RM Series Modular Rectifier FEATURES • • • • • • • • Forced cooled Modular for hot swap system Thermally protected Power factor corrected Input /output voltage & current protected Serial alarm & control interface Microprocessor controlled Conformal coating optional SPECIFICATIONS AC INPUT NOISE Nominal 230VAC Ripple <100Hz Voltage range 90-300V (175-275V not deratted output power) Voice band 100Hz-5KHz <1mV rms psophometric Frequency range 45-65 Hz Wide band 5kHz-1MHz <5mV rms unweighted Power factor >0.99 Peak to peak 0-20MHz <50 - 100mV peak to peak model dependant Peak efficiency ISOLATION see table Total harmonic distortion <5% (>30% output power) (THD) Input fuses HRC fuses in phase and neutral Maximum input current 11 to13A model dependant PROTECTION Input voltage Input inrush Auto shutdown, auto restart when correct voltage restored <2x maximum input current DC OUTPUT Output ratings <1mV rms unweighted Input to output 4000V DC Input to chassis 3500V DC (VDR to chassis removed) Output to chassis 2100V DC ENVIRONMENT Ambient temperature Nominal Range +25 +/- 5ºC Storage temperature -10ºC to +70ºC (maximum output power derated above +50ºC) -20 to +70ºC Humidity 5-95% RH (non-condensing) Altitude <2500m, De-rate maximum ambient temperature by 4ºC per 1000m above sea level Nominal voltage 48V constant power output from (48V to 58V) 24V current limited to 41.7A See table Rated voltage 24V (29V) & 48V (58V) Voltage range See table Dimensions W 111.5mm x H 44mm x D 282mm Maximum current See table Weight 1.5kg Cooling Forced cooled MECHANICAL REGULATION COMPLIANCES Line ±0.1% Load ±0.5% (no load to full load) Safety EN 60950-1:2006 Hold-up time >15ms for 20% output voltage drop. RF emissions CISPR 22 Class Start-up time Start up delay 1 second. (varies with AC supply voltage) RF immunity CISPR 24: EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11 Walk-in delay 6 seconds at full output. (varies with DC output voltage) AC harmonics EN 61000-3-2 AC flicker and fluctuation EN61000-3-3 Other CE & RoHS compliant PROTECTION Current limit Over temperature Adjustable to 50-100% of maximum rated current Automatic current turndown, backup shutdown protection Polarity reversal Output fuse with crowbar diode Over voltage Adjustable limit (under nominal conditions) Doc. No. PBRC Rev.H 18-2-2014 BATTERY CHARGER & SYSTEMS 1 - 2 K W AT T S C O M M U N I C AT I O N S RM SERIES RECTIFIER MODULE MODEL VOLTAGE RANGE MAXIMUM CURRENT EFFICIENCY POWER RM2048HE 48V (43-58V) 41.7A 96.5% 2kW RM2048XE 48V (43-60V) 41.7A 94% 2kW RM2048/24 24V (21-30V) 41.7A 92% 1kW Powering Progress – www.powerbox.com.au 20