PE38 Light Loading

SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 0.4" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
0
4
0
8
307
0
5
75
200
0
9
1
5
350
0
10
100
200
1
5
2
3
387
1
6
125
200
2
2
3
3
418
2
3
150
200
3
1
4
4
444
3
2
175
200
4
3
5
8
466
4
4
200
200
5
6
7
1
485
5
7
225
200
7
0
8
8
502
7
1
250
200
8
7
10
5
515
8
9
275
250
8
4
10
10
602
8
6
300
250
9
11
12
7
617
10
1
325
250
11
7
14
5
630
11
10
350
250
13
6
16
5
643
13
8
375
300
12
11
16
8
728
13
2
400
300
14
8
18
7
742
14
11
425
350
14
2
18
11
821
14
6
450
350
15
11
20
10
836
16
3
475
400
15
6
21
4
911
15
11
500
400
17
2
23
3
926
17
7
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 1 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 0.5" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
0
5
0
9
315
0
6
75
200
0
11
1
6
359
1
0
100
200
1
8
2
6
394
1
9
125
200
2
8
3
7
423
2
9
150
200
3
10
4
11
446
3
11
175
200
5
2
6
5
465
5
3
200
200
6
9
8
1
481
6
10
225
200
8
7
10
0
493
8
8
250
200
10
7
12
1
504
10
8
275
250
10
3
12
4
597
10
4
300
250
12
2
14
4
609
12
3
325
300
11
11
14
9
696
12
1
350
300
13
9
16
9
709
14
0
375
350
13
7
17
3
791
13
10
400
350
15
5
19
4
805
15
8
425
400
15
3
19
10
883
15
7
450
400
17
1
21
11
898
17
5
475
450
16
11
22
6
974
17
4
500
500
16
11
23
3
1045
17
4
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 2 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 0.6" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
0
6
0
10
324
0
6
75
200
1
1
1
8
368
1
2
100
200
1
11
2
8
403
2
0
125
200
3
0
3
11
430
3
1
150
200
4
4
5
4
451
4
5
175
200
5
11
7
1
468
6
0
200
200
7
9
8
11
482
7
10
225
250
7
10
9
6
572
8
0
250
250
9
8
11
6
586
9
10
275
300
9
9
12
1
673
9
11
300
300
11
8
14
1
687
11
9
325
350
11
8
14
9
770
11
11
350
400
11
10
15
7
848
12
2
375
400
13
7
17
6
865
13
11
400
400
15
6
19
7
881
15
9
425
450
15
7
20
4
958
15
11
450
500
15
8
21
2
1031
16
1
475
500
17
6
23
2
1048
17
11
500
550
17
7
24
0
1120
18
1
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 3 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 0.7" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
0
8
0
11
326
0
8
75
200
1
5
1
10
365
1
5
100
200
2
6
3
1
393
2
7
125
200
3
11
4
7
413
3
11
150
200
5
8
6
4
428
5
8
175
200
7
8
8
5
439
7
9
200
250
8
0
9
2
529
8
1
225
300
8
5
9
12
613
8
7
250
300
10
5
12
1
627
10
6
275
350
10
10
12
11
709
10
11
300
350
12
10
15
1
723
13
0
325
400
13
2
15
11
804
13
5
350
450
13
7
16
10
881
13
10
375
500
14
1
17
9
956
14
4
400
550
14
7
18
10
1029
14
11
425
600
15
1
19
10
1100
15
6
450
600
16
11
21
11
1117
17
3
475
650
17
4
23
0
1187
17
10
500
650
19
3
25
1
1205
19
9
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 4 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 0.8" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
0
9
1
0
328
0
9
75
200
1
8
2
1
363
1
9
100
200
3
0
3
6
385
3
0
125
200
4
8
5
3
401
4
9
150
200
6
9
7
4
411
6
10
175
250
7
4
8
2
499
7
5
200
300
8
0
9
2
584
8
1
225
350
8
8
10
2
665
8
10
250
350
10
9
12
4
679
10
10
275
400
11
4
13
4
759
11
6
300
450
12
0
14
5
836
12
2
325
500
12
8
15
6
911
12
11
350
550
13
4
16
8
985
13
8
375
600
14
1
17
9
1057
14
5
400
600
16
0
19
11
1075
16
4
425
650
16
8
21
1
1146
17
1
450
700
17
4
22
3
1216
17
10
475
750
18
1
23
6
1285
18
7
500
800
18
9
24
8
1354
19
4
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 5 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 0.9" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
0
11
1
1
329
0
11
75
200
2
0
2
4
359
2
0
100
200
3
6
3
11
377
3
6
125
200
5
6
5
11
389
5
6
150
250
6
4
6
11
475
6
4
175
300
7
2
8
1
558
7
3
200
350
8
0
9
2
639
8
1
225
400
8
10
10
4
718
9
0
250
400
10
11
12
6
732
11
1
275
450
11
9
13
8
810
11
11
300
500
12
7
14
11
886
12
10
325
550
13
5
16
2
961
13
8
350
600
14
3
17
5
1034
14
7
375
650
15
2
18
8
1107
15
6
400
700
16
0
19
11
1178
16
4
425
750
16
10
21
3
1248
17
3
450
800
17
9
22
7
1318
18
2
475
900
17
7
23
1
1435
18
1
500
950
18
5
24
5
1502
19
1
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 6 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.0" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
1
0
1
2
330
1
0
75
200
2
3
2
6
357
2
3
100
200
3
11
4
3
372
4
0
125
250
4
11
5
5
457
5
0
150
300
5
11
6
8
539
6
0
175
300
8
0
8
10
552
8
1
200
350
9
0
10
1
634
9
1
225
400
10
0
11
4
714
10
1
250
500
9
10
11
8
852
10
0
275
500
11
11
13
10
868
12
1
300
600
11
10
14
4
1000
12
1
325
650
12
10
15
8
1073
13
1
350
700
13
9
17
0
1145
14
1
375
750
14
9
18
5
1216
15
1
400
800
15
9
19
10
1287
16
2
425
850
16
9
21
3
1356
17
2
450
950
16
9
21
11
1474
17
4
475
1000
17
9
23
4
1542
18
4
500
1100
17
11
24
1
1655
18
7
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 7 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.1" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
1
2
1
4
323
1
3
75
200
2
8
2
11
342
2
8
100
250
3
10
4
2
424
3
10
125
300
4
11
5
6
503
5
0
150
350
6
1
6
10
582
6
2
175
400
7
3
8
2
659
7
4
200
500
7
7
8
10
794
7
9
225
500
9
7
11
0
811
9
9
250
600
9
11
11
8
942
10
1
275
650
11
1
13
1
1014
11
3
300
700
12
3
14
7
1086
12
6
325
800
12
7
15
4
1209
12
10
350
800
14
7
17
7
1228
14
10
375
900
14
10
18
4
1349
15
3
400
1000
15
2
19
2
1466
15
8
425
1000
17
2
21
5
1486
17
8
450
1100
17
6
22
3
1602
18
1
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 8 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.2" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
1
5
1
7
312
1
5
75
200
3
2
3
4
326
3
3
100
250
4
7
4
10
404
4
7
125
350
5
1
5
7
547
5
2
150
400
6
5
7
0
622
6
6
175
450
7
9
8
7
697
7
10
200
500
9
1
10
1
771
9
2
225
600
9
7
10
11
902
9
9
250
700
10
2
11
10
1028
10
4
275
800
10
9
12
9
1151
11
0
300
900
11
5
13
9
1271
11
8
325
900
13
4
15
11
1291
13
8
350
1000
13
11
16
11
1409
14
4
375
1100
14
7
17
11
1526
15
0
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.3" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
1
7
1
8
310
1
7
75
200
3
6
3
8
321
3
6
100
300
4
2
4
6
466
4
2
125
350
5
7
6
0
543
5
8
150
450
6
3
6
11
679
6
4
175
500
7
8
8
6
753
7
9
200
600
8
4
9
5
883
8
6
225
700
9
0
10
6
1010
9
3
250
750
10
5
12
1
1081
10
7
275
800
11
10
13
8
1152
12
1
300
900
12
6
14
9
1274
12
9
325
1000
13
2
15
10
1394
13
7
350
1100
13
11
16
11
1512
14
4
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 9 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.4" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
1
11
2
0
296
1
11
75
250
3
5
3
6
371
3
5
100
350
4
3
4
7
508
4
4
125
400
5
10
6
3
581
5
11
150
500
6
9
7
4
713
6
10
175
600
7
8
8
5
841
7
9
200
700
8
7
9
7
967
8
9
225
800
9
6
10
9
1090
9
8
250
900
10
5
12
0
1212
10
8
275
1000
11
4
13
2
1332
11
7
300
1100
12
3
14
5
1450
12
7
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.5" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
200
2
0
2
1
294
2
1
75
250
3
8
3
9
368
3
8
100
350
4
8
4
11
505
4
8
125
500
5
1
5
7
696
5
2
150
600
6
1
6
9
823
6
2
175
650
7
8
8
6
895
7
9
200
750
8
8
9
8
1020
8
10
225
850
9
8
10
11
1143
9
10
250
1000
10
2
11
9
1315
10
5
275
1100
11
2
13
1
1434
11
6
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 10 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.6" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
250
1
11
2
0
346
1
11
75
300
3
6
3
8
418
3
6
100
400
4
8
4
11
550
4
9
125
500
5
10
6
3
680
5
11
150
650
6
6
7
1
862
6
7
175
750
7
8
8
5
986
7
9
200
850
8
10
9
9
1109
9
0
225
1000
9
6
10
9
1281
9
8
250
1100
10
8
12
1
1400
10
11
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.7" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
250
2
1
2
2
341
2
1
75
350
3
4
3
6
473
3
4
100
450
4
7
4
10
602
4
7
125
600
5
4
5
10
785
5
5
150
700
6
8
7
2
910
6
9
175
800
7
11
8
8
1033
8
0
200
900
9
2
10
1
1155
9
4
225
1100
9
6
10
9
1377
9
9
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 11 of 12
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.8" DIAMETER FIGURE 8 CABLE
SAG UNDER EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG LIGHT LOADING
UNDER LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
50
250
2
3
2
4
337
2
3
75
350
3
7
3
9
468
3
8
100
500
4
6
4
9
654
4
7
125
600
5
10
6
3
780
5
11
150
700
7
3
7
9
905
7
4
175
900
7
8
8
5
1133
7
10
200
1000
9
0
9
11
1254
9
2
225
1100
10
4
11
6
1375
10
7
SAG AND TENSION TABLES FOR LIGHT LOADING
PE-38 1.9" DIAMETER FIGURE 8 CABLE
SAG UNDER
SPAN
LENGTH
(Feet)
50
75
100
125
150
175
STRINGING
TENSION(Lbs.)
300
450
600
800
1000
1100
STRINGING SAG
EXPECTED
TENSION
LIGHT LOADING
UNDER LOAD
(Feet) 2
3
4
5
6
8
(Feet) - (Inches)
2
5
3
8
5
0
5
11
7
0
8
7
(Inches)
5
7
10
7
6
0
(Lbs.)
375
555
732
959
1181
1300
UNLOADED SAG
AFTER STORM
(Feet) 2
3
4
5
6
8
NOTES: Light loading is defined under NESC Rules 250 and 251 as 9 PSF horizontal wind pressure
at 30º Fahrenheit and no ice. Stringing tensions are at 60º (F).
03/29/04
Page 12 of 12
(Inches)
5
7
10
8
7
2