EtherTRAKTM DISCRETE OUTPUTS

PRODUCT DATASHEET
ET-16DO2
EtherTRAKTM DISCRETE OUTPUTS
Select the ET-16DO2 when you need to control relays, solenoids, valves and other outputs
over an Ethernet network.
PRODUCT HIGHLIGHTS

High density outputs save space

Isolation protects the Ethernet network

Time proportioned outputs for variable control

Surge suppressors safely clamp inductive loads
PERFORMANCE SPECIFICATIONS

16 output channels

Output range 10 - 30 VDC

Max. output current per channel 1 Amp

Max. output current (entire module) 8 Amps

Max. OFF state leakage current 0.05 mA

Min. load current per channel 0.1 mA

Inrush current (100 mS surge) 5 Amps

Typical ON resistance 0.3 Ohms

Typical ON voltage (@ 1 Amp) 0.3 VDC

Time proportioned outputs1 configurable for each channel

Fastest scan rate (16 channels) 2 mS

Required supply voltage 10-30 VDC (0.75 watt typical)

Operating temperature range -30 to 70° C

Storage temperature range -40 to 85° C

Humidity (non-condensing) 5 to 95%
RS485 PORT FOR I/O EXPANSION





1
32 Max. RS485 stations (up to 512 I/O)
Baud rate: 38,400 bps
Recommended distance of up to 0.5 mile
Protocol: Sixnet “I/O for Windows”, Modbus ASCII & RTU
Isolation (from Ethernet port) 1200 Volts RMS 1 minute
Time proportioned outputs control the duty cycle of the output in proportion to an analog output register value. The cycle time and minimum
pulse time are configurable.
ORDERING INFORMATION
ET-16DO2-H
16 outputs with wiring base
ET-16DO2-M
Replacement module only
All specifications are subject to change. Consult factory for latest info.
Sixnet Technology Park • 331 Ushers Road • Ballston Lake, NY 12019 USA
1.518.877.5173 • Fax 1.518.877.8346 • [email protected]
SOLUTIONS FOR YOUR INDUSTRIAL NETWORKING CHALLENGES
2006 DATASHEET
ET-16DO2 2-MAR-09