Ground-Fault & Insulation Monitor PGR-6101 PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-B-020614 Copyright © 2014 by Littelfuse, Inc. All rights reserved. Document Number: PM-1101-EN Printed in Canada. PGR-6101 Ground-Fault & Insulation Monitor This page intentionally left blank. Page i Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor TABLE OF CONTENTS SECTION LIST OF FIGURES PAGE General....................................................................... 1 Operation................................................................... 1 2.1 Output Relay Operating Mode................................... 1 2.2 PGR-6101 Operating Mode ....................................... 1 2.2.1 Online Operation ......................................... 1 2.2.2 Offline Operation ........................................ 1 2.3 Front-Panel Controls .................................................. 1 2.3.1 Ground-Fault Trip Level ............................. 1 2.3.2 Ground-Fault Trip Time ............................. 1 2.3.3 Insulation Resistance Response .................. 1 2.3.4 Reset............................................................. 1 2.3.5 Test............................................................... 2 2.4 Front-Panel Indication ................................................ 2 2.4.1 Power ........................................................... 2 2.4.2 >I ............................................................... 2 2.4.3 CT ............................................................... 2 2.4.4 Active........................................................... 2 2.4.5 <R................................................................. 2 2.5 Analog Outputs........................................................... 2 2.5.1 OUT I........................................................... 2 2.5.2 OUT R ......................................................... 2 2.6 Remote Test ................................................................ 2 2.7 Remote Reset .............................................................. 2 2.8 CT Verification........................................................... 2 3 Installation................................................................. 2 3.1 PGH-5000 and PGH-6000 ......................................... 4 4 Technical Specifications ........................................... 8 4.1 PGR-6101 ................................................................... 8 4.1.1 PGR-6101 Online Operation ...................... 8 4.1.2 PGR-6101 Offline Operation...................... 8 4.2 PGH High Tension Couplers ..................................... 9 5 Ordering Information .............................................. 9 6 Performance Tests .................................................. 10 6.1 Ground-Fault Test .................................................... 10 6.2 Insulation Test .......................................................... 11 Appendix A PGR-6101 Revision History ........................ 12 1 2 Page ii Rev. 0-B-020614 FIGURE 1 2 3 4 5 6 7 8 PAGE PGR-6101 Outline and Mounting Details ................. 3 Typical Connection Diagram ..................................... 4 PGC-5000-Series Current Sensors ............................ 5 PGH-5000 Outline and Mounting Details ................. 6 PGH-6000 Outline and Mounting Details ................. 7 PGA-0500 Analog Percent Current Meter ................ 9 PGA-0510 Analog Ohm Meter................................ 10 Ground-Fault-Test Circuit........................................ 11 LIST OF TABLES TABLE 1 PAGE Ground-Fault-Test Record ....................................... 11 DISCLAIMER Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. PGR-6101 Ground-Fault & Insulation Monitor This page intentionally left blank. Page iii Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor 1. GENERAL The PGR-6101 Ground-Fault & Insulation Monitor can detect a motor ground fault whether the motor is running (Online mode) or stopped (Offline mode), and can be used to protect a motor supplied by a solidly grounded, resistance-grounded, or ungrounded system. On an ungrounded system, use only the Offline mode. On grounded systems, a current transformer (CT) is used to detect ground-fault current as low as 30 mA when the motor is running, and insulation resistance is measured to detect a fault when the motor is stopped. Online or Offline mode is selected with a digital input connected to a starter auxiliary contact. In the Online mode, ground-fault current is sensed by a PGC-5000-series zero-sequence CT. The trip level of the ground-fault circuit is selectable from 30 to 200 mA. Trip time is selectable from <50 to 250 ms. Additional current-detection features include harmonic filtering, a relay output that can operate in the fail-safe or non-failsafe mode, CT-connection detection, LED trip, power, and open-CT indication, autoreset or latching trips with front-panel and remote reset, a test button, and a 0- to 1mA-analog output. In the Offline mode, insulation-resistance monitoring is enabled, with a selectable 60- to 600-k alarm-setting range. Additional insulation-monitoring features include a relay output that can operate in the fail-safe or non-failsafe mode, LED active and low-resistance indication, and a 0- to 1-mA-analog output. The PGR-6101 can be directly connected to a supply up to 1.3 kV. For systems from 1.3 to 5 kV, use a PGH-5000 High Tension Coupler. For systems from 5 kV to 6 kV, use a PGH-6000 High Tension Coupler. 2. OPERATION 2.1 OUTPUT RELAY OPERATING MODE In the fail-safe mode the output relays energize when power is applied and the ground-fault and insulationresistance circuits are not tripped. Fail-safe mode is the factory setting. For non-fail-safe operation connect terminals 19-20 and 22-23. The respective output relay will energize when a fault occurs. See Fig. 2. 2.2 PGR-6101 OPERATING MODE Connect terminals 27 and 28 to a normally closed (Form B) auxiliary starter contact. When terminals 27 and 28 are open, Online mode (insulation monitoring off) is selected and when terminals 27 and 28 are connected, Offline mode (insulation monitoring active) is selected. Page 1 Rev. 0-B-020614 2.2.1 ONLINE OPERATION When the monitor is running, the PGR-6101 in conjunction with a PGC-5000-series zero-sequence current sensor operates as a sensitive ground-fault relay. 2.2.2 OFFLINE OPERATION The PGR-6101 changes mode by means of an auxiliary contact on the main contactor when the motor is off. It becomes an insulation-resistance monitor and imposes a small dc voltage to the motor windings and supply cable from the motor starter. Leakage to ground is detected. 2.3 FRONT-PANEL CONTROLS 2.3.1 GROUND-FAULT TRIP LEVEL The Leakage Current I selector switch is used to set the ground-fault trip level from 30 to 200 mA. For groundfault detection, the switch setting must be set substantially below the prospective ground-fault current. To avoid sympathetic tripping, the switch setting must be above the charging current of the protected feeder. 2.3.2 GROUND-FAULT TRIP TIME The PGR-6101 has a definite-time trip characteristic. In tripping systems, the TIME DELAY selector is used to set the ground-fault trip time for coordination with upstream and downstream ground-fault devices. Trip time is selectable from < 50 ms to 250 ms. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault. 2.3.3 INSULATION RESISTANCE RESPONSE The PGR-6101 insulation resistance function has an adjustable alarm range of 60 to 600 k. There is no selectable time delay. The unit will operate in less than three seconds. 2.3.4 RESET The front-panel RESET button is used to reset latching trips. After a fault has been cleared, cycling the supply voltage will also reset the PGR-6101. To use the PGR-6101 in autoreset mode, connect terminals 18-19 and 21-22. See Fig. 2. The reset function is not instantaneous. Press the RESET button for several seconds. PGR-6101 Ground-Fault & Insulation Monitor Page 2 Rev. 0-B-020614 2.3.5 TEST The TEST button will test both leakage-current and insulation-resistance circuits regardless of the selected operating mode. Press the TEST button for at least eight seconds to complete test. All LED’s will light and relay contacts will change to fault/alarm state. In the default mode (latching), the tripped state will remain until reset. Allow eight seconds before operating the RESET push button. 2.7 REMOTE RESET For remote reset, connect a switch or pushbutton with a normally closed contact between the neutral side of the supply voltage and terminal 5. See Fig. 2. For an alternate configuration, connect a normally open, double-pole, single-throw switch across terminals 18 and 19, and terminals 21 and 22. A momentary connection across these terminals will reset the PGR-6101. 2.4 FRONT-PANEL INDICATION 2.4.1 POWER The green LED labelled PWR indicates presence of supply voltage. 2.8 CT VERIFICATION A ground-fault trip will occur and the red CT LED will light when a PGC-5000-series CT is not connected to terminals 16 and 17. 2.4.2 >I The red LED labelled >I indicates a ground-fault trip. 3. INSTALLATION 2.4.3 CT The red LED labelled CT indicates that a PGC-5000-series current sensor is not connected. See Section 2.8. 2.4.4 ACTIVE The green LED labelled ACTIVE indicates that the Offline monitoring function is active. The insulation monitoring or lockout function is active when terminals 27 and 28 are connected. See Section 2.2. 2.4.5 <R The red LED labelled <R indicates a low resistance. 2.5 ANALOG OUTPUTS 2.5.1 OUT I A non-isolated, 0- to 1-mA output (terminals 24 and 25) indicates ground-fault current sensed by the CT. The fullscale value corresponds to the ground-fault trip setting. For example, if the ground-fault trip setting is 30 mA, then 1 mA output will be indicated when the measured current is 30 mA. The output is linear between zero and full scale. See Figs. 2 and 6. 2.5.2 OUT R A non-isolated, 0- to 1-mA output (terminals 25 and 26) indicates insulation resistance. The metering output relates to an insulation-resistance range of 0 to infinity. See Figs. 2 and 7. 2.6 REMOTE TEST Use external switches to test the current-sensor detection, insulation-monitoring activation, and insulationmonitoring functions. See Fig. 2. Response to a test input can take several seconds. NOTE: Mounting, terminal block connections and wiring must conform to applicable local electrical codes. Check all applicable codes prior to installation. This ground-fault monitoring system consists of a PGR-6101-series Ground-Fault & Insulation Relay, a PGC-5000-series CT, and for systems over 1.3 kV, a PGH-5000 or PGH-6000 High Tension Coupler connected as shown in Fig. 2. A PGR-6101 can be surface or DIN-rail mounted. See Fig. 1. Use terminal 6 (L1) as the line terminal for a 120 or 240 Vac supply. Use terminal 7 as the line terminal for a 24 Vac supply. Use terminal 5 (L2/N) as the neutral terminal. Connect terminal 30 to ground. Pass the phase conductors through the CT window and position them in the centre of the opening (for four-wire and single-phase systems, also pass the neutral conductor through the CT window). Do not pass ground conductors through the CT window. In applications that require shields or drain wires to pass through the CT window, return them through the CT window before connecting them to ground. CT connections are not polarity sensitive. Applications in electrically noisy environments require twisted- or shielded-twisted-pair CT-secondary conductors. Connect the CT-secondary leads to terminals 16 and 17, and connect the shield to terminal 17. See Fig. 3 for PGC-5000-series CT dimensional drawings. If insulation monitoring is required, connect terminals 27 and 28 to a normally closed contact on the motor starter. For systems up to 1.3 kV connect terminal 2 to one phase of the load side of the starter. Connect optional PGA-0500 Analog Current Meter and PGA-0510 Analog Ohm Meter as shown in Fig. 2. Meter outline, dimensions, and cutout size are shown in Figs. 6 and 7. Page 3 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). L2/N PHASE <1.3 KV 1 2 3 4 L1 5 24 V 6 7 8 9 10 INSULATION K1 11 12 13 2. MOUNTING SCREWS: M4 x 13 OR 8-32 x 0.50. LEAKAGE K2 14 15 3. OVERALL DIMENSION WHEN MOUNTED ON DIN EN50022 35.0 x 7.5 (1.38 x 0.30) TOP-HAT RAIL. TOP 115.0 (NOTE 3) 99.80 (3.93) (4.53) POWR-GARD GROUND-FAULT & INSULATION MONITOR 0= 30 mA 1= 60 mA 0= <50 ms 1= 150 ms 2= 100 mA 2= 200 ms 3= 200 mA 3= 250 ms ΔI 0 2 0 INSULATION RESISTANCE 1 2 CT PWR RESET RESPONSE 1 >ΔI TEST PUSH 8 s 3 FAULT PGR-6101 SERIES TIME DELAY 200 KΩ 400 KΩ ACTIVE 60 KΩ 600 KΩ <R 75.0 (2.95) LEAKAGE CURRENT 3 110.0 (4.33) FRONT SIDE 7.4 (0.29) 16 17 18 19 20 NON AUTO K2 FAI L RESET SAFE 21 22 23 NON AUTO K1 FAI L RESET SAFE 24 25 26 ANALOG OUT I OUT R 27 28 INSULATION 29 30 HTC >1. 3 K V 61.2 (2.41) 75.0 (2.95) CT 99.80 (3.93) 85.0 (3.35) MOUNTING DETAIL FIGURE 1. PGR-6101 Outline and Mounting Details. 6.9 (0.27) BOTTOM Page 4 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor (PGR-6101 terminal 2 is not used.) For PGR-6101 to PGH-5000/PGH-6000 distances greater than 10 m (30’), use shielded cable, and connect the cable shield to the second PGH-5000/PGH-6000 terminal E. Connect terminal A to one phase on the load side of the motor starter. See Fig. 2. The PGH-5000/PHG-6000 includes 915 mm (36”) of high-voltage conductor. 3.1 PGH-5000 AND PGH-6000 For 5-kV and 6-kV systems, connect the PGR-6101 to the monitored circuit with a PGH-5000 and PGH-6000 respectively. See Fig. 4 for PGH-5000 outline and mounting details. See Fig. 5 for PGH-6000 outline and mounting details. Connect protective-ground terminal ( ) to ground. Connect terminal E to ground or to PGR-6101 terminal 30, which must be grounded. Connect terminal M to PGR-6101 terminal 29. PGC-5000-SERIES CURRENT SENSOR STARTER LOAD NOTE 4 18 NOTE 3 19 A PGH-5000 / PGH-6000 2 120 VAC L2/N 6 7 24 VAC 5 27 L1 24 V NOTE 2 REMOTE RESET L2/N STARTER CONTACT HIGH TENSION COUPLER FOR CONNECTIONS ABOVE 1,300 VAC 20 21 NOTE 3 E E 22 M 23 REMOTE TEST 28 NOTES: 29 11 K1 LOW INSULATION 1. RELAY CONTACTS SHOWN WITH PGR-6101 DE-ENERGIZED. 10 12 14 K2 LEAKAGE CURRENT 13 S 15 PGA-0500 0-100% + A - PGA-0510 0Ω - INFINITY MΩ + 24 25 26 CURRENT SENSOR PGR-6101 16 19 20 21 30 CONNECT 18 & 19 FOR AUTORESET OPERATION OF K2 CONNECT 19 & 20 FOR NON-FAIL-SAFE OPERATION OF K2 22 CONNECT 21 & 22 FOR AUTORESET OPERATION OF K1 23 CONNECT 22 & 23 FOR NON-FAIL-SAFE OPERATION OF K1 FIGURE 2. Typical Connection Diagram. 3. WHEN PGH-5000 OR PGH-6000 IS USED, DO NOT CONNECT TERMINAL 2. 4. ALTERNATE REMOTE-RESET CONFIGURATION. 17 18 2. INSULATION MONITORING IS ONLY ACTIVE WHEN TERMINALS TERMINALS 27 AND 28 ARE CONNECTED. JUMPER THESE TERMINALS FOR EXTERNAL TESTING. WARNING: BEFORE CARRYING OUT MEGGER OR DIELECTRIC-STRENGTH TESTS ON THE SYSTEM, DISCONNECT THE PGR-6101. Page 5 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor C D H G J 14.0 (0.55) 68.5 (2.70) F TOP (COVER REMOVED) MOUNTING DETAIL NOTES: PGC-5200 OUTLINE 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M5 OR 10-32. 3. RoHS COMPLIANT. DIMENSIONS I D C BOTTOM FIGURE 3. PGC-5000-Series Current Sensors. J K G 1.7 (0.07) E FLUX CONDITIONER FRONT L 4. CE COMPLIANT. B A PGC-5200 PGC-5025 PGC-5060 PGC-5095 A 25.0 (0.98) 61.0 (2.40) 95.0 (3.74) B 99.0 (3.90) 131.5 (5.18) 175.0 (6.89) 218.0 (8.78) 309.0 (12.17) C 92.5 (3.64) 115.0 (4.53) 158.0 (6.22) 203.0 (7.99) 290.5 (11.44) D 75.0 (2.95) 98.0 (3.86) 141.0 (5.55) 178.0 (7.01) 267.5 (10.50) E 42.5 (1.67) 60.5 (2.38) 82.0 (3.22) 103.5 (4.07) 150.0 (5.90) F 32.0 (1.26) 32.0 (1.26) 32.0 (1.26) 32.0 (1.26) 34.0 (1.34) G 15.5 (0.61) 15.5 (0.61) 17.5 (0.69) 11.0 (0.43) 11.0 (0.43) H 15.0 (0.59) 14.5 (0.57) 15.0 (0.59) 13.3 (0.52) 13.3 (0.52) I 34.0 (1.34) 33.5 (1.32) 33.0 (1.30) 34.0 (1.34) 43.0 (1.69) J 9.0 (0.35) 7.5 (0.30) 9.0 (0.35) 11.0 (0.43) 11.5 (0.45) K 40.0 (1.57) 40.5 (1.59) 40.0 (1.57) 40.0 (1.57) 50.0 (1.97) L 5.3 (0.21) 5.3 (0.21) 5.3 (0.21) 7.0 (0.28) 7.0 (0.28) PGC-5130 130.0 (5.12) 200.0 (7.87) Page 6 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor 95.2 (3.75) 44.5 (1.75) 9.5 (0.38) NOTE 2 POWR-GARD PGH-5000 PGH-5000 Æ 5 KV HIGH TENSION COUPLER Æ HT Coupling Voltage: 5,000 Vac Max. Current to Ground: 2.5 mA Max. A DANGER HIGH VOLTAGE Impedance to Ground: >2M E M RELAY Revision: Serial No: Formerly HTC 5000 165.1 (6.50) PGH-5000 E 1-800-TEC-FUSE (1-800-832-3873) Made in Saskatoon, Canada ATTENTION! 150.0 (5.91) E E M 5kV HIGHTENSION COUPLER BOTH GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTIONS TO THE RELAY AND THE HIGH VOLTAGE LINE MAXIMUM VOLTAGE AC 5000V A A 915.0 (36.00) FRONT NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING HOLES: 5.00 (0.20). 3. ALL GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTION TO RELAY AND HIGH VOLTAGE LINE. 4. CORD PROVIDED IS APPROXIMATELY 915.0 (36.00) LONG. FIGURE 4. PGH-5000 Outline and Mounting Details. SIDE MOUNTING DETAIL Page 7 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor 145.0 (5.71) 120.0 (4.72) 98.5 (3.88) 12.50 (0.49) 12.50 (0.49) POWR-GARD POWR-GARD A E E M 6kV HIGHTENSION COUPLER PGH-6000 6kV HIGHTENSION COUPLER PGH-6000 PGH-6000 Æ 6 KV HIGH TENSION COUPLER Æ Coupling Voltage: 6,000 Vac Max. Current to Ground: 2.5 mA Max. HT A DANGER DANGER HIGH VOLTAGE ATTENTION! ATTENTION! BOTH GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTIONS TO THE RELAY AND THE HIGH VOLTAGE LINE 175.0 (6.89) 200.0 (7.87) HIGH VOLTAGE Impedance to Ground: >2M MAXIMUM VOLTAGE 1-800-TEC-FUSE (1-800-832-3873) Made in Saskatoon, Canada MAXIMUM VOLTAGE (0.49) 12.50 AC 6000V FRONT 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING HOLES: 6.35 (0.25). 3. ALL GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTION TO RELAY AND HIGH VOLTAGE LINE. 4. CORD PROVIDED IS APPROXIMATELY 915.0 (36.00) LONG. FIGURE 5. PGH-6000 Outline and Mounting Details. M Revision: Serial No: Formerly HTC 6000 915.0 (36.00) LONG NOTES: E RELAY BOTH GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTIONS TO THE RELAY AND THE HIGH VOLTAGE LINE AC 6000V PGH-6000 E SIDE Page 8 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor 4. TECHNICAL SPECIFICATIONS Certification ..................................UL Listed LISTED SWITCHES, IND CONT 19PF NRNT, NRNT7, E183688 4.1 PGR-6101 Supply: 120 Option...............................5 VA, 120/24 Vac, (+10, -15%) 50/60 Hz Operation Class.............................Continuous K1 and K2 Relay Contacts: Configuration ..........................N.O. and N.C. (Form C) Operating Mode ......................Fail-Safe or Non-Fail-Safe UL Contact Rating ..................5 A Resistive, 125 Vac Switching Capacity .................625 VA Supplemental Contact Ratings: Carry Continuous .............5 A, maximum Break: 30 Vdc .......................... 5 A 110 Vdc ........................ 0.3 A Trip Mode .....................................Latching or Autoreset Reset ..............................................Front-Panel Button and Remote N.C. Contact Test ................................................Front-Panel Button and Remote Contacts Terminals ......................................Wire Clamping, 12-22 AWG (0.3 to 2.5 mm2) conductors Dimensions: Height ...................................... 75 mm (3.0”) Width ....................................... 100 mm (3.9”) Depth ....................................... 113 mm (4.4”) Including DIN rail ............. 115 mm (4.5”) Shipping Weight ........................... 0.45 kg (1 lb) Environment: Operating Temperature ........... -10 to 60°C (14 to 140°F) Storage Temperature ............... -40 to 80°C (-40 to 176°F) Humidity..................................85% Non-Condensing UL508 Industrial Control Equipment FCC 4.1.1 PGR-6101 ONLINE OPERATION Trip-Level Settings (ΔI) .............. 30, 60, 100, and 200 mA Trip-Time Settings ....................... <50, 150, 200, and 250 ms Input: CT ............................................ PGC-5000-Series CT Detection ........................... Open-Circuit Detection Analog Output: Mode ....................................... Self Powered Range ...................................... 0 - 1 mA Output impedance .................. 5 k maximum 4.1.2 PGR-6101 OFFLINE OPERATION Maximum System Voltage: Direct Connection .................. 1,300 V With PGH-5000 ..................... 5,000 V With PGH-6000 ..................... 6,000 V Measuring Voltage ...................... 12 Vdc Measuring Current ....................... 20 A maximum DC Resistance .............................. 600 k AC impedance at 50-60 Hz ......... > 1 M Response-Level Settings ............. 60 to 600 k Response Delay ........................... < 3 s Maximum Leakage Capacitance to Ground ................ < 1 F Maximum Stray Voltage ............. 1,000 Vdc Analog Output: Mode ....................................... Self Powered Range ...................................... 0 - 1 mA Impedance .............................. 5 k maximum PGR-6101 Ground-Fault & Insulation Monitor 4.2 PGH HIGH TENSION COUPLERS Maximum Line Voltage: PGH-5000 ...............................5,000 Vac PGH-6000 ............................ 6,000 Vac Page 9 Rev. 0-B-020614 5. ORDERING INFORMATION PGR-6101- Current to Ground ..................... 2.5 mA maximum Supply: 120 – 120- or 24- Vac Supply Terminal M Maximum Voltage ................................. 50 Vac PGA-0500 ............ Analog Percent Current Meter PGA-0510 ............ Analog Ohm Meter PGC-5025 ............ Current Sensor, 25.0 mm (0.98”) window PGC-5060 ............ Current Sensor, 60.8 mm (2.39”) window PGC-5095 ............ Current Sensor, 95.0 mm (3.74”) window PGC-5130 ............ Current Sensor, 130.0 mm (5.12”) window PGC-5200 ............ Current Sensor, 200.0 mm (7.87”) window PGH-5000 ............ 5 kV High Tension Coupler PGH-6000 ............ 6 kV High Tension Coupler Terminals: E, E, and M .......................... Wire Clamping, 22 to 12 AWG (0.2 to 2.5 mm2) conductors ....................................... Wire Clamping, 10 AWG (5.26 mm2) maximum High Tension Lead A ................ 8 AWG (8.36 mm2), 40 kVdc, 915 mm (36”) 67.5 (2.657) 67.5 (2.657) 48.0 (1.890) 66.0 (2.598) R1.25(0.049) MAXIMUM NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). TOP 100 40 ® 20 65.0 (2.559) 80 60 71.0 (2.795) % MOUNTING CUTOUT 0 PGA-0500 ANALOG % CURRENT METER FRONT FIGURE 6. PGA-0500 Analog Percent Current Meter. SIDE REAR Page 10 Rev. 0-B-020614 PGR-6101 Ground-Fault & Insulation Monitor 67.5 (2.657) 67.5 (2.657) 48.0 (1.890) 66.0 (2.598) R1.25(0.049) MAXIMUM NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). TOP FRONT 65.0 (2.559) 71.0 (2.795) MOUNTING CUTOUT SIDE REAR FIGURE 7. PGA-0510 Analog Ohm Meter. 6. PERFORMANCE TESTS 6.1 GROUND-FAULT TEST Some jurisdictions require periodic ground-fault performance tests. A test record form is provided for recording the date and the result of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel. a) Evaluate the interconnected system in accordance with the overall equipment manufacturer’s detailed instructions. b) Verify proper location of the PGC-5000-series CT. Ensure the cables pass through the CT window. This check can be done visually with knowledge of the circuit. The connection of the current-sensor secondary to the PGR-6101 is not polarity sensitive. c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor. High-voltage testers and resistance bridges can be used to determine the existence of alternate ground paths. d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled ground-fault current. To simulate ground-fault current, use CT-primary current injection. Fig. 8 shows a test circuit using the SE-400 Ground-FaultRelay Test Unit. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Fig. 8 shows the use of resistors that reduce the injected current to 10% of the SE-400 setting. Set the test current to 120% of the PGR-6101 setting. Inject the test current through the CT window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and retest until the proper reaction is verified. PGR-6101 Ground-Fault & Insulation Monitor e) Record the date and the results of the test on the attached test-record form. Do not inject test current directly into NOTE: CT-input terminals 16 and 17. PGC-5000 SERIES FROM POWER SOURCE LOAD 16 17 R1 L ITEST N 6 5 CT L1 L2/N PGR-6101 R2 11 L N 3 5 OP1 8 9 12 L1 L2 SE-400 1 REMOTE TEST OP2 RMT1 RMT2 R1 = 1 Ω, 10 W, 1% R2 = 0.1 Ω , 10 W, 1% ITEST = 1/10 SE-400 SETTING FIGURE 8. Ground-Fault-Test Circuit. TABLE 1. GROUND-FAULT-TEST RECORD DATE TEST RESULTS Retain this record for the authority having jurisdiction. Page 11 Rev. 0-B-020614 6.2 INSULATION TEST Perform this test with the starter open and appropriate lock-out procedures. Connect a 10-k resistor between one phase and ground at the line side of the starter or motor terminal box. Select a phase that is not connected to PGR-6101 terminal 2 (or the PGH-5000 or PGH-6000). The PGR6101, operating in Offline mode as indicated by the green ACTIVE LED, will alarm, operating the K1 low insulation output relay and lighting the red <R LED. PGR-6101 Ground-Fault & Insulation Monitor MANUAL RELEASE DATE Page 12 Rev. 0-B-020614 APPENDIX A PGR-6101 REVISION HISTORY MANUAL PRODUCT REVISION REVISION (REVISION NUMBER ON PRODUCT LABEL) February 6, 2014 0-B-020614 01 November 22, 2013 0-A-112213 00 MANUAL REVISION HISTORY REVISION 0-B-020614 SECTION 3 Fig. 3 updated. SECTION 4 UL Certification and contact rating specifications added. REVISION 0-A-112213 Initial release. PRODUCT REVISION HISTORY PRODUCT REVISION 01 UL Certification. PRODUCT REVISION 00 Initial release.