PRODUCT DATASHEET ET-16AI2 EtherTRAKTM 4-20 MA ANALOG INPUTS Select the ET-16AI2 when you need to monitor 4-20 mA analog signals over an Ethernet network. PRODUCT HIGHLIGHTS 14 bit A/D for precision measurements Smart filtering rejects noise User choice of integration time – speed vs. filtering Field replaceable current shunts save maintenance time PERFORMANCE SPECIFICATIONS 16 channels counters Input range 4-20 mA A/D resolution 14 bits (0.01%) Full scale accuracy (@20°C) +/- 0.05% Span and offset temp. coefficient +/- 50 ppm per °C typical Input impedance 100 Ohms Input current protection replaceable shunts Fastest scan rate (16 channels) 5 mS Required supply voltage 10-30 VDC (0.75 watt typical) Operating temperature range -30 to 70° C Storage temperature range -40 to 85° C Humidity (non-condensing) 5 to 95% RS485 PORT FOR I/O EXPANSION 32 Max. RS485 stations (up to 512 I/O) Baud rate: 38,400 bps Recommended distance of up to 0.5 mile Protocol: SIXNET “I/O for Windows”, Modbus ASCII & RTU Isolation (from Ethernet port) 1200 Volts RMS 1 minute ORDERING INFORMATION ET-16AI2-H 16 inputs with wiring base ET-16AI2-M Replacement module only All specifications are subject to change. Consult factory for latest info. SIXNET Technology Park • 331 Ushers Road • Ballston Lake, NY 12019 • USA 518.877.5173 • Fax 518.877.8346 • [email protected] SOLUTIONS FOR YOUR INDUSTRIAL NETWORKING CHALLENGES WWW.SIXNET.COM