A. Input Characteristics: 1) Voltage: 400VAC, 3ØY 2) Frequency: 50/60 Hz. 3) Line Current: 16A Maximum 4) Load Capacity: 11.04 KVA 5) Power Cord: 10' (3m), #12AWG(3.3mm )/5C 6) Connector: IEC309-16A 7) Indicators: Power-on, LED 8) Transient Voltage Suppression (TVS) 9) Integral EMI Filter B. Output Characteristics: 1) Voltage: 230 VAC 2) Current: 16A/Phase (Total Connected Load) 3) Outlets: 3X 6 IEC C13 4) Overload Protection: (3) 2P/16A UL489 Circuit Breaker C. Mechanical Characteristics: 1) Material: CRS 2) Finish: Powder Coat, Black, Fine Texture 3) Lettering: Silk-Screen, White/Epoxy 4) Storage Temp.: -(13) - 149F (-25 - 65C) D. Operating Environment: 1) Temperature: 32 - 122F (0 - 50C) PLUG, IEC309-16A 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) E. Regulatory Conformance: 1) Safety Agency: UL/cUL, UL60950-1, CE 66.00 in / 1676.4 mm 2) RoHS: Compliant to Directive 2002/95/EC 69.00 in / 1752.6 mm 3.25 in / 82.6 mm REV CHANGE NOTICE CN-002298-SPMS 02 1.69 in / 42.9 mm DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: schoend TOLERANCES UNLESS OTHERWISE SPECIFIED: DECIMAL .X ± .050 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 DATE 9/14/2010 ANGLES ± 030' Spectrum Management Systems 400V,WYE,16A,3(6/C13),TVS,FLTR THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-116BXREN-10 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA