Twin 70 Raceway: D-SRSP28--WW-ENG

Pan-Way ® Twin-70 Surface Raceway System
S P E C I F I C AT I O N S H E E T
specifications
Twin-70 non-metallic, multi-channel surface raceway is used to
route, protect, and conceal data, voice, fiber optic, and power
cabling. The raceway is listed as suitable for use in applications
up to 600 volts between connectors when screw secured and
installed per instructions. A full complement of fittings with a 1"
minimum bend radius is available as well as device brackets and
internal junction boxes to install a variety of communication and
electrical devices. The raceway provides two separate covers to
maintain total separation of power and low voltage cabling. The
Twin-70 raceway finish is pure in color and will resist scratches
and dents, and will not peel or corrode. Twin-70 raceway is
available in three standard colors and is optimized for use with
the Panduit® Pan-Net® Communication System.
technical information
Material:
Rigid PVC
Flammability:
UL94V-0; FT4
Voltage rating:
UL 600V / CSA 600V
Safety compliance:
UL Listed 95425 (raceway); UL Listed E116129 (fittings)
NEC:
Article 388
Capacity:
Multi-channel
Operating and
storage temperature:
0° to 50°C
Pan-Way ® Twin-70 Raceway
Raceway Bases
8 feet: 10 feet:
Raceway Covers
8 feet: 10 feet:
Divider Walls
8 feet: 10 feet:
T702BIW8
T702BIW10
T70CIW8
T70CIW10
T70DW8
T70DW10
Twin-70 Raceway Fittings
Base coupler:
Cover coupler:
Outside corner:
Inside corner:
Right angle:
End cap:
Entrance end:
Tee fitting:
Transition to T-70:
Transition to
LD/T-45:
Transition divider
insert:
T702BCIW-X
T70CCIW-X
T702OCIW
T702ICIW
T702RAIW
T702ECIW
T702EEIW
T702TIW
T702TRIW
T702TRLIW
T702TRI
Twin-70 Accessories
key features and benefits
Separate covers
throughout the system
Maintains complete separation of power and data cabling
systems and provides maximum safety during installation for
moves, adds, and changes
1" bend radius
control fittings
Cables in the raceway will satisfy the minimum 1" bend radius
requirement, preventing the potential degradation of cable
performance
Snap-on faceplates
Faceplates snap directly onto the raceway base; cabling can be
quickly accessed by removing only the faceplate, requiring less
labor and lowers the cost of maintenance
Designer profile
Maintains the same aesthetically pleasing profile of Panduit T-45,
T-70, and TG-70 raceway which allows all four systems to work
together or independently
Non-metallic
Lightweight, reducing installer fatigue and labor required to install
the raceway. Easy to cut with standard saws and saw blades,
eliminating the need for special cutting devices
Available in different
lengths, and colors
Available lengths – 8', 10'
Available colors – IW, EI, WH
Raceway is field paintable to match walls and surrounding décor.
applications
Pan-Way ® Twin-70 Surface Raceways are
designed to provide easy and economical
solutions for routing power and low voltage
cable in independent channels along
perimeter walls, baseboards or ceilings.
w w w. p a n d u it.c o m
This raceway is a perfect solution for schools,
hospitals, offices or anywhere high cable
capacity is required.
Wire retainer:
Device bracket:
Standard faceplate
bracket:
Three sided
hanging box:
GFCI three sided
hanging box:
Hanging box:
Spacer plate:
Fiber spool
bracket:
T70WR-X
T70DB-X
T70SDB-X
T70HB3-X
T70HB3GFCI-X
T70HB-X
T70S-X
T70FSB
For standard colors other than IW (Off White),
replace IW in part number with EI (Electrical
Ivory) or WH (White).
Pan-Way ® Twin-70 Surface Raceway System
Wire Fill
TWIN-70
Left Internal Area = 4.59 Sq. In.
Right Inrenal Area = 4.59 Sq. In.
Electrical Cables
14
AWG
12
AWG
Data Grade Cables
10
AWG
THHN/THWN/T90
Raceway Type
and
Configuration
Fill
Area
(in²)
0.111
0.130
0.164
MAX
MAX
MAX
(UL Temp Rise Test)
Twin-70: Power
and data (no
terminations)
24 AWG
23 AWG
26 AWG
23 AWG
Cat. 5e
Cat. 6
Cat. 6A (SD)
Cat. 6A
DIA = 0.193
DIA = 0.240
DIA = 0.240
FILL
FILL
FILL
FILL
Fiber Optic
Cable
Coax Cables
RG6
RG59/u
2 Strand
DIA = 0.300
DIA = 0.275
DIA = 0.242
DIA = 0.175
FILL
FILL
FILL
FILL
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
2.05
—
—
—
28
42
18
27
18
27
11
17
13
20
17
26
34
51
1.43
16
16
15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Twin-70: One
channel (no devices)
4.59
—
—
—
62
94
40
60
40
60
25
38
30
46
39
59
76
114
Twin-70: Data only
(Screw-On Faceplate)
3.11
—
—
—
42
63
27
41
27
41
17
26
20
31
27
40
51
77
Twin-70: Power only
(Screw-On Faceplate)
3.32
15
13
13
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Twin-70: Data only
(Snap-On Faceplate)
4.14
—
—
—
56
84
36
54
36
54
23
35
27
41
36
54
68
103
Twin-70: TVSS Power
(Snap-On Faceplate)
2.33
16
16
14
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Note: Cable diameters shown are industry averages and not necessarily Panduit specific, except for Cat. 6A (SD).
Tw i n - 7 0 L i n e a r t
T702B
T702B
ww w . p a n d u it.c o m
T70C
T70C
Pan-Way ® Twin-70 Surface Raceway System
Fittings and Accessories
T702BC-X
T70CC-X
T702OC
T702IC
T702RA
T702EC
T702EE
T702T
T702TR
T702TRL
T702TRI
T70WR-X
T70DB-X
T70SDB-X
T70HB3-X
T70HB3GFCI-X
T70HB-X
T70S-X
T70FSB
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT CANADA
Markham, Ontario
[email protected]
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK
[email protected]
Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore
[email protected]
Phone: 65.6305.7575
PANDUIT JAPAN
Tokyo, Japan
[email protected]
Phone: 81.3.6863.6000
PANDUIT LATIN AMERICA
Guadalajara, Mexico
[email protected]
Phone: 52.33.3777.6000
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
[email protected]
Phone: 61.3.9794.9020
For a copy of Panduit product warranties, log on to www.panduit.com/warranty