Specification Sheet

PSC06 Series
1 0 0 0 - 6 0 0 0 W AT T S 2 U U LT R A C O M PA C T B AT T E R Y C H A R G E R S
FEATURES
•
•
•
•
•
•
1000W - 6000W
Configurable Battery Charging System
2U 19" Rack Mounting
Network Monitoring
N+1 Operation
Fully Featured Telecom Grade Rectifier
SPECIFICATIONS
MONITORING & CONTROL
INPUT
AC input
240V AC (90-300V) Single phase or 415V AC
Three phase (shelf type dependant)*
Frequency range
45-66 Hz
Power factor
>0.99 full load
Termination
Single phase, 6 - 10mm² L, N, E tunnel terminals*
Three phase, 6 - 10 mm² L1,L2,L3,N,E terminals *
(Single phase by linking line terminals)
DC OUTPUTT
Nominal voltage
48V (+48V or +24V optional)*
Rated system output
power
6-8k Watts @ -48V (refer to table)
3-4k Watts @ 24V
Positive earth,
(negative earth option available)*
Polarity
Display
Multi-lingual alpha numeric backlit display
Communications
Serial: 1x USB port on front panel for local PC interface
TCP/IP: Ethernet interface for communication using
SNMP protocol and internal web based configurator*
Modbus: Supported via TCP/IP*
LED Indicators
Green: Power on/monitor OK
Yellow: Non urgent alarm
Red: Urgent alarm
Audible
90dBA buzzer mappable to user defined conditions
Controls
3x push buttons for parameter setting or viewing on
front panel
Signal Inputs
Serial bus for rectifier control and interface to
peripheral modules
6x digital inputs
2x temperature sensors (one fitted by default)
Alarms
6x alarm relays, 5x of which can be mapped for
customised alarm settings
Alarm Contacts
0.3A 100V volts free changeover contacts
Logging Capacity
Periodic log, 16,384 records (dependant on number of
parameters logged)
Event log, 16,384 records (dependant on number of
parameters logged)
Connections
Relay outputs, mini combicon to accept 1.5mm² wire
USB port, USB mini B
DC DISTRIBUTION
Load
Battery
Standard Shelf configuration.
(Customized configuration available)*
Standard Shelf configuration
(Customized configuration available)*
Breaker fail detection
Electronic fail detection on both load
and battery breakers
DC terminals
Rear Connect DIN Rail
Load
Tunnel terminals 6 mm² to 16mm²*
Battery
Tunnel terminals 35mm²*
Low voltage disconnect See Standard Shelf configuration.
ENVIRONMENTAL REQUIREMENTS
Ambient Temperature
-20ºC to +70ºC
Storage Temperature
-30ºC to +85ºC
Humidity
5-95% RH (non-condensing)
Altitude
<2,500m at full power
*TCP/IP and modbus options only available with SM36 supervisory module.
CONFIGURATION AND OPTIONS
Rectifiers
RM2048XE: 2.0kW modular rectifier, 230V AC input,
48V DC output, 41.7A maximum output
RM2048HE: 2.0kW modular rectifier, 230V AC input,
48V DC output, 41.7A maximum output
RM2048/24: 2.0kW modular rectifier, 230V AC input,
48 or 24V DC output, 41.7A maximum output
RM1860/48: 1.8kW modular rectifier, 230V AC input,
60 or 48V DC output, 30.0A maximum output
Supervisory Modules
SM35: standard monitor featuring full temperature
compensation, automated and manual battery
testing/equalisation
SM36: enhanced monitor featuring full temperature
compensation, automated and manual battery
testing/equalisation with TCP/IP
ARBP-1M
Metal rectifier blanking panel
ASM-ABM24(-24-48-60)
Battery condition monitor for 24, 48 or 60V battery
strings
ASM-AC3P
AC mains monitor
MECHANICAL
Dimensions
W, H, D
482.6mm (19” mount), 89.0mm (2U), 390.0mm
Weight
9kg (excluding rectifier modules)
Shipping Dimensions
W, H, D
540.0mm, 150.0mm, 435.0mm
Shipping Weight
10.5kg (excluding rectifier modules)
Doc. No. PSC06 Series Rev.C 28-9-15
1
Powering Progress
PSC06 Series
1 0 0 0 - 6 0 0 0 W AT T S 2 U U LT R A C O M PA C T B AT T E R Y C H A R G E R S
SELECTION TABLE
MODEL NUMBER
MAX RECTIFIERS
MAX SHELF POWER
DC DISTRIBUTION
PSC06 V1
3
24, 48 or 60VDC
6.0kW
Positive or Negative Earth
6 x load circuit breakers (6-63A)
2 x battery circuit breakers (max 63A)
125A magnetically latching battery LVD
PSC06 V2
3
24, 48 or 60VDC
6.0kW
Positive or Negative Earth
16 x load circuit breakers (2-30A)
2 x battery circuit breakers (max 100A)
125A magnetically latching battery LVD
*System part numbers are dependent on configuration options. For final system part numbers consult our sales staff for configuration advice.
TECHNICAL ILLUSTRATIONS
Doc. No. PSC06 Series Rev.C 28-9-15
www.powerbox.com.au
www.powerbox.co.nz
1800 251 380
09 4158 320
2