PDF cURus UL 60950-1, CSA 60950-1

1285 Walt
Whitman Road
Melville, New
York 11747-3081
(516) 271-6200
FAX No. (516)
271-8259/8260
http://www.ul.co
m
File E123535
Project 98ME11255
March 9, 1998
REPORT
ON
COMPONENT - POWER SUPPLIES,
INFORMATION TECHNOLOGY EQUIPMENT
INCLUDING ELECTRICAL BUSINESS EQUIPMENT
Westcor, Div. of Vicor Corp.
Sunnyvale, CA
Copyright © 1998 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce this Report provided it is reproduced in its entirety.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce that portion of this Report consisting of this Cover Page through
Page 2.
File E123535
Vol. 2
Sec. 7
and Report
Page 1
Issued:
Revised:
1998-03-09
2010-08-16
DESCRIPTION
PRODUCT COVERED:
USR, CNR - Component AC-DC Switching Power Supply, PFC Mini Series,
Model PMw-xyq-zzz-r-v. The power supply is for use with data processing
equipment, office appliances, and business equipment.
PFC Mini Series Model PMw-xyq-zzz-r-v
w = Total number of outputs, maximum of 9, each output can be 0-95 V dc
x = Total number of VI-200 and/or VI-J00 Series DC/DC Converters
y = Total number of 2nd Gen Fastrack DC-DC Converters and/or discrete
regulated outputs
q = Optional, standard part designator, non-safety related, any
alphanumeric character or blank
r = Optional, denotes revision to original configuration if applicable,
any alphanumeric or blank, r = G to denote RoHS compliance
z = Factory assigned code, non-safety related, can be any alphanumeric
combination or blanks
v = Optional, denotes special model configurations if applicable
v = EL for extended length chassis, no change to rated output
power
v = LNF for Low Noise Fan (reduced CFM). Output power de-rated
for LNF models
v = LL for low leakage models
v = LLEL for low leakage models with extended length chassis
v = MI for Mil COTs
File E123535
Vol. 2
Sec. 7
and Report
Page 1-1
Issued:
Revised:
1998-03-09
2011-10-25
GENERAL CHARACTER AND USE:
The PFC Mini is built using up to six Recognized (QQAQ2) Vicor DC-DC
switching power supplies which provide primary to secondary isolation. It is
provided with input terminals for connection to a single phase power source.
*This product was investigated under the Standard for
UL 60950-1, 2nd Edition, 2007-03-27 (Information Technology Equipment Safety - Part 1: General Requirements) CSA C22.2 No. 60950-1-07, 2nd Edition,
2007-03 (Information Technology Equipment - Safety - Part 1: General
Requirements)
Outputs which are less than 60 V dc are SELV.
Use - For use in (or with) complete equipment where the acceptability
of the combination is determined by Underwriters Laboratories Inc.
ELECTRICAL RATING:
Model: PMw-xyq-zzz-r-v
Inputs:
115-230 V ac, 10 A max, 47-500 Hz
300 V dc, 10 A max
Outputs:
Up to six rated 0 - 95 V dc.
OUTPUT POWER:
Using VI-200 Series and/or VI-J00 Series DC-DC Converters - 600 W Max.
Using
Second Gen Fastrak Series DC-DC Converters 800 W at 115 V ac input
1200 W at 230 V ac/300 V dc inputs (output voltages < 24)
1500 W at 230 V ac/300 V dc inputs (24 V dc output and higher)
File E123535
Vol. 2
ELECTRICAL RATING:
Model:
Sec. 7
and Report
Page 1A
Issued:
Revised:
(Low noise fan option)
PMw-xyq-zzz-r-LNF
Inputs:
115-230 V ac, 10 A max, 47-500 Hz
300 V dc, 10 A max
Outputs:
Up to six rated 0 – 95 V dc
OUTPUT POWER:
Using VI-200 Series and/or VI-J00 Series DC-DC Converters –
600 W at 115 V ac input for all –LNF models
600 W at 230 V ac/300 V dc inputs for 5 V outputs
750 W at 230 V ac/300 V dc inputs for 12 V outputs
800 W at 230 V ac/300 V dc inputs for 15 V outputs
900 W at 230 V ac/300 V dc inputs for 24 V outputs
1100 W at 230 V ac/300 V dc inputs for 28 V outputs
1150 W at 230 V ac/300 V dc inputs for 48 V outputs
1998-03-09
2007-03-28
File E123535
Vol. 2
Sec. 7
and Report
Page 2
Issued:
Revised:
1998-03-09
2011-10-25
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
Use - For use only in end-use equipment where the acceptability of the
combination is determined by Underwriters Laboratories Inc.
Special Considerations - The following items are considerations that
were used when evaluating this product.
*USR/CNR indicates investigation to the U.S. and Canadian (BiNational) Standard for UL 60950-1, 2nd Edition, 2007-03-27 (Information
Technology Equipment - Safety - Part 1: General Requirements) CSA C22.2 No.
60950-1-07, 2nd Edition, 2007-03 (Information Technology Equipment - Safety Part 1: General Requirements)
Conditions of Acceptability - When installed in the end-use equipment,
consideration shall be given to the following:
*1.
This component has been judged on the basis of the required spacings
in the Standard for UL 60950-1, 2nd Edition, 2007-03-27 (Information
Technology Equipment - Safety - Part 1: General Requirements) CSA C22.2 No.
60950-1-07, 2nd Edition, 2007-03 (Information Technology Equipment - Safety Part 1: General Requirements)
2.
The power supply should be installed in compliance with the enclosure,
mounting, spacings, temperature, casualty and segregation requirements
of the ultimate application.
3.
The Normal Temperature Test should be conducted with the unit mounted
in the end-use equipment.
4.
Secondary circuits have not been investigated for secondary
interconnection or user accessibility.
5.
This product has been evaluated as Class I, Component Supply for
building-in.
6.
The input and output terminals are not acceptable for field connections
and are only intended for connection to mating connectors of internal
wiring inside the end-use machine. The acceptability of these and the
mating connectors relative to secureness, insulating materials, and
temperature should be considered.