72A 148BXOGN 00

A. Input Characteristics:
1) Voltage: 400 VAC,3ØY
2) Frequency: 50/60 Hz.
3) Line Current: 16A Maximum
4) Load Capacity: 11.04 KVA
5) Overload Protection: (3) 1P/16A UL489 Circuit Breaker
6) Power Cord: 10' (3m), #12AWG(3.3mm 2 )/5C
7) Connector: IEC309-16A
8) Indicators: Power on, LED
B. Output Characteristics:
1) Voltage: 230VAC
2) Current: 16A/ Phase (Total Connected Load)
3) Outlets: 3X (4-IEC C13, 1-IEC C19)
C. Mechanical Characteristics:
1) Material: CRS
2) Finish: Powder Coat, Black, Fine Texture
L3
L2
3) Lettering: Silk-Screen, White/Epoxy
N
4) Storage Temp.: -(13) - 149F (-25 - 65C)
L1
D. Operating Environment:
1) Temperature: 32 - 122F (0 - 50C)
IEC309-16A
2) Relative Humidity: 0 - 95% (Non-Condensing)
3) Elevation: 0 - 10,000FT (0 - 3000 m)
E. Regulatory Conformance:
3.25 in / 82.6 mm
1) Safety Agency: UL/cUL, UL60950-1, CE
1.73 in / 43.9 mm
2) RoHS: Compliant to Directive 2002/95/EC
CHANGE NOTICE
0
0243-ENG
REV
33 in / 838.2 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
CarrS
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
FRACTIONS ±1/64
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
ANGLES ± 030'
DATE
2/22/2008
Spectrum
Management Systems
12x c13, 3x c19, 3PH-WYE, 0U PDU
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-148BXOGN
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA