A. Input Characteristics: 1) Voltage: 400VAC, 3ØY 2) Frequency: 50/60 Hz. 3) Line Current: 16A Maximum 4) Load Capacity: 11.04 KVA 5) Overload Protection: (3) 1P/16A UL489 Circuit Breaker 6) Power Cord: 10' (3m), #12AWG(3.3mm 2 )/5C 7) Connector: IEC309-16A 8) Indicators: Power-on, LED B. Output Characteristics: 1) Voltage: 230 VAC 2) Current: 16A/Phase (Total Connected Load) 3) Outlets: 3X 6 IEC C13 C. Mechanical Characteristics: L3 L2 1) Material: CRS N 2) Finish: Powder Coat, Black, Fine Texture L1 3) Lettering: Silk-Screen, White/Epoxy 4) Storage Temp.: -(13) - 149F (-25 - 65C) D. Operating Environment: IEC309-16A 1) Temperature: 32 - 122F (0 - 50C) 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) 1 REV 33 in / 838.2 mm CHANGE NOTICE INFORMATIONAL LABEL 01130-SPMS 2) RoHS: Compliant to Directive 2002/95/EC 1.73 in / 43.9 mm 1) Safety Agency: UL/cUL, UL60950-1, CE 3.25 in / 82.6 mm E. Regulatory Conformance: DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 ANGLES ± 030' DATE 2/22/2008 Spectrum Management Systems 18X C13, 3PH-WYE, 0U PDU THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-148BXREN-00 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA