pdf

Description
Purpose and application
The LS/PD MULTI 3 A sensor detects the presence of persons
and measures the intensity of ambient light.
LS/PD MULTI 3 A
The sensor is available in two colours:
• LS/PD MULTI 3 A (anthracite)
LS/PD MULTI 3 A-w
• LS/PD MULTI 3 A-w (white)
The sensor is installed in luminaires or can be attached to
luminaires later using a clip (ideal for
T5/T8 louver luminaires).
Design
A
B C
The sensor is made up of the following components:
• Light sensor (A)
• Motion sensor (B)
• LED (C)
• Connection cable (D)
• Housing (E)
E
D
Light and motion sensor
Fitting instructions
Installation
Safety instructions
The sensor must only be installed and put into operation by
a qualified electrician. The applicable safety regulations and
accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the sensor when it is de-energised.
CAUTION!
Destruction of the sensor and other devices through
incorrect mounting!
• Only use OSRAM control units of the following
types: DALI MULTI 3/DIM MULTI 3, DALI
MULTIeco/MULTIeco, DALI PROFESSIONAL
Sensor Coupler.
• Do not connect control line with external voltage.
• Do not exceed the maximum total line length.
• Do not route the sensor line together with the
power or lamp line.
Connecting the sensor
Sensor
F
DALI MULTI 3
VI 2011
G
LSPD_MULTI3-A_A-w_ma1106_en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Connect the sensor using the supplied cable or a commercially
available 4-pin cable. If the cable is shortened or lengthened,
ensure that the wiring is correct.
Sensors can be connected in parallel via a Y-branch. For the
maximum number of sensors: see the separate control unit
manual.
F Y-branch
G Sensor
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083216535984
4008321653598
40083216536110
4008321653611
Page 1 of 2
Selecting the installation location
Installation (cont.)
H Monitoring cone: entire workplace; not on window surfaces.
I Avoid exposure to direct light.
80°
80°
K Avoid drafts (e.g. from ventilators or fans).
L Mounting distance = min. mounting height
H
I
K
>h
h
L
Mounting options
The sensor is suitable for installation in luminaires and for
retrofitting existing luminaires.
When retrofitted, the sensor is attached to the luminaire by
means of the included retaining clip (ideal for T5/T8 louver
luminaires).
Appendix
Technical data
Combined control and
supply connection
4-pin modular connection
(4p4c)
20
1: Supply voltage
2: L
ight measurement value
3: Motion signal
4: Signal ground
Length 2.1 m
3
22,20
37,70
Maximum total length of
signal line (incl. all connections to the control units)
See control unit
Insulation
Basic insulation as per IEC 664
Dimensions
(L x W x I)
37.70 x 20 x 22.20 mm
Light sensor detection area
20 – 600 lx (measured at
sensor),
opening angle approx. 90°
Motion detection area
Conical,
opening angle approx. 80°
Mounting height
2 – 4 m
The CE requirements to EN 60928 are fulfilled.
The EMC requirements to EN 61547 are fulfilled.
Conformity with the relevant EU directives is
confirmed by the CE symbol.
Page 2 of 2