Lashed 6M Medium Loading

SAG AND TENSION TABLES FOR LASHED CABLES ON 1/4 INCH STRAND
MEDIUM ICE LOADING AREAS
0.5" DIAMETER (0.2 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
0
4
200
1100
1
6
300
1100
3
3
400
1100
5
10
500
1100
9
1
600
1100
13
2
700
1100
17
10
780
1100
22
2
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
1
1
1199
3
11
1313
8
0
1445
13
0
1575
18
10
1698
25
5
1813
32
8
1920
38
11
1999
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
1
1
2
8
4
10
7
7
11
1
15
4
20
2
24
8
0.6" DIAMETER (0.25 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
0
5
200
1100
1
8
300
1100
3
10
400
1100
6
9
500
1100
10
6
600
1100
15
2
700
1100
20
8
710
1100
21
3
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
1
2
1206
4
2
1332
8
6
1472
13
10
1607
20
0
1733
27
0
1849
34
9
1955
35
7
1965
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
1
2
2
10
5
2
8
4
12
4
17
1
22
9
23
4
0.7" DIAMETER (0.3 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG HEAVY LOADING UNDER HEAVY LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
1100
0
6
1
3
1213
1
2
200
1100
1
11
4
5
1350
2
11
300
1100
4
4
9
0
1498
5
7
400
1100
7
8
14
7
1638
9
1
500
1100
12
0
21
2
1765
13
7
600
1100
17
3
28
7
1881
19
0
645
1100
19
11
32
3
1929
21
9
NOTES:
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
04/01/04
Page 1 of 5
SAG AND TENSION TABLES FOR LASHED CABLES ON 1/4 INCH STRAND
MEDIUM ICE LOADING AREAS
0.8" DIAMETER (0.4 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
0
7
200
1100
2
4
300
1100
5
4
400
1100
9
6
500
1100
14
10
560
1100
18
7
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
1
4
1223
4
10
1372
9
9
1526
15
11
1665
23
2
1789
28
0
1855
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
1
3
3
3
6
5
10
9
16
2
19
0
0.9" DIAMETER (0.5 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
0
8
200
1100
2
10
300
1100
6
4
400
1100
11
3
495
1100
17
3
SAG UNDER EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
1
6
1233
5
3
1393
10
7
1549
17
3
1687
24
9
1799
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
1
3
3
8
7
4
12
4
18
5
1.0" DIAMETER (0.7 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
0
11
200
1100
3
9
300
1100
8
5
400
1100
14
11
405
1100
15
4
NOTES:
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
04/01/04
SAG UNDER
EXPECTED TENSION UNLOADED SAG
HEAVY LOADING UNDER HEAVY LOAD
AFTER STORM
(Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
1
8
1247
1
5
5
11
1416
4
5
12
0
1567
9
2
19
10
1689
15
9
20
3
1694
16
2
Page 2 of 5
SAG AND TENSION TABLES FOR LASHED CABLES ON 1/4 INCH STRAND
MEDIUM ICE LOADING AREAS
1.1" DIAMETER (0.8 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
1
1
200
1100
4
2
300
1100
9
5
370
1100
14
4
SAG UNDER
EXPECTED TENSION UNLOADED SAG
HEAVY LOADING UNDER HEAVY LOAD AFTER STORM
(Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
1
10
1257
1
6
6
4
1432
4
9
12
11
1581
10
1
18
7
1666
15
1
1.2" DIAMETER (0.9 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
1
2
200
1100
4
8
300
1100
10
5
335
1100
13
0
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
1
11
1266
6
9
1446
13
9
1593
16
8
1635
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
1
7
5
2
11
1
13
8
1.3" DIAMETER (1.2 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION
SPAN LENGTH
STRINGING
STRINGING SAG HEAVY LOADING UNDER HEAVY LOAD
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
100
1100
1
6
2
2
1281
200
1100
6
0
7
9
1456
275
1100
11
4
13
9
1553
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
1
10
6
5
11
10
1.4" DIAMETER (1.4 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
1
9
200
1100
6
11
240
1100
9
11
NOTES:
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
2
1
7
4
10
4
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
04/01/04
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
2
5
1291
8
6
1461
11
10
1512
Page 3 of 5
SAG AND TENSION TABLES FOR LASHED CABLES ON 1/4 INCH STRAND
MEDIUM ICE LOADING AREAS
1.5" DIAMETER (1.5 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
1
10
200
1100
7
4
230
1100
9
9
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
2
6
1299
8
11
1470
11
6
1507
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
2
2
7
9
10
1
1.6" DIAMETER (1.8 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
2
2
200
1100
8
9
SAG UNDER
EXPECTED TENSION UNLOADED SAG
HEAVY LOADING UNDER HEAVY LOAD
AFTER STORM
(Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
2
10
1309
2
5
10
1
1465
9
1
1.7" DIAMETER (2.1 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
2
6
175
1100
7
9
SAG UNDER
EXPECTED TENSION UNLOADED SAG
HEAVY LOADING UNDER HEAVY LOAD AFTER STORM
(Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
3
1
1316
2
9
8
9
1430
8
0
1.8" DIAMETER (2.4 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION
SPAN LENGTH
STRINGING
STRINGING SAG HEAVY LOADING UNDER HEAVY LOAD
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
100
1100
2
10
3
5
1321
155
1100
6
11
7
9
1403
NOTES:
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
04/01/04
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
3
1
7
1
Page 4 of 5
SAG AND TENSION TABLES FOR LASHED CABLES ON 1/4 INCH STRAND
MEDIUM ICE LOADING AREAS
1.9" DIAMETER (2.6 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG HEAVY LOADING UNDER HEAVY LOAD
AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
1100
3
1
3
7
1326
3
3
145
1100
6
6
7
3
1392
6
9
2.0" DIAMETER (2.7 #/FT.) FILLED FOAM-SKIN CABLE
SPAN LENGTH
STRINGING
STRINGING SAG
(Feet)
TENSION(Lbs.) (Feet) - (Inches)
100
1100
3
2
140
1100
6
3
NOTES:
UNLOADED SAG
AFTER STORM
(Feet) - (Inches)
3
5
6
6
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
04/01/04
SAG UNDER
EXPECTED TENSION
HEAVY LOADING UNDER HEAVY LOAD
(Feet) - (Inches)
(Lbs.)
3
9
1331
7
0
1391
Page 5 of 5