72RA260BVFFN 00

A. Input Characteristics:
1) Voltage: 200-240V
2) Frequency: 50/60 Hz.
3) Current: 24A Maximum
4) Load Capacity: 14.400 KVA Total Between Both Groups
5) Overload Protection: (4) 2P/20A & (2) 1P/20A UL489 Circuit Breakers
6) Power Cord: 3' (.914m), 10/3 cord
7) Connector: Side A = L6-30P,Side B = L14-30P
B. Output Characteristics:
1) Voltage: 120VAC NEMA 5-20R,240VAC IEC C19
2) Current: 24A (Total Connected Load) Per Power Group
3) Outlets: 4 IEC C19, 2X NEMA 5-20R
19 in / 482.6 mm
C. Mechanical Characteristics:
1) Material: CRS/G40 Galv. Coating
2) Finish: Powder Coat, Black, Fine Texture
3) Lettering: Silk-Screen, White/Epoxy
4) Storage Temp.: -(25) - 149C (-25 - 65C)
D. Operating Environment:
1) Temperature: 32 - 122F (0 - 50C)
2) Relative Humidity: 0 - 95% (Non-Condensing)
3) Elevation: 0 - 10,000FT (0 - 3000 m)
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1
6.5 in / 165.1 mm
1.72 in / 43.7 mm
2) RoHS: Compliant to Directive 2002/95/EC
CHANGE NOTICE
1
9251-ENG
REV
17 in / 431.8 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
DeVierR
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
FRACTIONS ±1/64
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
DATE
5/22/2009
ANGLES ± 030'
Spectrum
Management Systems
1RU,208VAC DUAL 1/P
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72RA260BVFFN-00
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA