Australia cata.qxd

1U Ultra Compact System
1 0 0 0 - 4 0 0 0 W AT T S T E L E C O M R E C T I F I E R S Y S T E M S
FEATURES
•
•
•
•
•
•
•
•
•
•
1000W - 4000W
Configurable Battery Charging System
1U 19" Rack Mounting
Network Monitoring
N+1 Operation
System Monitoring
Load & Battery MCBs
Battery LVD
Customized shelf configurations available
Fully Featured Telecom Grade Rectifier
SPECIFICATIONS
MONITORING & CONTROL
INPUT
AC input
240V AC (90-300V) Single phase
Display
Frequency range
45-66 Hz
Power factor
>0.99 full load
Termination Single phase, 6 or 10mm² L,
N, E tunnel terminals
Serial: 1x USB port on front panel for local PC interface
TCP/IP: Ethernet interface for communication using SNMP
Communications
protocol and internal web based configurator*
Modbus: Supported via TCP/IP*
Termination
DC OUTPUTT
Nominal voltage
Rated system output power
Polarity
LED Indicators
48V (+48V or +24V optional)*
4k Watts @ -48V
2k Watts @ 24V
Positive earth, (negative earth option
available)
DC DISTRIBUTION
Load
Signal Inputs
Battery
Low voltage disconnect
See Shelf configuration system
Breaker fail detection
Controls
Standard Shelf configuration. (Customized
configuration available)*
Standard Shelf configuration (Customized
configuration available)*
Electronic fail detection on both load and
battery breakers
Tunnel terminals 10 mm²
Battery
Audible
ENVIRONMENTAL REQUIREMENTS
Ambient Temperature
-20ºC to +70ºC
Storage Temperature
-30ºC to +85ºC
Humidity
5-95% RH (non-condensing)
Altitude
<2,500m at full power
Alarms
Alarm Contacts
482.6mm (standard 19" module),
44.45mm (1U), 285mm
Weight
5kg (excluding rectifier modules)
Shipping Dimensions
W, H, D
540.0mm, 95.0mm, 400.0mm
Shipping Weight
6.0kg (excluding rectifier modules)
Green: Power on/monitor OK
Yellow: Non urgent alarm
Red: Urgent alarm
90dBA buzzer mappable to user defined conditions
3x push buttons for parameter setting or viewing on front
panel
Serial bus for rectifier control and interface to peripheral
modules
6x digital inputs
2x temperature sensors (one fitted by default)
6x alarm relays, 5x of which can be mapped for customised
alarm settings
0.3A 100V volts free changeover contacts
Periodic log, 16,384 records (dependant on number of
parameters logged)
Logging Capacity
Event log, 16,384 records (dependant on number of
parameters logged)
Connections
Relay outputs, mini combicon to accept 1.5mm² wire USB
port, USB mini B
*TCP/IP and modbus options only available with SM36 supervisory module.
CONFIGURATION AND OPTIONS
MECHANICAL
Dimensions
W, H, D
Multi-lingual alpha numeric backlit display
Rectifiers
Supervisory
Modules
ARBP-1M
RM2048XE: 2.0kW modular rectifier, 230V AC input, 48V
DC output, 41.7A maximum output
RM2048HE: 2.0kW modular rectifier, 230V AC input, 48V
DC output, 41.7A maximum output
RM2048/24: 2.0kW modular rectifier, 230V AC input, 48 or
24V DC output, 41.7A maximum output
RM1860/48: 1.8kW modular rectifier, 230V AC input, 60 or
48V DC output, 30.0A maximum output
SM35: standard monitor featuring full temperature
compensation, automated and manual battery
testing/equalisation
SM36: enhanced monitor featuring full temperature
compensation, automated and manual battery
testing/equalisation with TCP/IP
Metal rectifier blanking panel
ASM-ABM24
(-24-48-60)
Battery condition monitor for 24, 48 or 60V battery strings
ASM-AC3P
AC mains monitor
1U Ultra Compact System
1 0 0 0 - 4 0 0 0 W AT T S T E L E C O M R E C T I F I E R S Y S T E M S
TECHNICAL ILLUSTRATIONS
MODEL NUMBER
MAX RECTIFIERS
MAX SHELF POWER
DC DISTRIBUTION
24, 48 or 60VDC
1 x load circuit breaker (6-63A)
4.0kW
1 x battery circuit breaker (max 63A)
Positive or negative earth 80A Magnetically latching battery LVD
24, 48 or 60VDC
1 x load circuit breaker (6-63A)
4.0kW
1 x battery circuit breaker (max 63A)
PSC04 V2
2
Positive or negative earth 80A Magnetically latching battery LVD
*System part numbers are dependent on configuration options. For final system part numbers consult our sales staff for configuration
advice.
PSC04 V1
2
TECHNICAL ILLUSTRATIONS
Powering Progress – www.powerbox.com.au