SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 0.4" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 0 4 0 8 307 0 5 75 200 0 9 1 5 350 0 10 100 200 1 5 2 3 387 1 6 125 200 2 2 3 3 418 2 3 150 200 3 1 4 4 444 3 2 175 200 4 3 5 8 466 4 4 200 200 5 6 7 1 485 5 7 225 200 7 0 8 8 502 7 1 250 200 8 7 10 5 515 8 9 275 250 8 4 10 10 602 8 6 300 250 9 11 12 7 617 10 1 325 250 11 7 14 5 630 11 10 350 250 13 6 16 5 643 13 8 375 300 12 11 16 8 728 13 2 400 300 14 8 18 7 742 14 11 425 350 14 2 18 11 821 14 6 450 350 15 11 20 10 836 16 3 475 400 15 6 21 4 911 15 11 500 400 17 2 23 3 926 17 7 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 1 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 0.5" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 0 5 0 9 315 0 6 75 200 0 11 1 6 359 1 0 100 200 1 8 2 6 394 1 9 125 200 2 8 3 7 423 2 9 150 200 3 10 4 11 446 3 11 175 200 5 2 6 5 465 5 3 200 200 6 9 8 1 481 6 10 225 200 8 7 10 0 493 8 8 250 200 10 7 12 1 504 10 8 275 250 10 3 12 4 597 10 4 300 250 12 2 14 4 609 12 3 325 300 11 11 14 9 696 12 1 350 300 13 9 16 9 709 14 0 375 350 13 7 17 3 791 13 10 400 350 15 5 19 4 805 15 8 425 400 15 3 19 10 883 15 7 450 400 17 1 21 11 898 17 5 475 450 16 11 22 6 974 17 4 500 500 16 11 23 3 1045 17 4 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 2 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 0.6" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 0 6 0 10 324 0 6 75 200 1 1 1 8 368 1 2 100 200 1 11 2 8 403 2 0 125 200 3 0 3 11 430 3 1 150 200 4 4 5 4 451 4 5 175 200 5 11 7 1 468 6 0 200 200 7 9 8 11 482 7 10 225 250 7 10 9 6 572 8 0 250 250 9 8 11 6 586 9 10 275 300 9 9 12 1 673 9 11 300 300 11 8 14 1 687 11 9 325 350 11 8 14 9 770 11 11 350 400 11 10 15 7 848 12 2 375 400 13 7 17 6 865 13 11 400 400 15 6 19 7 881 15 9 425 450 15 7 20 4 958 15 11 450 500 15 8 21 2 1031 16 1 475 500 17 6 23 2 1048 17 11 500 550 17 7 24 0 1120 18 1 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 3 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 0.7" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 0 8 0 11 326 0 8 75 200 1 5 1 10 365 1 5 100 200 2 6 3 1 393 2 7 125 200 3 11 4 7 413 3 11 150 200 5 8 6 4 428 5 8 175 200 7 8 8 5 439 7 9 200 250 8 0 9 2 529 8 1 225 300 8 5 9 12 613 8 7 250 300 10 5 12 1 627 10 6 275 350 10 10 12 11 709 10 11 300 350 12 10 15 1 723 13 0 325 400 13 2 15 11 804 13 5 350 450 13 7 16 10 881 13 10 375 500 14 1 17 9 956 14 4 400 550 14 7 18 10 1029 14 11 425 600 15 1 19 10 1100 15 6 450 600 16 11 21 11 1117 17 3 475 650 17 4 23 0 1187 17 10 500 650 19 3 25 1 1205 19 9 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 4 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 0.8" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 0 9 1 0 328 0 9 75 200 1 8 2 1 363 1 9 100 200 3 0 3 6 385 3 0 125 200 4 8 5 3 401 4 9 150 200 6 9 7 4 411 6 10 175 250 7 4 8 2 499 7 5 200 300 8 0 9 2 584 8 1 225 350 8 8 10 2 665 8 10 250 350 10 9 12 4 679 10 10 275 400 11 4 13 4 759 11 6 300 450 12 0 14 5 836 12 2 325 500 12 8 15 6 911 12 11 350 550 13 4 16 8 985 13 8 375 600 14 1 17 9 1057 14 5 400 600 16 0 19 11 1075 16 4 425 650 16 8 21 1 1146 17 1 450 700 17 4 22 3 1216 17 10 475 750 18 1 23 6 1285 18 7 500 800 18 9 24 8 1354 19 4 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 5 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 0.9" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 0 11 1 1 329 0 11 75 200 2 0 2 4 359 2 0 100 200 3 6 3 11 377 3 6 125 200 5 6 5 11 389 5 6 150 250 6 4 6 11 475 6 4 175 300 7 2 8 1 558 7 3 200 350 8 0 9 2 639 8 1 225 400 8 10 10 4 718 9 0 250 400 10 11 12 6 732 11 1 275 450 11 9 13 8 810 11 11 300 500 12 7 14 11 886 12 10 325 550 13 5 16 2 961 13 8 350 600 14 3 17 5 1034 14 7 375 650 15 2 18 8 1107 15 6 400 700 16 0 19 11 1178 16 4 425 750 16 10 21 3 1248 17 3 450 800 17 9 22 7 1318 18 2 475 900 17 7 23 1 1435 18 1 500 950 18 5 24 5 1502 19 1 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 6 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.0" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 1 0 1 2 330 1 0 75 200 2 3 2 6 357 2 3 100 200 3 11 4 3 372 4 0 125 250 4 11 5 5 457 5 0 150 300 5 11 6 8 539 6 0 175 300 8 0 8 10 552 8 1 200 350 9 0 10 1 634 9 1 225 400 10 0 11 4 714 10 1 250 500 9 10 11 8 852 10 0 275 500 11 11 13 10 868 12 1 300 600 11 10 14 4 1000 12 1 325 650 12 10 15 8 1073 13 1 350 700 13 9 17 0 1145 14 1 375 750 14 9 18 5 1216 15 1 400 800 15 9 19 10 1287 16 2 425 850 16 9 21 3 1356 17 2 450 950 16 9 21 11 1474 17 4 475 1000 17 9 23 4 1542 18 4 500 1100 17 11 24 1 1655 18 7 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 7 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.1" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 1 2 1 4 323 1 3 75 200 2 8 2 11 342 2 8 100 250 3 10 4 2 424 3 10 125 300 4 11 5 6 503 5 0 150 350 6 1 6 10 582 6 2 175 400 7 3 8 2 659 7 4 200 500 7 7 8 10 794 7 9 225 500 9 7 11 0 811 9 9 250 600 9 11 11 8 942 10 1 275 650 11 1 13 1 1014 11 3 300 700 12 3 14 7 1086 12 6 325 800 12 7 15 4 1209 12 10 350 800 14 7 17 7 1228 14 10 375 900 14 10 18 4 1349 15 3 400 1000 15 2 19 2 1466 15 8 425 1000 17 2 21 5 1486 17 8 450 1100 17 6 22 3 1602 18 1 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 8 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.2" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 1 5 1 7 312 1 5 75 200 3 2 3 4 326 3 3 100 250 4 7 4 10 404 4 7 125 350 5 1 5 7 547 5 2 150 400 6 5 7 0 622 6 6 175 450 7 9 8 7 697 7 10 200 500 9 1 10 1 771 9 2 225 600 9 7 10 11 902 9 9 250 700 10 2 11 10 1028 10 4 275 800 10 9 12 9 1151 11 0 300 900 11 5 13 9 1271 11 8 325 900 13 4 15 11 1291 13 8 350 1000 13 11 16 11 1409 14 4 375 1100 14 7 17 11 1526 15 0 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.3" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 1 7 1 8 310 1 7 75 200 3 6 3 8 321 3 6 100 300 4 2 4 6 466 4 2 125 350 5 7 6 0 543 5 8 150 450 6 3 6 11 679 6 4 175 500 7 8 8 6 753 7 9 200 600 8 4 9 5 883 8 6 225 700 9 0 10 6 1010 9 3 250 750 10 5 12 1 1081 10 7 275 800 11 10 13 8 1152 12 1 300 900 12 6 14 9 1274 12 9 325 1000 13 2 15 10 1394 13 7 350 1100 13 11 16 11 1512 14 4 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 9 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.4" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 1 11 2 0 296 1 11 75 250 3 5 3 6 371 3 5 100 350 4 3 4 7 508 4 4 125 400 5 10 6 3 581 5 11 150 500 6 9 7 4 713 6 10 175 600 7 8 8 5 841 7 9 200 700 8 7 9 7 967 8 9 225 800 9 6 10 9 1090 9 8 250 900 10 5 12 0 1212 10 8 275 1000 11 4 13 2 1332 11 7 300 1100 12 3 14 5 1450 12 7 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.5" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 200 2 0 2 1 294 2 1 75 250 3 8 3 9 368 3 8 100 350 4 8 4 11 505 4 8 125 500 5 1 5 7 696 5 2 150 600 6 1 6 9 823 6 2 175 650 7 8 8 6 895 7 9 200 750 8 8 9 8 1020 8 10 225 850 9 8 10 11 1143 9 10 250 1000 10 2 11 9 1315 10 5 275 1100 11 2 13 1 1434 11 6 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 10 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.6" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 250 1 11 2 0 346 1 11 75 300 3 6 3 8 418 3 6 100 400 4 8 4 11 550 4 9 125 500 5 10 6 3 680 5 11 150 650 6 6 7 1 862 6 7 175 750 7 8 8 5 986 7 9 200 850 8 10 9 9 1109 9 0 225 1000 9 6 10 9 1281 9 8 250 1100 10 8 12 1 1400 10 11 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.7" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 250 2 1 2 2 341 2 1 75 350 3 4 3 6 473 3 4 100 450 4 7 4 10 602 4 7 125 600 5 4 5 10 785 5 5 150 700 6 8 7 2 910 6 9 175 800 7 11 8 8 1033 8 0 200 900 9 2 10 1 1155 9 4 225 1100 9 6 10 9 1377 9 9 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 11 of 12 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.8" DIAMETER FIGURE 8 CABLE SAG UNDER EXPECTED TENSION UNLOADED SAG SPAN LENGTH STRINGING STRINGING SAG LIGHT LOADING UNDER LOAD AFTER STORM (Feet) TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches) (Lbs.) (Feet) - (Inches) 50 250 2 3 2 4 337 2 3 75 350 3 7 3 9 468 3 8 100 500 4 6 4 9 654 4 7 125 600 5 10 6 3 780 5 11 150 700 7 3 7 9 905 7 4 175 900 7 8 8 5 1133 7 10 200 1000 9 0 9 11 1254 9 2 225 1100 10 4 11 6 1375 10 7 SAG AND TENSION TABLES FOR LIGHT LOADING PE-38 1.9" DIAMETER FIGURE 8 CABLE SAG UNDER SPAN LENGTH (Feet) 50 75 100 125 150 175 STRINGING TENSION(Lbs.) 300 450 600 800 1000 1100 STRINGING SAG EXPECTED TENSION LIGHT LOADING UNDER LOAD (Feet) 2 3 4 5 6 8 (Feet) - (Inches) 2 5 3 8 5 0 5 11 7 0 8 7 (Inches) 5 7 10 7 6 0 (Lbs.) 375 555 732 959 1181 1300 UNLOADED SAG AFTER STORM (Feet) 2 3 4 5 6 8 NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F). 03/29/04 Page 12 of 12 (Inches) 5 7 10 8 7 2