PRODUCT DATASHEET ET-16DI2 EtherTRAKTM DISCRETE INPUTS Select the ET-16DI2 when you need discrete (on/off) inputs reported over an Ethernet Network PRODUCT HIGHLIGHTS Supports DC sinking/sourcing or AC wiring User-configurable smart filtering Pulse counters with contact bounce filtering One high-speed counter channel to 2 KHz PERFORMANCE SPECIFICATIONS 16 input channels Nominal input voltage 12/24 VDC/VAC Guaranteed ON voltage1 9 VDC/VAC Maximum input voltage 30 VDC/VAC Guaranteed OFF voltage2 5.0 VDC Guaranteed OFF current2 1.4 mA Input resistance 3.6K Ohms Nominal input current @ 24VDC 6.7 mA Filtered Mode ON/OFF delay (note 3) 25mS Filtered Mode count feature 10 Hz maximum Fast Mode count feature 100 Hz (2 KHz on channel 1) Fastest scan rate (16 channels) 2 mS4 Required supply voltage 10-30 VDC (0.75 watt typical) Operating temperature range -30 to 70° C Storage temperature range -40 to 85° C Humidity (non-condensing) 5 to 95% RS485 PORT FOR I/O EXPANSION 32 (up to 512 I/O) Max. RS485 stations Protocol Sixnet “I/O for Windows” and Modbus ASCII and RTU Baud rate 38,400 bps Up to 0.5 mile recommended distance Isolation (from Ethernet port) 1200 Volts RMS 1 minute Notes: 1 Minimum voltage guaranteed to turn the module ON. 2 The maximum input current/voltage that will not switch the input from OFF to ON. 3 Smart logic ignores transients, power line dropouts and switch contact bounce. 4 I/O register update time does not include external communications. ORDERING INFORMATION ET-16DI2-H 16 inputs with wiring base ET-16DI2-M Replacement module only All specifications are subject to change. Consult factory for latest info. Sixnet Technology Park • 331 Ushers Road • Ballston Lake, NY 12019 USA 1.518.877.5173 • Fax 1.518.877.8346 • [email protected] SOLUTIONS FOR YOUR INDUSTRIAL NETWORKING CHALLENGES 2002 DATASHEET ET-16DI2 28-FEB-09 WWW.SIXNET.COM