. For 3.3V use a 5.11KΩ resistor; for 12V use a 21KΩ resistor. Open drain PMBus signal; can be left open if not used. PMBus Address; ADDR can be grounded or left open if not used. If grounded, the address will be 000, if it is open, the default address will be 111. Analog representation of main output current; can be left open if not used. Three level signal based on DC input and DC output status; can be left open if not used. I2C clock I2C data Mode Operating Condition Input Turn-off DC Input is below minimum power-supply turn-on specification Standby Power supply standby output is operating within normal parameters and main output is disabled Power-good Power supply standby & main outputs are operating within normal parameters and delivering power Warning Warning condition in power supply has been detected Fault Fault condition in power supply has been detected. PRESENT# PS INTERRUPT ADDR ISHARE PSOK3 I2C CLOCK I2C DATA LED State 1. Off 2. Green – blinking 1Hz 3. Green – solid 4. Yellow – blinking 1Hz 5. Yellow – solid OUTPUT CONNECTOR AND SIGNAL SPECIFICATION Pin# 14-26, 39-51 1-13, 52-64 37 Function RTN 12V 12VSB Pin Type Power Ground Power Power 38 PSINTERRUPT Output 36 PRESENT# Input 35 PSOK3 Analog output 34 ISHARE Analog I/O 33 32 31 30 29 28 27 PSON# SCL SDA GND N/A N/A ADDR Input Input I/O Analog I/O N/A N/A Analog input Description Power and Standby Return 12V Output 12V Standby Output Active low; interrupt line for power supply fault & warning detection as per PMBus spec Power Supply Present Signal (shortest pin) Combination of there power supply output indicator signals: 1. DC input OK 2. Power Good 3. Power Supply Fault Analog representation of main output current. Typical analog voltage shall be 60.15mV/Amp of main output current. Power Supply on/off control signal SMBus/PMBus Clock SMBus/PMBus Data Power Supply Signal Ground Reserved; no User connection Reserved; no User connection PMBus Address Power Supply Output Card Edge 64 1 33 32 PCB Top Side PCB Bottom Side CONNECTOR AND SIGNAL SPECIFICATION3 PSOK TRUTH TABLE VS. ANALOG OUTPUT DC_OK_H 0 0 1 1 X PWR_GOOD_H 0 1 0 1 X PS_FAULT_L 1 1 1 1 0 PSOK < 0.1Vdc (1/3) VDD (2/3) VDD VDD 0.2-0.4Vdc VDD = 3.3Vdc OPERATION MODE No DC Input Invalid Standby Power Good PS Fault www.murata-ps.com/support D1U86-D-1600-12-HxxDC.A01 Page 3 of 5 D1U86-D-1600-12-HxxDC Series 86mm 1U Front End DC-DC Power Supply Converter WIRING DIAGRAM FOR OUTPUT 1-13, 52-64 1-13, 52-64 Main output load 14-26, 39-51 D1U86 RTN RTN 14-26, 39-51 12VSB 12VSB 37 37 33 PSON# PSON# 33 VSB load FET,BJT,wire or switch (debounced) to turn on 12V main output RTN D1U86 FET,BJT,wire or switch (debounced) to turn on 12V main output RTN CURRENT SHARING NOTES Main Output: Current share is achieved using the droop method. Nominal output voltage (12.20V) is achieved at 50% load and output voltage changes at a rate of 3.10mv per amp. Startup of parallel power supplies is not internally synchronized. If more than 1600W combined power is needed, start-up synchronization must be provided by using a common PS_ON signal. To account for ±5% full load current sharing accuracy and the reduction in full load output voltage due to droop, available output power must be derated by 10% when units are operated in parallel. Internal ORing FETs are provided. Standby output can be tied together for redundancy but total combined output power must not exceed 30W; Internal MOSFET ORing devices are used. www.murata-ps.com/support D1U86-D-1600-12-HxxDC.A01 Page 4 of 5 D1U86-D-1600-12-HxxDC Series 86mm 1U Front End DC-DC Power Supply Converter MECHANICAL DIMENSIONS 3.00 ±0.25 9.00 ±0.30 16.50 ±0.30 197.70 ±0.65 51.36 ±0.30 83.52 ±0.30 1.41 0.50 2X2.80 ±0.25 198.05 0.65 AIRFLOW FRONT TO BACK AIRFLOW BACK TO FRONT 6.80 ±0.40 39.90 ±0.50 4.20 ±0.40 40.50 REF 0.062" 9.56 ±0.25 41.90 86.40 ±0.60 8.00 ±0.30 3.30 ±0.25 230.41 REF 10.25 0.40 DC input connector: Terminal Block, Dinkle Enterprise: Part No. DT-7C-B14W-02 Dimensions: 3.4" x 7.75" x 1.59" [86mm x 196.85mm x 39.9mm] MATING CONNECTOR Part Number Description FCI 10053363-200LF FCI 10046971-008LF Right Angle Vertical OPTIONAL ACCESSORIES Description Part Number 12V D1U86P Output Connector Card D1U86P-12-CONC APPLICATION NOTES Document Number Description ACAN-50 D1U86P Output Connector Card ACAN-54 D1U86P Communication Protocol Murata Power Solutions, Inc. 11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A. ISO 9001 and 14001 REGISTERED This product is subject to the following operating requirements and the Life and Safety Critical Application Sales Policy: Refer to: http://www.murata-ps.com/requirements/ Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without notice. © 2015 Murata Power Solutions, Inc. www.murata-ps.com/support D1U86-D-1600-12-HxxDC.A01 Page 5 of 5