QUICKTRONIC FIT T8 osram.com QUICKTRONIC FIT T8 QT-FIT8 ECG for T8/ 26mm linear fluorescent lamps QT-FIT8 LUMILUX® T8 GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 01 QUICKTRONIC FIT T8 Product Features: 50.000 hours lifetime with max. failure rate of 10% Lamp start with optimized filament preheating within 2 sec. Suitable for lighting with high switching cycles Reliable lamp ignition between -15°C...+50°C Suitable for luminaries of protection class I CELMA Energy-Efficiencies-Index A2 Automatic safety shut-down in case of a defect or at the end of the lamp’s life (EoL T.2) Automatic restart after lamp replacement Suitable for emergency installations (DC, 0 Hz) Technical Data Max. cable diameter for 2 push-in contact [mm ]: 1 s : 0.5 - 1.5 Starting time: t: 2 sec. Line voltage: 220 - 240 V Voltage range (AC): 198 - 264 V Voltage range (DC): 185 - 264 V; for lamp ignition min. 198 V; max. 1 hour 185 - 198V Line frequency: 50 - 60 Hz Operating frequency: 40 - 50 kHz Electrical strength: Ambient temperature ta: Measuring point temperature tc: U-OUT: 1 280 V permanent; 300 V 2 hours -15 °C to +50 °C Max. +70 °C 430 V s = solid wire GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 02 QUICKTRONIC FIT T8 Inrush current and max. number of ECG per circuit breaker ECG QT-FIT8 QT-FIT8 QT-FIT8 QT-FIT8 QT-FIT8 QT-FIT8 QT-FIT8 QT-FIT8 Inrush Current Ip [A] 15 15 15 15 15 15 15 15 1x18 2x18 3x18, 4x18 1x36 2x36 3x36 1x58-70 2x58-70 Max. number of ECG per circuit breaker TH [µs] 200 200 200 200 200 200 200 200 B: 10A 17 17 8 17 8 8 17 8 C: 10A 13 28 - B: 16A 28 28 13 28 13 13 28 13 C: 16 A 49 49 22 49 22 22 49 22 Standards and approval marks Safety: acc. to EN 61347-2-3 / IEC 61347-2-3 Radio interference: acc. EN 55015: 2006 + A1: 2007 + A2: 2009 Harmonic content: acc. to EN 61000-3-2 / IEC 61000-3-2 Immunity: acc. to EN 61547 / IEC 61547 Approval marks: Dimensions & weight Description Description Length [mm] Width [mm] Height [mm] Distance Mounting Holes [mm] Weight [g] QT-FIT8 1x18 280 30 28 270 260 QT-FIT8 2x18 360 30 28 350 350 QT-FIT8 3x18, 4x18 280 40 28 270 370 QT-FIT8 1x36 280 30 28 270 270 QT-FIT8 2x36 360 30 28 350 350 QT-FIT8 3x36 280 40 28 270 390 QT-FIT8 1x58-70 280 30 28 270 280 QT-FIT8 2x58-70 360 30 28 350 350 GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 03 QUICKTRONIC FIT T8 Lamp wiring QT-FIT8 1x… Max. permitted cable length in between ECG and lamp: 2.0 m (PIN 21, 22); 1.0 m (PIN 23, 24) QT-FIT8 2x... Max. permitted cable length in between ECG and lamp: 2.0 m (PIN 21, 22); 1.5 m (PIN 23, 24); 1.0 m (PIN 25, 26) QT-FIT8 3x18, 4x18, QT-FIT8 3x36 – 3 lamp operation QT-FIT8 3x18, 4x18 QT-FIT8 3x36 Max. permitted cable length in between ECG and lamp: 1.0 m (PIN 25, 26); 1.5 m (PIN 4, 5, 21, 22, 23, 24) GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 04 QUICKTRONIC FIT T8 QT-FIT8 3x18, 4x18 – 4 lamp operation QT-FIT8 3x18, 4x18 Max. permitted cable length in between ECG and lamp: 1.0 m (PIN 6, 7, 25, 26); 1.5 m (PIN 4, 5, 21, 22, 23, 24) Logistic Data Description EAN 10 EAN 40 Packaging Unit QT-FIT8 1x18 4008321294180 4008321294197 20 QT-FIT8 2x18 4008321294241 4008321294258 20 QT-FIT8 3x18, 4x18 4008321294302 4008321294319 20 QT-FIT8 1x36 4008321294203 4008321294210 20 QT-FIT8 2x36 4008321294265 4008321294272 20 QT-FIT8 3x36 4008321512055 4008321512062 20 QT-FIT8 1x58-70 4008321294227 4008321294234 20 QT-FIT8 2x58-70 4008321294289 4008321294296 20 Lifetime Measuring point temperature tc: 70 °C Lifetime with max. 10% failure rate 50,000 h GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 05 QUICKTRONIC FIT T8 Lamp/ECG System Combination ECG QT-FIT8 1x18 QT-FIT8 2x18 QT-FIT8 3x18, 4x18 QT-FIT8 1x36 QT-FIT8 2x36 QT-FIT8 3x36 QTP8 1x58-70 QTP8 2x58-70 Lamp L18 2 L16 ES 2x L18 2 2x L16 ES 3x L18 2 3x L16 ES 4x L18 2 4x L16 ES L36 2 L32 ES 2x L36 2 2x L32 ES 3x L36 2 3x L32 ES L58 L70 2 L 51 ES 2x L58 2x L70 2 2x L 51 ES HF lamp wattage [W] 16 14.2 2x16 2x14.2 3x16 3x14.2 4x16 4x14.2 32 29 2x32 2x29 3x32 3x29 50 57 44.5 2x50 2x57 2x44.5 System wattage [W] 19 17.2 36 32.4 54 47.1 74 64 36 32 71 64 105 100 54 62 50 109 124 96 Line current [A] 0.09 0.08 0.16 0.14 0.25 0.21 0.33 0.28 0.16 0.15 0.32 0.30 0.48 0.43 0.24 0.28 0.23 0.48 0.55 0.43 Luminous flux at 25°C [lm] 1350 1100 2x 1300 2x 1100 3x 1350 3x 1100 4x 1350 4x 1100 3200 2500 2x 3200 2x 2500 3x 3500 3x 2500 5000 5900 4200 2x 5000 2x 5900 2x4200 Luminous flux at 35°C [lm] - Power factor [λ] 0.95 0.90c 0.98 0.97 0.97 0.98 0.99 0.98 0.96 0.93c 0.98 0.97 0.99 0.99 0.96 0.96 0.96 0.98 0.98 0.98 For more information on ECG refer to http://www.osram.com/ecg For more information on System Guarantee refer to http://www.osram.com/guarantee 2 Additional Lamp-ballast combination without ENEC; ta = +10 °C to +50 °C GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 06