Description Purpose and application The DIM MULTI sensor controls brightness at the workplace and in offices to increase comfort and save energy. DIM MULTI The sensor is installed in T5/T8 fluorescent lamps or ceilings and is connected directly to control gear with a 1...10 V interface. The following application types are available, depending on how the sensor is connected (see the connection diagram in the fitting instructions): • Alternative 1: One sensor controls and switches a load area. • Alternative 2: Multiple sensors with a shared (coupled) motion detector individually control and switch separate load areas. • Alternative 3: One sensor controls and switches a large load area, and additional sensors are used as pure motion sensors to enlarge the detection area. • Alternative 4: One sensor controls and switches a load area and motion detection is deactivated. Function The sensor measures the brightness in the area to be regulated and keeps this to an adjustable set value by introducing artificial light according to the amount of daylight available. Light and motion sensor Operating instructions The sensor also detects the movements of people. As daylight increases the artificial light is reduced. If the sensor no longer detects any motion, it switches the luminaires off after an adjustable delay period. Design A The sensor is made up of the following components: • Connections (A, on the back of the sensor): –– L, N: Supply lines –– 0 V, 1-10 V: control lines H –– ↑: Load G C F –– B: Control button or parallel circuit for shared motion detection –– Function selection switch –– DIP switch • Push button: Setpoint for brightness (C) • Motion sensor (D) E D • Light sensor (E) • Setscrew: Activating/deactivating motion detection (F) • Setscrew: Switch-off delay time (F) • Housing (H) Operation Automatic control principle Precondition: Motion detection is activated. Luminaire OFF Motion? no yes III 2011 DIM_Multi_ba1103_en_we2.01.indd OSRAM GmbH Kunden Service Center Customer-Service-Center (CSC) Steinerne Furt 62 86167 Augsburg Germany Artificial light required? no yes Luminaire ON Tel : +49 (0) 1803 677 - 200 (kostenpflichtig / charges apply) Fax.: +49 (0) 1803 677 - 202 www.osram.com www.osram.de 40503005544718 4050300554471 Page 1 of 4 Luminaire ON Operation (cont.) Luminaire ON 5 - 30 min Motion? Luminaire OFF no yes 3 min Artificial light required? no Luminaire OFF yes 0 Control button of luminaire Luminaire on Short press (< 0.5 s) Luminaire off Brightness with automatic regulation 2 4 6 C E Symbols 8 A Specifying the setpoint for brightness control Press the push button on the sensor until the desired brightness is reached. Ten seconds after the push button is pushed, the brightness is measured and stored as the setpoint. Alternative: Adjust the setpoint by double-clicking on the external control button. 0 Left stop: Automatic motion detection à The lighting is dimmed after the switch-off delay time, switched off after 10 minutes and automatically switched on again when motion is detected 2 Right stop: Depending on the basic function setting (see “Setting the basic functions”): 4 6 C E Setting the operating mode for motion detection 8 A • Variant 1: operation without motion detection • Variant 2: operation without motion detection 0 2 Adjusting the switch-off delay time 4 6 C E • Variant 3: semi-automatic motion detection à like automatic motion detection, except that lighting that was switched off automatically because of lack of motion must be switched on again manually using the external control button. 8 A Switch-off delay time if no motion is detected. Turn the setscrew on the sensor to the required setting: • To the left: Shorter (max. 1 min.) 2x 2 • To the right: Longer (max. 30 min) 3 Switching and dimming the luminaire Precondition: control button is connected to connector B; see the connection diagram in the fitting instructions. 2 0 4 6 max 2 C E A 8 A < 30 s To switch: Short press. To dim: Long press. Note: The brightness control is deactivated until the next time the luminaire is switched on. 3 B Each repeated long control button press causes a toggle be... tween increased brightness and decreased brightness. Page 2 of 4 2x Setting the basic functions 0 2 4 6 C E Operation (cont.) The function selection switch is used to select the basic functions for the setscrew for motion detection, the external control button and the reflection correction. In each variant, the device acts as a constant light control with motion detection. Only the functions of the setscrew and the external control button differ for each variant. 8 A Var. Device function 1 Switch setting Right stop = operation without motion detection 0 1 2 3 4 5 6 7 8 9 A B Change between operation with automatic/without motion detection 2 Right stop = operation without motion detection Switching and dimming the luminaire 3 Right stop = semi-automatic motion detection Switching and dimming the luminaire 4 Device is only used for detection area expansion F Switch settings C, D, E are currently not in use. Adjusting the reflection correction Depending on the room characteristics, set the reflection correction in 4 stages using the function selection switch: • Increase the value (e.g. from 0 to 1 to 2 to 3 in function variant 1) if the artificial light is dimmed too much. • Decrease the value (e.g. from 7 to 6 to 5 to 4 in function variant 2) if the artificial light remains too bright. Valid for all 3 function variants. Restricting the basic functions The function variants (2 and 3) set via the function selection switch can be restricted as follows via the DIP switch: 1: OFF 2: OFF On/off active Lighter/darker dimming active Setpoint storage activ 1: ON 2: OFF On/off active Lighter/darker dimming active Setpoint storage blocked 1: ON 2: ON On/off active Lighter/darker dimming blocked Setpoint storage blocked 2x 1 < 30 s 2 3 A max Page 3 of 4 1 2 3 Appendix Technical data Operating voltage 230 V / 50-60 Hz (no DC operation) Fuse External 6 A Power consumption Approx. 2 W Maximum total line length (control line: 0.5 mm2, load and supply line: 1.5 mm2) 100 m Line connection Screw terminals for single-wire or fine-wire conductors with 0.3 – 1.5 mm2 or with 1.5 m cables Control connection Basic insulation as per IEC 664, no safety extra low voltage Load capacity of control output 100 mA (approx. 100 ECG or transformers) Load capacity of switching output 5 A resistive load. Max. number of ECG for line cross section of 1.5 mm² and line length of 15 m (distributor to device) + 20 m (to the middle of the load circuit, impedance approx. 800 mΩ): 30 x HF 1x18/230-240 DIM 20 x HF 2x18/230-240 DIM 30 x HF 1x36/230-240 DIM 20 x HF 2x36/230-240 DIM 20 x HF 1x58/230-240 DIM 10 x HF 2x58/230-240 DIM For larger line cross sections or shorter lines, the permissible load is reduced (e.g. by 20 % for an impedance of 400 mΩ). Transient time of control output (dependent on control error) Approx. 10 – 30 seconds Absence delay time 1 – 30 minutes + 10 minutes switch-off delay time Working temperature 0 °C ... +50 °C Adjustable light value Approx. 15 – 1500 lx measured at sensor Detection area Conical, opening angle approx. 110° Pollution severity 2 (dry, not conductive as per IEC 664 10/92) Dimensions (L x W x I) 58.8 x 70.5 x 42 mm Weight Approx. 150 g Protection class II Protection type IP 20 Dimensioned drawing The CE requirements are fulfilled: EMC as per EN 61547, low voltage as per EN 60669-2-1. Conformity with the relevant EU directives is confirmed by the CE symbol. Page 4 of 4