Trifab 601-601T-601UT Framing

Trifab 601, 601T and 601UT Framing Systems
®
Larger, more versatile span
delivers more thermal options
and more design choices
Designed to add increased thermal performance and value,
Kawneer’s new addition to the company’s trusted Trifab® platform
gives you more. More flexibility. More thermal options. More
design choices. Flexible enough for a wide range of building
projects, Trifab® 601 Series Framing Systems have a 6" depth, which
accommodates higher spans than conventional 4-1/2" storefront
framing systems. The new 3-in-1 series includes the non-thermal
Trifab® 601, the single thermal break Trifab® 601T and the dual
thermal break Trifab® 601UT. The greater system depth combined
with three thermal performance options make this one of the most
versatile framing systems available.
Performance
Trifab® 601 Series Framing Systems leverage Kawneer’s exclusive
dual IsoLock® lanced pour and debridge technology to provide
three levels of thermal performance – non-thermal, single thermal
break and dual thermal break. By combining the greater 6" depth
with superior thermal performance and versatility, Kawneer is able
to bridge the gap between traditional framing systems and low-rise
curtain walls.
Trifab® 601, 601T and 601UT framing systems are perfect for projects
where an economical alternative to a low-rise curtain wall is desired.
These systems meet the same high standards that are traditionally
found in Kawneer products for air and water infiltration and thermal
performance. Trifab® 601 Series Framing Systems also have an HP
(High Performance) sill design. The sill attaches to the sill flashing by
way of a raceway and eliminates the troublesome blind seal method
used on many flashing systems. The HP sill also includes a screwapplied end dam, which ensures positive and tight joints between
the sill flashing and end dam.
Fabrication and Installation
Trifab® 601, 601T and 601UT employ screw spline joinery construction
for efficient fabrication and installation. This construction method
provides quality joinery and allows for shop-controlled fabrication
and assembly, which leads to smaller field crews and less installation
time. The framing can be specified for glazing from either the
inside or outside. Inside glazing can help reduce field labor costs
by eliminating the need for exterior scaffolding or swing stages
for installation on floors above the ground level. In addition, the
frames have a two-piece receptor option that easily accommodates
attachment of air-barrier systems.
Aesthetics and Versatility
Trifab® 601
Trifab® 601T
Trifab® 601UT
Thermal simulations showing
temperature variations from exterior/
cold side to interior/warm side.
Performance
Test Standards
Air Performance
ASTM E 283
Water Performance
ASTM E 331
Uniform Static Structural
ASTM E 330
Sound Transmission Class (STC)AAMA 1801 and in accordance
with ASTM E 1425
Condensation Resistance (CRF)
AAMA 1503 and CAN/CSA-A440
Thermal Transmittance (U-Value)
AAMA 1503.1
U-Value Simulations for Other Glazing OptionsAAMA 507, NFRC 100, NFRS 200,
NFRC 500 and CAN/CSA-A440.2
Trifab® 601, 601T and 601UT Framing Systems are designed with
cost and flexibility in mind. With a 2" x 6" frame profile, the sightline
is consistent with current framing systems and the glass pockets are
aligned to the 4-1/2"-deep center set Trifab® framing systems. This
allows for a shallow horizontal member that not only lowers overall
metal costs, but also provides flexibility to accommodate interior
finishes, such as blinds, that can span the full uninterrupted elevation
height. The flexibility of the 3-in-1 series provides a pre-designed
solution for non-thermal as well as thermal entrances. Framing
options include non-thermal and thermally broken door framing
members to accommodate 1-3/4"-deep and 2-1/4"-deep entrance
doors, an expansion mullion and a two-piece head and jamb receptor.
The 6" depth accommodates higher spans than conventional 4-1/2"
storefront framing systems, and an optional 2-1/4" wide vertical
mullion allows for internal steel reinforcement for projects with greater
structural performance requirements.
For the Finishing Touch
Permanodic® anodized finishes are available in clear (Class I and
Class II) and color (Class I) choices, including champagne, black, light
bronze, medium bronze and dark bronze.
Painted finishes, including fluoropolymers that meet or exceed the
standards of AAMA 2605, are offered in many standard choices and
an unlimited number of specially designed colors.
Solvent-free powder coatings add the “green” element with
high performance, durability and scratch resistance that meet the
standards of AAMA 2604.
Kawneer Company, Inc.
Technology Park / Atlanta
555 Guthridge Court
Norcross, GA 30092
© Kawneer Company, Inc. 2012
kawneer.com
kawneergreen.com
770 . 449 . 5555
LITHO IN U.S.A.
Form No. 12-2158
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
Features
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
• TrifabTM 601/601T/601UT is 6" (152.4) deep with a 2" (50.8) sightline
•
•
•
•
•
•
•
•
Center Plane glass applications
Flush glazed from either the inside or outside
Screw Spline fabrication
Dual IsoLockTM lanced and debridged thermal break
Infill options up to 1-1/8" (28.6) thickness
High performance sill flashing
PermanodicTM anodized finishes in seven choices
Painted finishes in standard and custom choices
Optional Features
•
•
•
Acoustical rating per AAMA 1801 and ASTM E 1425
Project specific U-factors (See Thermal Charts)
Integrates with VersoleilTM SunShade Outrigger System and Horizontal Single Blade System
Product Applications
•
•
•
•
Storefront, Ribbon Window or Punched Openings
Single-span
Integrated entrance framing allowing Kawneer standard entrances or other specialty entrances to be incorporated
Kawneer windows or GLASSvent TM Windows are easily incorporated
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
• Profit$MakerTM Plus die sets available
For specific product applications,
Consult your Kawneer representative.
kawneer.com
ADMC070
1
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601/601T/601UT Framing System
BLANK PAGE
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
2
JANUARY, 2015
EC 97911-071
JANUARY, 2015
TrifabTM 601/601T/601UT Framing System
EC 97911-071
INDEX (CENTER)
BASIC FRAMING DETAILS (Outside Glazed)................................... 4
BASIC FRAMING DETAILS (Inside Glazed)...................................... 5
MISCELLANEOUS FRAMING............................................................. 6
CURVING............................................................................................. 7
CORNERS............................................................................................ 8
AATM250/425 THERMAL ENTRANCE DETAILS ................................ 9
350 STANDARD ENTRANCE DETAILS ........................................... 10
350 STANDARD ENTRANCE DETAILS
WITH CRIPPLE JAMBS......................................................... 11
GLASSvent TM WINDOW DETAILS.................................................... 12
8225TL THERMAL WINDOW DETAILS ............................................ 13
GLASSventTM UT WINDOW DETAILS .............................................. 14
WINDLOAD / DEADLOAD CHARTS ........................................... 15-22
THERMAL CHARTS .................................................................... 23-35
© Kawneer Company, Inc., 2013
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
3
kawneer.com
ADMC070
2
HORIZONTAL
2"
(50.8)
2"
(50.8)
4
JAMB
5
VERTICAL
3
SILL
ADMC070
2"
(50.8)
5
2
3
TrifabTM 601T IsoLockTM
THERMAL BREAK
TrifabTM 601UT DUAL IsoLockTM
THERMAL BREAK
SCREW SPLINE
451CG004
601CG021
451CG004
601CG014
601CG037
kawneer.com
© Kawneer Company, Inc., 2013
BASIC FRAMING DETAILS (CENTER - Outside Glazed)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601/601T/601UT Framing System
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
2"
(50.8)
1
HEAD
2"
(50.8)
ELEVATION IS NUMBER KEYED TO DETAILS
1/2"
(12.7)
SCALE 3" = 1'-0"
601CG002
4
601CG001
601CG001
601CG026
4
JANUARY, 2015
EC 97911-071
1
601CG026
601CG001
6"
(152.4)
1/2"
(12.7)
© Kawneer Company, Inc., 2013
kawneer.com
1
HEAD
2
HORIZONTAL
2"
(50.8)
2"
(50.8)
4
JAMB
5
VERTICAL
3
SILL
ADMC070
2"
(50.8)
ELEVATION IS NUMBER KEYED TO DETAILS
2"
(50.8)
EC 97911-071
2"
(50.8)
4
601CG002
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
SCALE 3" = 1'-0"
601CG001
601CG001
601CG026
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
JANUARY, 2015
TrifabTM 601/601T/601UT Framing System
TrifabTM 601T IsoLockTM
THERMAL BREAK
451CG004
5
BASIC FRAMING DETAILS (CENTER - Inside Glazed)
1
5
2
3
TrifabTM 601UT DUAL IsoLockTM
THERMAL BREAK
SCREW SPLINE
601CG026
601CG003
601CG004
6"
(152.4)
601CG011
601CG004
601CG014
601CG037
TrifabTM 601/601T/601UT Framing System
6
JANUARY, 2015
MISCELLANEOUS FRAMING (CENTER)
EC 97911-071
SCALE 3" = 1'-0"
601CG112
2-1/4" (57.2) MULLION
2-1/4" (57.2) MULLION
WITH STEEL
THERMAL
FLAT FILLER
TUBULAR
EXPANSION MULLION
WITH OPTIONAL STEEL
601UTCG216
601TCG216
601CG216
ULTRA THERMAL
FLAT FILLER
THERMAL POCKET
FILLER
601VG570
601CG001
601CG004
601CG026
601VG570
451VG573
601CG026
3"
(76.2)
451VG572
601CG026
601VG570
1"
(25.4)
1"
(25.4)
FLAT FILLER
601CG001
601VG174
REINFORCING
STANDARD
HEAD RECEPTOR
HEAVY WEIGHT
HEAD RECEPTOR
3/8"
(9.5)
3/4"
(19.1)
451VG572
2-3/4"
(69.9)
JAMB
RECEPTOR
601CG521
2"
(50.8)
3"
(76.2)
TUBULAR
EXPANSION MULLION
601CG001
STRAP ANCHOR
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
2" (50.8) HEAVY
WALL MULLION
2-1/2"
(63.5)
2-1/2"
(63.5)
2-1/4"
(57.2)
601CG001
2-1/4"
(57.2)
601TCG002
2"
(50.8)
400110
STEEL
REINFORCING
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
450110
STEEL
REINFORCING
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
601CG540
601CG010
601CG540
601CG002
601CG010
601CG112
601CG002
601CG002
601CG013
© Kawneer Company, Inc., 2013
2
kawneer.com
1/4"
(6.4)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
2"
(50.8)
TYPICAL
1
3/8"
(9.5)
1-5/16"
(33.3)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
JANUARY, 2015
TrifabTM 601/601T/601UT Framing System
EC 97911-071
CURVING
SCALE 3" = 1'-0"
1
3
2
CURVING DETAILS
601187
175186
175190
601188
6"
(152.4)
TYPICAL
175186
175190
601191
ADMC070
2"
(50.8)
3
7
1
2
1
OUTSIDE 90°
CORNER
3
4
INSIDE 135°
CORNER
ADMC070
4
5
NOTE: 1" (25.4) infill shown.
2
6" (152.4) MULLION POST
3
INSIDE 90°
CORNER
5
OUTSIDE 135°
CORNER
kawneer.com
© Kawneer Company, Inc., 2013
CORNERS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601/601T/601UT Framing System
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
8
JANUARY, 2015
EC 97911-071
SCALE 3" = 1'-0"
THESE DETAILS ARE TYPICAL FOR ALL 601, 601T, AND 601UT CONTITIONS.
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
AATM 250/425 THERMAL ENTRANCE DETAILS
SCALE 3" = 1'-0"
TrifabTM 601T FRAMING INCORPORATING KAWNEER "AATM250" DOORS.
NOTE: OTHER TYPES OF KAWNEER DOORS MAY BE USED WITH THIS FRAMING SYSTEM.
SEE ENTRANCE DETAILS FOR ADDITIONAL INFORMATION.
4A
HEAD
2
601TCG026
2"
(50.8)
1
601TCG001
6"
(152.4)
5
1-1/16"
(27)
3/8"
(9.5)
4
601137
3
BOTTOM
RAIL
2-1/2"
(63.5)
452138
3-7/8"
(98.4)
ELEVATION IS NUMBER KEYED
TO DETAILS.
Door Opening
Door Opening
TRANSOM
BAR
450022
2"
(50.8)
1/8"
(3.2)
2
3
601136
601136
452041
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
1
452138
452041
2"
(50.8)
4A
TRANSOM
JAMB
3/8"
(9.5)
5/8"
(15.9)
3/32"
(2.4)
2"
(50.8)
2-9/16"
(65.1)
2-1/2"
(63.5)
Door Opening
4
5
DOOR
JAMB
2-1/2"
(63.5)
MEETING
STILES
AATM 250/425 THERMAL DOOR
kawneer.com
1/4"
(6.4)
ADMC070
9
10
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
350 STANDARD ENTRANCE DETAILS
EC 97911-071
SCALE 3" = 1'-0"
601CG001
6"
(152.4)
1-1/16"
(27)
3/8"
(9.5)
1
4A
450022
TRANSOM
BAR
452038
Door Opening
5
3
601037
3-1/2"
(88.9)
2
4
2"
(50.8)
1/8"
(3.2)
2
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
601CG026
2"
(50.8)
TrifabTM 601 FRAMING INCORPORATING KAWNEER "350" DOORS.
NOTE: OTHER TYPES OF KAWNEER DOORS MAY BE USED WITH
THIS FRAMING SYSTEM.
1
SEE ENTRANCE DETAILS FOR ADDITIONAL INFORMATION.
HEAD
452041
452038
452041
2"
(50.8)
4A
DOOR
JAMB
3/8"
(9.5)
5/8"
(15.9)
3/32"
(2.4)
2"
(50.8)
3-1/2"
(88.9)
3-5/8"
(92.1)
Door Opening
4
1/8"
(3.2)
3-1/2"
(88.9)
5
DOOR
JAMB
MEETING
STILES
350 MEDIUM STILE DOOR
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
601036
11/16"
(17.5)
601036
6-1/2"
(165.1)
3
BOTTOM
RAIL
Door Opening
ELEVATION IS NUMBER KEYED
TO DETAILS.
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
11
350 STANDARD ENTRANCE DETAILS WITH CRIPPLE JAMBS
SCALE 3" = 1'-0"
601CG026
2"
(50.8)
TrifabTM 601 FRAMING INCORPORATING KAWNEER "350" DOORS.
NOTE: OTHER TYPES OF KAWNEER DOORS MAY BE USED WITH
THIS FRAMING SYSTEM.
SEE ENTRANCE DETAILS FOR ADDITIONAL INFORMATION.
1
HEAD
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
601CG001
6"
(152.4)
1-1/16"
(27)
3/8"
(9.5)
1
450022
TRANSOM
BAR
601020
Door Opening
5
3
3-1/2"
(88.9)
2
4
2"
(50.8)
1/8"
(3.2)
2
6-1/2"
(165.1)
11/16"
(17.5)
601018
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
3
BOTTOM
RAIL
Door Opening
ELEVATION IS NUMBER KEYED
TO DETAILS.
3/32"
(2.4)
2"
(50.8)
3-5/8"
(92.1)
3-1/2"
(88.9)
Door Opening
4
1/8"
(3.2)
3-1/2"
(88.9)
5
DOOR
JAMB
MEETING
STILES
350 MEDIUM STILE DOOR
kawneer.com
ADMC070
TrifabTM 601/601T/601UT Framing System
12
GLASSvent
TM
JANUARY, 2015
WINDOW for STOREFRONT FRAMING DETAILS
EC 97911-071
SCALE 3" = 1'-0"
OUTSWING CASEMENT
VERTICAL SECTION
PROJECT-OUT
VERTICAL SECTION
451CG004
601CG026
1
1
3
601CG001
469407
5
6
2
469407
3
7
8
4
469407
ELEVATION IS NUMBER KEYED TO DETAILS
469407
4
451CG004
451CG004
601CG014
601TCG037
469407
5
601CG001
601CG002
601CG001
601CG002
601CG002
601CG001
PROJECT-OUT
HORIZONTAL SECTION
469407
469407
6
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
OUTSWING CASEMENT
HORIZONTAL SECTION
601CG001
469407
7
8
NOTE: Black spacer is recommended when 1" (25.4) insulating glass is used.
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
601CG021
601CG026
2
601CG021
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601 FRAMING SHOWN.
OTHER FRAMING OPTIONS AVAILABLE.
CONSULT YOUR KAWNEER REPRESENTATIVE.
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
8225TL THERMAL WINDOWS
SCALE 3" = 1'-0"
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601T FRAMING SHOWN.
OTHER FRAMING OPTIONS AVAILABLE.
CONSULT YOUR KAWNEER REPRESENTATIVE.
PROJECT-OUT
VERTICAL SECTION
451CG004
601TCG021
8225TL THERMAL WINDOWS SHOWN
NOTE: OTHER VENT TYPES CAN BE
ACCOMMODATED, CONSULT YOUR KAWNEER
REPRESENTATIVE FOR OTHER OPTIONS
1
469407
1
4
3
2
ELEVATION IS NUMBER KEYED TO DETAILS
601TCG021
451CG004
2
PROJECT-OUT
HORIZONTAL SECTION
601TCG001
601TCG002
601TCG001
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
469407
601TCG002
469407
469407
3
kawneer.com
4
ADMC070
13
TrifabTM 601/601T/601UT Framing System
14
GLASSvent
TM
JANUARY, 2015
UT WINDOW DETAILS
EC 97911-071
SCALE 3" = 1'-0"
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601UT FRAMING SHOWN.
OTHER FRAMING OPTIONS AVAILABLE.
CONSULT YOUR KAWNEER REPRESENTATIVE.
PROJECT-OUT
VERTICAL SECTION
1
451CG004
601UTCG021
1-13/16"
(46)
2-1/4"
(57.2)
469407
D.L.O.
1
4
3
ELEVATION IS NUMBER KEYED TO DETAILS
469407
451CG004
NOTE:Black spacer is recommended when 1" (25.4) insulating glass is used.
2
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
1-13/16"
(46)
D.L.O.
2
2-1/4"
(57.2)
601UTCG021
PROJECT-OUT
HORIZONTAL SECTION
601UTCG001
601TCG002
601UTCG001
601TCG002
W.D.
1/8" (3.2)
C.W. D.L.O.
4-3/8"
(111.1)
469407
469407
1-13/16"
(46)
1-13/16"
(46)
2-1/4"
(57.2)
3
1/8" (3.2)
D.L.O.
D.L.O.
2-1/4"
(57.2)
W.D.
W.D.
C.W. D.L.O.
C.W. D.L.O.
ADMC070
4
1/8" (3.2)
kawneer.com
© Kawneer Company, Inc., 2013
W.D.
C.W. D.L.O.
1/8" (3.2)
GLASSventTM UT WINDOWS SHOWN
NOTE: OTHER VENT TYPES CAN BE
ACCOMMODATED, CONSULT YOUR KAWNEER
REPRESENTATIVE FOR OTHER OPTIONS
JANUARY, 2015
TrifabTM 601/601T/601UT Framing System
EC 97911-071
15
WIND LOAD / DEADLOAD CHARTS
Mullions are designed for deflection limitations in accordance with AAMA TIR-A11 of L\175 up to 13'-6" and L\240 + 1/4"
above 13'-6". These curves are for mullions WITH and WITHOUT HORIZONTALS and are based on engineering calculations for stress and deflection. Allowable wind load stress for ALUMINUM (assuming full lateral buckling support)
15,152 psi (104 MPa), FORMED STEEL 30,000 P.S.I. (207 MPa), STEEL BAR 20,000 psi (138 MPa). Charted curves, in all cases, are for the limiting value. If the design wind load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in allowable stress design. A 4/3 increase in
allowable stress has not been used to develop these curves. For special situations not covered by these curves, contact your Kawneer representative for additional information.
DEADLOAD CHARTS
Horizontal or deadload limitations are based upon 1/8" (3.2), maximum allowable deflection at the center of an
intermediate horizontal member. The accompanying charts are calculated for 1" (25.4) thick insulating glass or 1/4"
(6.35) thick glass supported on two setting blocks placed at the loading points shown.
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
WIND LOAD CHARTS
kawneer.com
ADMC070
TrifabTM 601/601T/601UT Framing System
14
11
A3.0
10
9
B
8
C
D
2.0
E
7
6
2
3
4
5
6
7
8
11
A
10
B
9
3.0
C
D
E
8
2.0
6
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
2.0
1.0
15
2.0
15
14
14
A3.0
9
B
8
C
D
2.0
E
7
6
5
4
1
2
3
4
5
6
7
HEIGHT IN FEET
11
10
HEIGHT IN METERS
12
4.0
13
12
11
A
10
B
9
C
D
E
8
7
601CG112
6
I = 5.495 (228.72 x 104)
S = 1.727 (28.30 x 103)
5
3.0
2.0
4
8
1
2
3
4
5
6
7
8
WIDTH IN FEET
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
1.0
HEIGHT IN METERS
4.0
13
HEIGHT IN FEET
12
WIDTH IN FEET
1.0
2.0
1.0
15
2.0
15
14
14
12
11
B
10
C
3.0
E
9
F
8
7
2.0
6
5
HEIGHT IN FEET
A
HEIGHT IN METERS
4.0
13
HEIGHT IN FEET
4.0
7
I = 5.431 (226.05 x 104)
S = 1.717 (28.14 x 103)
4
1
14
601CG001
5
2.0
13
A 4.0
12
B
11
C
E
3.0
F
10
9
8
601CG013
7
IA = 10.593 (440.91 x 104)
SA = 3.411 (55.90 x 103)
6
4
HEIGHT IN METERS
HEIGHT IN FEET
12
1.0
15
13
HEIGHT IN METERS
4.0
WIDTH IN METERS
2.0
5
4
1
2
3
4
5
6
7
8
1
WIDTH IN FEET
2
3
4
5
6
7
8
WIDTH IN FEET
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
15
WITHOUT HORIZONTALS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
2.0
13
EC 97911-071
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WIDTH IN METERS
1.0
601)
A = 20 PSF (960 Pa)
B = 30 PSF (1440 Pa)
C = 40 PSF (1920 Pa)
D = 45 PSF (2160 Pa)
E = 50 PSF (2400 Pa)
F = 60 PSF (2880 Pa)
WITH HORIZONTALS
JANUARY, 2015
HEIGHT IN METERS
WINDLOAD CHARTS (Trifab
TM
HEIGHT IN FEET
16
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
WINDLOAD CHARTS (TrifabTM 601)
A = 20 PSF (960 Pa)
B = 30 PSF (1440 Pa)
C = 40 PSF (1920 Pa)
D = 45 PSF (2160 Pa)
E = 50 PSF (2400 Pa)
WITH HORIZONTALS
WIDTH IN METERS
1.0
2.0
15
1.0
11
10
B
9
C
D
E
8
7
3.0
2.0
6
601CG112
WITH 450110 STEEL
14
4
1
2
3
4
5
6
7
8
C
D
E 3.0
10
9
8
2.0
6
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WIDTH IN METERS
WIDTH IN METERS
2.0
1.0
15
2.0
15
14
4.0
11
B
10
C3.0
D
E
9
8
HEIGHT IN FEET
12
4
2
3
4
5
6
7
8
B
11
C
D
E 3.0
10
9
8
2.0
6
601CG010
I = 10.570 (439.95 x 104)
S = 3.406 (55.81 x 103)
5
12
7
2.0
6
1
A4.0
13
HEIGHT IN METERS
A
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
1.0
HEIGHT IN METERS
14
2.0
1.0
15
2.0
15
13
12
4.0
B
11
C
3.0
D
E
10
9
8
7
2.0
6
4
1
2
3
4
5
6
7
4.0
13
601CG010
WITH 400110 STEEL
IA = 10.570 (439.95 x 104)
SA = 3.406 (55.81 x 103)
IS = 0.970 (40.37 x 104)
SS = 0.535 (8.77 x 103)
5
A
14
8
HEIGHT IN FEET
A
HEIGHT IN METERS
14
B
12
C
D
E
11
10
3.0
9
8
7
2.0
6
5
4
1
WIDTH IN FEET
2
3
4
5
6
WIDTH IN FEET
ADMC070
7
8
HEIGHT IN METERS
HEIGHT IN FEET
B
11
WITHOUT HORIZONTALS
1.0
HEIGHT IN FEET
12
WITH HORIZONTALS
7
© Kawneer Company, Inc., 2013
A4.0
IS = 1.929 (80.29 x 104)
SS = 0.935 (15.32 x 103)
WIDTH IN FEET
kawneer.com
13
7
IA = 5.495 (228.72 x 104)
SA = 1.727 (28.30 x 103)
5
2.0
15
HEIGHT IN FEET
12
HEIGHT IN METERS
A
13
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WIDTH IN METERS
4.0
13
HEIGHT IN FEET
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
14
WITHOUT HORIZONTALS
HEIGHT IN METERS
EC 97911-071
17
TrifabTM 601/601T/601UT Framing System
15
14
11
10
3.0
A
9
B
8
C
2.0
D
E
7
6
3
4
5
6
7
8
WIDTH IN FEET
14
12
11
A
10
B
3.0
9
C
D
E
8
7
2.0
6
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
2.0
1.0
15
2.0
15
14
4.0
11
10
3.0
A
9
B
8
C
D 2.0
E
7
6
2
3
4
5
6
7
8
WIDTH IN FEET
11
A
10
B
9
3.0
C
D
E
8
2.0
6
5
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
12
7
601TCG112
5
1
HEIGHT IN FEET
12
4.0
13
HEIGHT IN METERS
13
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
1.0
HEIGHT IN METERS
14
2.0
1.0
15
2.0
15
14
14
4.0
12
11
10
3.0
B
9
8
7
C
6
E
5
F
HEIGHT IN FEET
A
13
HEIGHT IN METERS
13
1
2
3
4
5
6
WIDTH IN FEET
7
8
601TCG013
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
ADMC070
4.0
12
B
11
C
10
9
3.0
E
F
8
7
2.0
4
A
HEIGHT IN METERS
HEIGHT IN FEET
4.0
WITH HORIZONTALS
1.0
HEIGHT IN FEET
2.0
13
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
2
1.0
15
601TCG001
5
1
WIDTH IN METERS
HEIGHT IN FEET
HEIGHT IN FEET
12
HEIGHT IN METERS
4.0
WITHOUT HORIZONTALS
2.0
6
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
kawneer.com
© Kawneer Company, Inc., 2013
2.0
13
EC 97911-071
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
WIDTH IN METERS
1.0
601T)
A = 20 PSF (960 Pa)
B = 30 PSF (1440 Pa)
C = 40 PSF (1920 Pa)
D = 45 PSF (2160 Pa)
E = 50 PSF (2400 Pa)
F = 60 PSF (2880 Pa)
WITH HORIZONTALS
JANUARY, 2015
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WINDLOAD CHARTS (Trifab
TM
HEIGHT IN METERS
18
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
WINDLOAD CHARTS (TrifabTM 601T)
A = 20 PSF (960 Pa)
B = 30 PSF (1440 Pa)
C = 40 PSF (1920 Pa)
D = 45 PSF (2160 Pa)
E = 50 PSF (2400 Pa)
WITH HORIZONTALS
WIDTH IN METERS
1.0
2.0
15
1.0
11
10
3.0
B
9
8
C
D 2.0
E
7
6
14
1
2
3
4
5
6
8
7
WIDTH IN FEET
9
8
2.0
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WIDTH IN METERS
WIDTH IN METERS
2.0
1.0
2.0
15
14
4.0
B
10
C
D
E
9
8
3.0
2.0
6
HEIGHT IN FEET
11
HEIGHT IN METERS
A
12
13
1
2
3
4
5
6
7
8
WIDTH IN FEET
4.0
B
11
C
D
3.0
E
10
9
8
2.0
6
5
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
12
7
601TCG010
5
A
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
1.0
HEIGHT IN METERS
14
2.0
1.0
15
2.0
15
14
A
14
A4.0
B
11
C
10
D
9
3.0
E
8
7
2.0
6
5
4
1
2
3
4
5
6
WIDTH IN FEET
7
8
HEIGHT IN FEET
12
4.0
13
HEIGHT IN METERS
13
601TCG010
WITH 400110 STEEL
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
ADMC070
B
12
C
D
E
11
10
3.0
9
8
7
2.0
6
5
4
1
2
3
4
5
6
7
WIDTH IN FEET
8
HEIGHT IN METERS
HEIGHT IN FEET
C3.0
D
E
10
5
15
HEIGHT IN FEET
B
11
WITHOUT HORIZONTALS
7
© Kawneer Company, Inc., 2013
12
WITH HORIZONTALS
1.0
kawneer.com
A4.0
6
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
13
7
601TCG112
WITH 450110 STEEL
5
2.0
15
HEIGHT IN FEET
A
HEIGHT IN METERS
12
13
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WIDTH IN METERS
4.0
13
HEIGHT IN FEET
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
14
WITHOUT HORIZONTALS
HEIGHT IN METERS
EC 97911-071
19
TrifabTM 601/601T/601UT Framing System
15
14
11
10
3.0
A
9
8
B
7
C 2.0
D
E
6
3
4
5
6
7
8
WIDTH IN FEET
14
12
11
A
10
3.0
9
B
C
D
E
8
7
2.0
6
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
2.0
1.0
15
2.0
15
14
4.0
11
10
3.0
A
9
8
B
7
C
D 2.0
E
6
2
3
4
5
6
7
8
WIDTH IN FEET
11
A
10
9
B
8
C
D
E
3.0
2.0
6
5
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
12
7
601UTCG112
5
1
HEIGHT IN FEET
12
4.0
13
HEIGHT IN METERS
13
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
1.0
HEIGHT IN METERS
14
2.0
1.0
15
2.0
15
14
14
4.0
A
11
10
B
3.0
9
8
C
7
E
F
6
5
4
1
2
3
4
5
6
WIDTH IN FEET
7
8
HEIGHT IN FEET
12
4.0
13
HEIGHT IN METERS
13
A
12
11
B
10
C
9
E
F
8
7
2.0
601UTCG013
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
ADMC070
3.0
HEIGHT IN METERS
HEIGHT IN FEET
4.0
WITH HORIZONTALS
1.0
HEIGHT IN FEET
2.0
13
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
2
1.0
15
601UTCG001
5
1
WIDTH IN METERS
HEIGHT IN FEET
HEIGHT IN FEET
12
HEIGHT IN METERS
4.0
WITHOUT HORIZONTALS
2.0
6
5
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
kawneer.com
© Kawneer Company, Inc., 2013
2.0
13
EC 97911-071
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
WIDTH IN METERS
1.0
601UT)
A = 20 PSF (960 Pa)
B = 30 PSF (1440 Pa)
C = 40 PSF (1920 Pa)
D = 45 PSF (2160 Pa)
E = 50 PSF (2400 Pa)
F = 60 PSF (2880 Pa)
WITH HORIZONTALS
JANUARY, 2015
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WINDLOAD CHARTS (Trifab
TM
HEIGHT IN METERS
20
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
WINDLOAD CHARTS (TrifabTM 601UT)
A = 20 PSF (960 Pa)
B = 30 PSF (1440 Pa)
C = 40 PSF (1920 Pa)
D = 45 PSF (2160 Pa)
E = 50 PSF (2400 Pa)
WITH HORIZONTALS
WIDTH IN METERS
1.0
2.0
15
1.0
14
11
10
B
9
3.0
C
D
E
8
7
2.0
6
HEIGHT IN FEET
A
5
3
4
5
6
7
8
WIDTH IN FEET
9
8
2.0
4
1
2
3
4
5
6
7
8
WIDTH IN FEET
WIDTH IN METERS
WIDTH IN METERS
2.0
1.0
2.0
15
14
4.0
11
B
10
C
D
E
9
3.0
8
2.0
6
5
2
3
4
5
6
7
4.0
8
WIDTH IN FEET
12
B
11
C
D
E
10
601UTCG010
WITH 400110 STEEL
3.0
9
8
7
2.0
6
5
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
1
HEIGHT IN FEET
12
HEIGHT IN METERS
A
A
13
4
1
3
2
4
5
6
7
8
WIDTH IN FEET
WITH HORIZONTALS
WITHOUT HORIZONTALS
WIDTH IN METERS
WIDTH IN METERS
1.0
HEIGHT IN METERS
14
2.0
1.0
15
2.0
15
14
14
4.0
11
A
10
3.0
B
9
8
C
D
2.0
E
7
6
5
4
1
2
3
4
5
6
WIDTH IN FEET
7
8
HEIGHT IN FEET
12
A 4.0
13
HEIGHT IN METERS
13
601UTCG112
WITH 450110 STEEL
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
ADMC070
12
B
11
C3.0
D
E
10
9
8
7
2.0
6
5
4
1
2
3
4
5
6
7
WIDTH IN FEET
8
HEIGHT IN METERS
HEIGHT IN FEET
C3.0
D
E
5
15
HEIGHT IN FEET
B
WITHOUT HORIZONTALS
7
© Kawneer Company, Inc., 2013
11
10
WITH HORIZONTALS
1.0
kawneer.com
12
6
WINDLOAD CHARTS ARE BASED ON
COMPOSITE PROPERTIES WHICH
ARE CALCULATED IN ACCORDANCE
WITH AAMA TIR-8 AND AAMA 505
4
2
4.0
A
7
601UTCG010
1
2.0
15
13
HEIGHT IN METERS
12
13
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WIDTH IN METERS
4.0
13
HEIGHT IN FEET
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
14
WITHOUT HORIZONTALS
HEIGHT IN METERS
EC 97911-071
21
TrifabTM 601/601T/601UT Framing System
22
JANUARY, 2015
DEADLOAD CHARTS
EC 97911-071
A = (1/4 POINT LOADING)
B = (1/6 POINT LOADING)
C = (1/8 POINT LOADING)
WIDTH IN METERS
WIDTH IN METERS
1.0
2.0
11
10
10
3.0
9
3.0
7
2.0
6
5
4
1.0
3
C
B
A
2
1
2
3
4
5
6
7
8
7
2.0
6
5
4
1.0
3
C
B
A
2
601CG011
0
1
HEIGHT IN FEET
8
1
601CG021
HEIGHT IN METERS
9
HEIGHT IN METERS
HEIGHT IN FEET
2.0
11
0
8
1
2
WIDTH IN FEET
3
4
5
6
7
8
WIDTH IN FEET
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
1.0
WIDTH IN METERS
1.0
WIDTH IN METERS
1.0
2.0
11
10
10
3.0
3.0
7
2.0
6
5
4
1.0
3
C
B
A
2
1
601037
HEADER / T-BAR
601079
C.O.C. HEADER /
T-BAR
0
8
7
2.0
6
5
4
1.0
3
C
B
A
2
1
HEIGHT IN METERS
8
HEIGHT IN FEET
9
HEIGHT IN METERS
9
HEIGHT IN FEET
2.0
11
0
1
2
3
4
5
6
7
8
1
WIDTH IN FEET
2
3
4
5
6
7
8
WIDTH IN FEET
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
A = (1/4 POINT LOADING)
B = (1/6 POINT LOADING)
C = (1/8 POINT LOADING)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Height limitations for transom glass over a doorway are based upon a 1/16" (1.6) maximum allowable deflection at the center of a transom bar.
The accompanying charts are calculated for 1" (25.4) thick insulating glass supported on two setting blocks placed at the loading points shown.
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL CHARTS
Generic Project Specific U-factor Example Calculation
(Percent of Glass will vary on specific products depending on sitelines)
15'-8"
2'-0"
9'-6"
7'-0"
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
5'-0"
Example Glass U-factor= 0.42 Btu/hr·ft2·oF
Total Daylight Opening = 3(5' x 7') + 3(5' x 2') = 135ft2
Total Projected Area
= (Total Daylight Opening + Total Area of Framing System)
= 15'-8" x 9'-6" = 148.83ft2
Percent of Glass
= (Total Daylight Opening ÷ Total Projected Area)
= (135 ÷ 148.83)100 = 91%
System U-factor vs Percent of Glass Area
0.80
0.70
0.65
X
E
COG
U-factor
0.55
M
0.48
0.46
0.44
0.42
0.40
0.38
0.36
0.34
0.32
0.30
0.28
0.26
0.24
0.22
0.20
0.50
P
0.45
L
0.40
E
© Kawneer Company, Inc., 2013
0.60
A
0.35
0.30
0.25
70
75
80
90
91%
85
0.20
95
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
0.75
Percent of Glass
Based on 91% glass and center of glass (COG) U-factor of 0.42
System U-factor is equal to 0.49 Btu/hr x ft2 x oF
kawneer.com
ADMC070
0.49
23
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL CHARTS
Note:
Values in parentheses are metric.
COG=Center of Glass.
Charts are generated per AAMA 507.
TrifabTM 601
0.47 (2.67)
0.46 (2.61)
0.44 (2.50)
0.42 (2.39)
0.40 (2.27)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
COG
U-factor
0.38 (2.16)
0.36 (2.05)
0.34 (1.93)
0.32 (1.82)
0.30 (1.71)
0.28 (1.59)
0.26 (1.48)
0.24 (1.37)
0.22 (1.25)
0.20 (1.14)
0.18 (1.02)
0.16 (0.91)
0.14 (0.79)
0.12 (0.68)
0.10 (0.57)
Vision Area / Total Area (%)
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
System U-Factor for Vision Glass
System U-Factor (Btu/h·ft2·°F)
24
System VT
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JANUARY, 2015
kawneer.com
TrifabTM 601/601T/601UT Framing System
EC 97911-071
COG
SHGC
COG
VT
Vision Ares / Total Area (%)
Charts are generated per AAMA 507.
ADMC070
25
THERMAL CHARTS
TrifabTM 601
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
Vision Area / Total Area (%)
Charts are generated per AAMA 507.
TrifabTM 601
System Visible Transmittance (VT) vs Percent of Vision Area
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
THERMAL PERFORMANCE MATRIX (NFRC SIZE)
EC 97911-071
TrifabTM 601
Overall U-Factor 4
0.48
0.68
0.46
0.67
0.44
0.66
0.42
0.64
0.40
0.63
0.38
0.61
0.36
0.59
0.34
0.58
0.32
0.56
0.30
0.55
0.28
0.53
0.26
0.52
0.24
0.50
0.22
0.48
0.20
0.47
0.18
0.45
0.16
0.44
0.14
0.42
0.12
0.40
0.10
0.39
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
2000mm wide by 2000mm high (78-3/4" by 78-3/4").
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Glass U-Factor 3
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Thermal Transmittance 1 (BTU/hr • ft 2 • °F)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
26
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL CHARTS
TrifabTM 601
TrifabTM 601
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
SHGC Matrix 2
Visible Transmittance 2
Glass SHGC 3
Overall SHGC 4
Glass VT 3
Overall VT 4
0.75
0.68
0.75
0.66
0.70
0.63
0.70
0.61
0.65
0.59
0.65
0.57
0.60
0.55
0.60
0.53
0.55
0.50
0.55
0.48
0.50
0.46
0.50
0.44
0.45
0.41
0.45
0.39
0.40
0.37
0.40
0.35
0.35
0.33
0.35
0.31
0.30
0.28
0.30
0.26
0.25
0.24
0.25
0.22
0.20
0.19
0.20
0.18
0.15
0.15
0.15
0.13
0.10
0.11
0.10
0.09
0.05
0.06
0.05
0.04
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
2000mm wide by 2000mm high (78-3/4" by 78-3/4").
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
NOTE: For glass values that are not listed, linear interpolation is permitted.
kawneer.com
ADMC070
27
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL CHARTS
Note:
Values in parentheses are metric.
COG=Center of Glass.
Charts are generated per AAMA 507.
TrifabTM 601T
COG
U-factor
0.47 (2.67)
0.46 (2.61)
0.42 (2.39)
0.40 (2.27)
0.38 (2.16)
0.36 (2.05)
0.34 (1.93)
0.32 (1.82)
0.30 (1.71)
0.28 (1.59)
0.26 (1.48)
0.24 (1.37)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
0.44 (2.50)
0.22 (1.25)
0.20 (1.14)
0.18 (1.02)
0.16 (0.91)
0.14 (0.79)
0.12 (0.68)
0.10 (0.57)
Vision Area / Total Area (%)
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
System U-Factor for Vision Glass
System U-Factor (Btu/h·ft2·°F)
28
System VT
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JANUARY, 2015
kawneer.com
TrifabTM 601/601T/601UT Framing System
EC 97911-071
COG
SHGC
COG
VT
Vision Ares / Total Area (%)
Charts are generated per AAMA 507.
ADMC070
29
THERMAL CHARTS
TrifabTM 601T
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
Vision Area / Total Area (%)
Charts are generated per AAMA 507.
TrifabTM 601T
System Visible Transmittance (VT) vs Percent of Vision Area
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
THERMAL PERFORMANCE MATRIX (NFRC SIZE)
EC 97911-071
TrifabTM 601T
Overall U-Factor 4
0.48
0.55
0.46
0.54
0.44
0.53
0.42
0.51
0.40
0.50
0.38
0.48
0.36
0.46
0.34
0.45
0.32
0.43
0.30
0.42
0.28
0.40
0.26
0.38
0.24
0.37
0.22
0.35
0.20
0.34
0.18
0.31
0.16
0.30
0.14
0.28
0.12
0.26
0.10
0.25
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
2000mm wide by 2000mm high (78-3/4" by 78-3/4").
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Glass U-Factor 3
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Thermal Transmittance 1 (BTU/hr • ft 2 • °F)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
30
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL CHARTS
TrifabTM 601T
TrifabTM 601T
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
SHGC Matrix 2
Visible Transmittance 2
Glass SHGC 3
Overall SHGC 4
Glass VT 3
Overall VT 4
0.75
0.66
0.75
0.66
0.70
0.62
0.70
0.61
0.65
0.58
0.65
0.57
0.60
0.53
0.60
0.53
0.55
0.49
0.55
0.48
0.50
0.44
0.50
0.44
0.45
0.40
0.45
0.39
0.40
0.36
0.40
0.35
0.35
0.31
0.35
0.31
0.30
0.27
0.30
0.26
0.25
0.23
0.25
0.22
0.20
0.18
0.20
0.18
0.15
0.14
0.15
0.13
0.10
0.09
0.10
0.09
0.05
0.05
0.05
0.04
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
2000mm wide by 2000mm high (78-3/4" by 78-3/4").
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
NOTE: For glass values that are not listed, linear interpolation is permitted.
kawneer.com
ADMC070
31
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL CHARTS
Note:
Values in parentheses are metric.
COG=Center of Glass.
Charts are generated per AAMA 507.
TrifabTM 601UT
COG
U-factor
0.47 (2.67)
0.46 (2.61)
0.44 (2.50)
0.40 (2.27)
0.38 (2.16)
0.36 (2.05)
0.34 (1.93)
0.32 (1.82)
0.30 (1.71)
0.28 (1.59)
0.26 (1.48)
0.24 (1.37)
0.22 (1.25)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
0.42 (2.39)
0.20 (1.14)
0.18 (1.02)
0.16 (0.91)
0.14 (0.79)
0.12 (0.68)
0.10 (0.57)
Vision Area / Total Area (%)
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
System U-Factor for Vision Glass
System U-Factor (Btu/h·ft2·°F)
32
System VT
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JANUARY, 2015
kawneer.com
TrifabTM 601/601T/601UT Framing System
EC 97911-071
COG
SHGC
COG
VT
Vision Ares / Total Area (%)
Charts are generated per AAMA 507.
ADMC070
33
THERMAL CHARTS
TrifabTM 601UT
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
Vision Area / Total Area (%)
Charts are generated per AAMA 507.
TrifabTM 601UT
System Visible Transmittance (VT) vs Percent of Vision Area
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
THERMAL PERFORMANCE MATRIX (NFRC SIZE)
EC 97911-071
TrifabTM 601UT
Overall U-Factor 4
0.48
0.53
0.46
0.52
0.44
0.50
0.42
0.48
0.40
0.47
0.38
0.45
0.36
0.44
0.34
0.42
0.32
0.40
0.30
0.39
0.28
0.37
0.26
0.36
0.24
0.34
0.22
0.32
0.20
0.31
0.18
0.28
0.16
0.27
0.14
0.25
0.12
0.24
0.10
0.22
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
2000mm wide by 2000mm high (78-3/4" by 78-3/4").
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Glass U-Factor 3
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Thermal Transmittance 1 (BTU/hr • ft 2 • °F)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
34
TrifabTM 601/601T/601UT Framing System
JANUARY, 2015
EC 97911-071
THERMAL PERFORMANCE MATRIX (NFRC SIZE)
TrifabTM 601UT
TrifabTM 601UT
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
SHGC Matrix 2
Visible Transmittance 2
Glass SHGC 3
Overall SHGC 4
Glass VT 3
Overall VT 4
0.75
0.67
0.75
0.66
0.70
0.62
0.70
0.61
0.65
0.58
0.65
0.57
0.60
0.53
0.60
0.53
0.55
0.49
0.55
0.48
0.50
0.45
0.50
0.44
0.45
0.40
0.45
0.39
0.40
0.36
0.40
0.35
0.35
0.31
0.35
0.31
0.30
0.27
0.30
0.26
0.25
0.23
0.25
0.22
0.20
0.18
0.20
0.18
0.15
0.14
0.15
0.13
0.10
0.10
0.10
0.09
0.05
0.05
0.05
0.04
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
2000mm wide by 2000mm high (78-3/4" by 78-3/4").
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
NOTE: For glass values that are not listed, linear interpolation is permitted.
kawneer.com
ADMC070
35
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
TrifabTM 601/601T/601UT Framing System
BLANK PAGE
ADMC070
kawneer.com
© Kawneer Company, Inc., 2013
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
36
JANUARY, 2015