72A 116BXREN 10

A. Input Characteristics:
1) Voltage: 400VAC, 3ØY
2) Frequency: 50/60 Hz.
3) Line Current: 16A Maximum
4) Load Capacity: 11.04 KVA
5) Power Cord: 10' (3m), #12AWG(3.3mm )/5C
6) Connector: IEC309-16A
7) Indicators: Power-on, LED
8) Transient Voltage Suppression (TVS)
9) Integral EMI Filter
B. Output Characteristics:
1) Voltage: 230 VAC
2) Current: 16A/Phase (Total Connected Load)
3) Outlets: 3X 6 IEC C13
4) Overload Protection: (3) 2P/16A UL489 Circuit Breaker
C. Mechanical Characteristics:
1) Material: CRS
2) Finish: Powder Coat, Black, Fine Texture
3) Lettering: Silk-Screen, White/Epoxy
4) Storage Temp.: -(13) - 149F (-25 - 65C)
D. Operating Environment:
1) Temperature: 32 - 122F (0 - 50C)
PLUG, IEC309-16A
2) Relative Humidity: 0 - 95% (Non-Condensing)
3) Elevation: 0 - 10,000FT (0 - 3000 m)
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, UL60950-1, CE
66.00 in / 1676.4 mm
2) RoHS: Compliant to Directive 2002/95/EC
69.00 in / 1752.6 mm
3.25 in / 82.6 mm
REV
CHANGE NOTICE
CN-002298-SPMS
02
1.69 in / 42.9 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
schoend
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
DECIMAL .X ± .050
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
DATE
9/14/2010
ANGLES ± 030'
Spectrum
Management Systems
400V,WYE,16A,3(6/C13),TVS,FLTR
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-116BXREN-10
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA