Cooper CEAG requirements for LED controlgears
Manufacturer:
OSRAM GmbH
Marcel-Breuer-Str.6
D-80807 München
Type / Description: Constant current LED controlgear
LED controlgear: OT 50/220-240/24
Specifications:
CEAG-Datas
Explanation:
Fulfilled: (Yes / No)
186V - 275V DC
Possible voltage range of the battery in emergency mode
(Not necessary for AT-S+ System)
Umschaltzeit:
180 ms - 450 ms
Typical switch over time of CEAG CPS/LPS-devices
YES
starting charakteristic controlgear:
Stabile Stromaufnahme
nach kleiner 1,6 s
necessary for selective control
∆ I < 12,5 mA per luminaire, at max. 20 luminaires for one
current circuit: ∆ I in summ < 250 mA
YES
Fullfilled the standard*:
DIN EN 62384
DC. Or AC supplied electronic control gear for LED modules Performance requirements
YES
Fullfilled the standard*:
DIN EN 61347-2-13
Fullfilled the standard*:
DIN EN 55015
(Messung bei AC und DC)
Fullfilled the standard*:
DIN EN 61000-3-2
Fullfilled the standard*:
DIN EN 61000-3-2, Pkt. 7.3 a.)
Fullfilled the standard*:
DIN EN 61547
LED module fullfilles the standard:
DIN EN 62031
Voltagerange DC:
Switch over time:
from AC to DC
YES (176-276 V)
Lamp controlgear — Part 2‑13: Particular requirements for
d. c. or a. c. supplied electronic controlgear for LED modules
YES
Limits and methods of measurement of radio disturbance
characteristics of electrical lighting and similar equipment
Electromagnetic compatibility (EMC) — Part 3-2: Limits —
Limits for harmonic current emissions (equipment input
current ≤ 16 A per phase)
YES
is forceful necessary for AT-S+ Systems special for LED
drivers!! (sinusoidal current draw)
Equipment for general lighting purposes — EMC immunity
requirements
YES
YES
YES
LED modules for general lighting — Safety specifications
N/A
* The labeling "according to VDE 0108" is not meaningful, because it is not a ballast standard !
Specifications:
CEAG-Datas
Explanation:
V-CG-S2: >9,4 mA oder >12,7 mA = OK
No load current of the ballast
V-CG-S: >16 mA oder >47 mA = OK
(without tube or with defect tube) in V-CG-SE: >16 mA oder >47 mA = OK
DC-operation
V-CG-SUW:
>47 mA = OK
CG-K:
>16 mA oder >47 mA
= OK
selection aid for monitoring modules also for identification of
the max. luminaire quantity per circuit and the required
battery capacity.
these values are not allowed to be failed below def. limits for
the voltagerange of:
186 - 275V DC und 189 - 264 V AC
(for AT-S+ Systems must be the current draw sinusoidal
See DIN EN 61000-3-2, clause 7.3 a.)
V-CG-S2: <5,8 mA oder <7,9 mA = n.OK
voltage dependent = No load current
V-CG-S: <10 mA oder <28 mA = n.OK
of the ballast (without or with defect
V-CG-SK: <10 mA oder <28 mA = n.OK
LED module) in DC and AC V-CG-SUW:
<28 mA = n.OK
operation*:
CG-K:
<10 mA oder <28 mA = n.OK
selection aid for monitoring modules:
these values are not allowed to exceed the def. limits for the
voltagerange of:
186 - 275V DC und 189 - 264 V AC
(for AT-S+ Systems must be the current draw sinusoidal
(See DIN EN 61000-3-2, clause 7.3 a.)
Max. inrush current each
converter/luminaire in
AC-operation:
Max. permitted inrush current per circuit:
SKU 2 x 3A (CG) => 120 A
SKU 1 x 6A (CG) => 180 A
SKU 4 x 1,5A CG-S => 60 A
SKU 2 x 3A CG-S => 250 A
SKU 1 x 6A CG-S => 250 A
SOU CG-S // S+
=> 250 A
SU S+
=> 250 A
Lightoutput in
DC-operation at 186 V in comparison
to 230 V AC operation
-
Fulfilled: (Yes / No)
AC:YES, TO BE TESTED
WITH CEAG SYSTEM
DC: YES, TO BE TESTED
WITH CEAG SYSTEM
AC:YES, TO BE TESTED
WITH CEAG SYSTEM
DC: YES, TO BE TESTED
WITH CEAG SYSTEM
Describes the max. inrush current of all ballasts in a circuit, to
< 30 A / < 215 us
calculate the maximum contact rating of the circuit.
In battery operation of the ballast, for the light calculation
at 25 °C EBLF > 0,98 acc.
Datasheet
prep. Sniegon 07-2012 (7.2.2013)
luminaires, which are used for emergency lighting, must be according to the standard DIN EN 60598-2-22 (particular requirements - Luminaires for emergency
lighting) and DIN EN 62471 classification group 1 (Photobiological safety for lamps and lamp systems)
*Die Module der Baureihe V-CG-S überwachen die Stromaufnahme auf der Primärseite des Betriebsgerätes für LED-Module in den angegebenen Grenzen. Ausfälle einzelner
LEDs (niederohmig) auf der Sekundärseite führen nicht zwangsläufig zu einer Änderung der Stromaufnahme auf der Primärseite und können in diesen Fällen nicht als Fehler
detektiert werden.
**Vorschaltgerät schaltet oberhalb der Temperatur ta > 45°C ab (bei Volllast)
*The modules of the family V-CG-S can controll only the input current of the LED converters, in the above defined tolerances. Individual failures of LEDs (low resistive) on the
secudary side of the converters could also create input current values out of CEAG "definition", so that the CEAG modules on the input side of converters could produce wrong
informations for the emergency controlling station.
**ballast is switching off by temperature ta > 45°C (full load)
***)information to EN 60598-2-22 was not tested
page 1 of 2
CEAG - OT 50/220-240/24
c: Hummel/Sniegon
OSRAM
Manufacturer:
OSRAM GmbH
Marcel-Breuer-Str.6
D-80807 München
LED controlgear type
OT 50/220-240/24
Type / Description: Constant current LED controlgear
LED controlgear: OT 50/220-240/24
Max. inrush current for
ECG AC-operation
Values for load range
Ip = 30 A; TH = 215 µs
Maximum load 50W
IN
in AC-operation
(220-240 V)
IN
in DC-operation
(176-276 V)
INoLoad
in AC-operation
INoLoad
in DC-operation
270 mA (220V)
250 mA (240V)
266 mA (220V)
242 mA (240V)
34 mA (220V)
33 mA (240V)
28mA [ 176VDC ]
24 mA [ 240VDC ]
21 mA [ 276VDC ]
prep. Sniegon 07-2012 (7.2.2013)
CEAG - OT 50/220-240/24
c: Hummel/Sniegon
page 2 of 2
OSRAM