PDF cURus UL 60950-1, CSA 60950-1

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date
Issued to:
This is to certify that
representative samples of
20121130-E123535
E123535-A3-UL
2012-NOVEMBER-30
VICOR CORP
25 FRONTAGE RD
ANDOVER MA 01810
Power Supplies for Information Technology Equipment
Including Electrical Business Equipment
AC-DC Converter, PFC MegaPAC Series, See
Miscellaneous Enclosure for model matrix
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety:
Additional Information:
UL 60950-1, CSA C22.2 No. 60950-1-07, (Information
Technology Equipment - Safety - Part 1: General
Requirements)
See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Recognized Component Mark should be considered as being
covered by UL's Recognition and Follow-Up Service.
The UL Recognized Component Mark generally consists of the manufacturer’s identification and
catalog number, model number or other product designation as specified under “Marking” for the
particular Recognition as published in the appropriate UL Directory. As a supplementary means of
identifying products that have been produced under UL’s Component Recognition Program, UL’s
Recognized Component Mark: , may be used in conjunction with the required Recognized Marks.
The Recognized Component Mark is required when specified in the UL Directory preceding the
recognitions or under “Markings” for the individual recognitions.
Recognized components are incomplete in certain constructional features or restricted in
performance capabilities and are intended for use as components of complete equipment submitted
for investigation rather than for direct separate installation in the field. The final acceptance of the
component is dependent upon its installation and use in complete equipment submitted to UL LLC.
Look for the UL Recognized Component Mark on the product.
William R. Carney, Director, North American Certification Programs
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus
Page 1 of 1
Issue Date:
2012-11-28
Page 1 of 8
Report Reference #
E123535-A3-UL
UL TEST REPORT AND PROCEDURE
Standard:
Certification Type:
CCN:
UL 60950-1, 2nd Edition, 2011-12-19 (Information Technology
Equipment - Safety - Part 1: General Requirements)
CSA C22.2 No. 60950-1-07, 2nd Edition, 2011-12 (Information
Technology Equipment - Safety - Part 1: General Requirements)
Component Recognition
QQGQ2, QQGQ8 (Power Supplies for Information Technology
Equipment Including Electrical Business Equipment)
Product:
Model:
AC-DC Converter
PFC MegaPAC Series
Rating:
See Miscellaneous Enclosure for model matrix.
115-230Vac or 300Vdc
47-500Hz
Output Voltage: 1-95Vdc
Rated Output Current: 15A Max.
Output Power: 2400Wmax
See Miscellaneous Enclosure for model details.
Applicant Name and Address:
VICOR CORP
25 FRONTAGE RD
ANDOVER MA 01810
UNITED STATES
This is to certify that representative samples of the products covered by this Test Report have been investigated in accordance with the
above referenced Standards. The products have been found to comply with the requirements covering the category and the products are
judged to be eligible for Follow-Up Service under the indicated Test Procedure. The manufacturer is authorized to use the UL Mark on
such products which comply with this Test Report and any other applicable requirements of UL LLC ('UL') in accordance with the FollowUp Service Agreement. Only those products which properly bear the UL Mark are considered as being covered by UL's Follow-Up
Service under the indicated Test Procedure.
The applicant is authorized to reproduce the referenced Test Report provided it is reproduced in its entirety.
UL authorizes the applicant to reproduce the latest pages of the referenced Test Report consisting of the first page of the Specific
Technical Criteria through to the end of the Conditions of Acceptability.
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL.
Prepared by:
Gerard Soprych
Reviewed by: Daniel Pirozzi
Copyright © 2012
Issue Date:
2012-11-28
Page 2 of 8
Report Reference #
E123535-A3-UL
Supporting Documentation
The following documents located at the beginning of this Procedure supplement the requirements of this Test
Report:
A. Authorization - The Authorization page may include additional Factory Identification Code markings.
B. Generic Inspection Instructions i. Part AC details important information which may be applicable to products covered by this Procedure.
Products described in this Test Report must comply with any applicable items listed unless otherwise
stated in the body of this Test Report.
ii. Part AE details any requirements which may be applicable to all products covered by this Procedure.
Products described in this Test Report must comply with any applicable items listed unless otherwise
stated in the body of each Test Report.
iii. Part AF details the requirements for the UL Certification Mark which is not controlled by the technical
standard used to investigate these products. Products are permitted to bear only the Certification
Mark(s) corresponding to the countries for which it is certified, as indicated in each Test Report.
Product Description
The PFC MegaPAC is an AC-DC/DC-DC chassis based configurable power supply that includes an EMI
filter, a single phase power factor corrected front end, cooling fan, and 8 output slots that can provide up to
32 outputs. The PFC MegaPAC accepts a 100-240 Vac or 300Vdc input and the output slots are populated
with ConverterPACs or FlexPAC subassemblies. The ConverterPACs are constructed with the Vicor
Corporation VI-J, VI-200, or 2nd Gen FastTrak series of modules. The FlexPAC is an approved component
that can provide up to 4 outputs totaling 200W max.
The PFC MegaPAC is designed for building-in and can provide a maximum output power of 2400Wmax. The
product is for use with Information Technology Equipment. The baseplate temperature of the Vicor modules
should be monitored in the end product.
Model Differences
See Miscellaneous Enclosure for model nomenclature.
Issue Date:
2012-11-28
Page 3 of 8
Report Reference #
E123535-A3-UL
Technical Considerations

Equipment mobility : for building-in

Connection to the mains : not directly connected to mains

Operating condition : continuous

Access location : building-in

Over voltage category (OVC) : OVC II

Mains supply tolerance (%) or absolute mains supply values : 15-230Vac or 300Vdc

Tested for IT power systems : No

IT testing, phase-phase voltage (V) : -

Class of equipment : Class I (earthed)

Considered current rating of protective device as part of the building installation (A) : 20A

Pollution degree (PD) : PD 2

IP protection class : IP X0

Altitude of operation (m) : less than 2000

Altitude of test laboratory (m) : less than 2000

Mass of equipment (kg) : MP Chassis(4.42kg), Mx Chassis(4.54kg)

The product was submitted and evaluated for use at the maximum ambient temperature (Tma)
permitted by the manufacturer’s specification of: maximum baseplate temperature of the 1st Gen VI200 and BatMod Modules is 85°C maximum baseplate temperature of the VI-J and 2nd Gen
FasTrack Modules is 100°C. maximum case temperature of FlexPAC is 50°C.
Issue Date:
2012-11-28
Page 4 of 8
Report Reference #
E123535-A3-UL
Engineering Conditions of Acceptability
For use only in or with complete equipment where the acceptability of the combination is determined by UL
LLC. When installed in an end-product, consideration must be given to the following:

The following Production-Line tests are conducted for this product: Electric Strength

The end-product Electric Strength Test is to be based upon a maximum working voltage of: PrimaryEarthed Dead Metal: 264 Vrms, Primary-SELV: 400 Vpk

The power supply terminals and/or connectors are: Not investigated for field wiring

The investigated Pollution Degree is: 2

The following end-product enclosures are required: Mechanical, Fire, Electrical

The PFC MegaPAC is designed for building-in and must be installed in accordance with the
manufacturer’s instructions.

The maximum baseplate temperature of the 1st Gen VI-200 and BatMod Modules is 85°C.

The maximum baseplate temperature of the VI-J and 2nd Gen FasTrack Modules is 100°C

The maximum case temperature of FlexPAC is 50°C.

Series or single output voltages less than 60 Vdc meet the requirements of SELV.

Series or single output voltages above 60 Vdc are non-SELV and should be considered hazardous
secondary.

VI-J outputs are limited to less than 40 Vdc to be considered SELV.

Outputs greater than 240 VA should be considered hazardous energy.

An external fuse, Bussmann ABC-15, or Littelfuse 505 series rated 15A was used during fault
testing.
Additional Information
N/A
PFC MegaPAC Series: Model Mpaa-zbbcccccc-v-xx (Mp may be replaced by IMp)
Item 0. M = MegaPAC, constant
Item 1. Module Configurations
st
p = P when populated with 1 Gen Vicor Modules or FlexPACs
st
nd
p = X when populated with any combination of 1 or 2 Gen Vicor Modules or FlexPACs
Item 2. Number of Outputs
aa = any number 0 – 32
Item 3. MegaPAC Type
z = 7 for PFC MegaPAC
Item 4. Number of Modules & FlexPACs
bb = any number 0 – 16
Item 5. Factory assigned Code (Optional, non-safety related)
cccccc = any alphanumeric combination of up to 6 characters
Item 6. MegaPAC configuration Revision (Optional, non-safety related)
v = any alphanumeric combination
(note: v = G for RoHs)
Item 7. MegaPAC chassis description (Optional, non-safety related)
xx = any alphanumeric combination
(note: xx = EL for Extended Length)
(note: xx = LL for Low Leakage)
(note: xx = MI for Mil COTs)
Example
MX1-743463-G
M = Constant, MegaPAC series
st
nd
X = X, unit populated with any combination of 1 or 2 Gen Vicor DC-DC Modules or FlexPACs
1 = single output configuration
7 = PFC
4 = Number of Vicor modules & FlexPACs
3463 = factory assigned code (non safety related)
G = RoHs compliant