Lashed 10M Medium Loading

SAG AND TENSION TABLES FOR LASHED CABLES ON 10M STRAND
MEDIUM ICE LOADING AREAS
1.0" DIAMETER (0.7 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG MEDIUM LOADING UNDER MEDIUM LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
2100
0
6
1
0
2187
1
3
200
2100
2
1
3
11
2285
3
1
300
2100
4
9
8
4
2411
5
11
400
2100
8
6
14
0
2544
9
9
500
2100
13
3
20
10
2674
14
7
600
2100
19
1
28
8
2796
20
6
640
2100
21
8
32
1
2842
23
2
1.2" DIAMETER (0.9 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG MEDIUM LOADING UNDER MEDIUM LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
2100
0
8
1
2
2196
1
3
200
2100
2
7
4
5
2312
3
5
300
2100
5
10
9
5
2454
6
10
400
2100
10
4
15
9
2597
11
5
500
545
2100
2100
16
19
2
3
23
27
5
3
2730
2787
17
20
4
5
1.4" DIAMETER (1.4 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG MEDIUM LOADING UNDER MEDIUM LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
2100
0
11
1
6
2212
1
6
200
2100
3
9
5
6
2353
4
5
300
2100
8
6
11
8
2506
9
3
400
2100
15
2
19
8
2644
15
11
410
NOTES:
04/05/04
2100
15
11
20
6
2657
16
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
Page 1 of 2
8
SAG AND TENSION TABLES FOR LASHED CABLES ON 10M STRAND
MEDIUM LOADING AREAS
1.6" DIAMETER (1.8 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION
UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG MEDIUM LOADING UNDER MEDIUM LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
2100
1
2
1
9
2227
1
8
200
2100
4
9
6
5
2385
5
3
300
2100
10
8
13
6
2540
11
3
340
2100
13
8
17
0
2595
14
3
1.8" DIAMETER (2.4 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG MEDIUM LOADING UNDER MEDIUM LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
2100
1
6
2
1
2244
1
11
200
270
2100
2100
6
11
2
3
7
13
8
5
2415
2521
6
11
7
8
2.0" DIAMETER (2.7 #/FT.) FILLED FOAM-SKIN CABLE
SAG UNDER
EXPECTED TENSION UNLOADED SAG
SPAN LENGTH
STRINGING
STRINGING SAG MEDIUM LOADING UNDER MEDIUM LOAD AFTER STORM
(Feet)
TENSION(Lbs.) (Feet) - (Inches) (Feet) - (Inches)
(Lbs.)
(Feet) - (Inches)
100
2100
1
9
2
3
2257
2
1
200
2100
6
11
8
4
2436
7
3
245
2100
10
4
12
2
2506
10
9
NOTES:
04/05/04
Medium ice loading is defined under NESC Rules 250 and 251 as 0.25 inch radius thickness of ice
and 4 PSF horizontal wind pressure at 15º F.
Stringing tensions are at 60º F.
Page 2 of 2