MEANWELL 1K2S-P036

SCP-1K2
900~1200W Parallel (N+1) With PFC Function
series
Features :
AC input 180~260VAC only
PF> 0.98@ 230VAC
Protections: Short circuit / Overload / Over voltage / Over temperature
Built in remote sense function
Built-in remote ON-OFF control
Built-in power good signal output
Built-in parallel operation function(N+1)
Can adjust from 20~100% output voltage by external control 1-5V
Forced air cooling by built-in DC fan
3 years warranty
SPECIFICATION
ORDER NO.
OUTPUT
SCP-1K2-05 SCP-1K2-09 SCP-1K2-12 SCP-1K2-15 SCP-1K2-18 SCP-1K2-24 SCP-1K2-36 SCP-1K2-48 SCP-1K2-60
SAFETY MODEL NO.
1K2S-P005
1K2S-P009
1K2S-P012
1K2S-P015
1K2S-P018
1K2S-P024
1K2S-P036
1K2S-P048
1K2S-P060
DC VOLTAGE
5V
9V
12V
15V
18V
24V
36V
48V
60V
RATED CURRENT
200A
133A
100A
80A
66.6A
50A
33.3A
24A
20A
CURRENT RANGE
0 ~ 200A
0 ~ 133A
0 ~ 100A
0 ~ 80A
0 ~ 66.6A
0 ~ 50A
0 ~ 33.3A
0 ~ 24A
0 ~ 20A
RATED POWER
1000W
1197W
1200W
1200W
1198W
1200W
1198W
1152W
1200W
100mVp-p
120mVp-p
150mVp-p
180mVp-p
240mVp-p
360mVp-p
480mVp-p
500mVp-p
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
3.0% Typical adjustment by potentiometer
20%~100% adjustment by 1~5VDC external control
VOLTAGE TOLERANCE Note.3 2.0%
1.5%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
LINE REGULATION
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
LOAD REGULATION
1.5%
1.0%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
SETUP, RISE, HOLD UP TIME 500ms, 200ms, 16ms at full load
INPUT
VOLTAGE RANGE
180 ~ 260VAC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR
>0.98 / 230VAC
80%
AC CURRENT
INRUSH CURRENT (max.)
10A / 230VAC
60A / 230VAC
LEAKAGE CURRENT (max.)
3.5mA / 240VAC
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
(Note. 5)
SPECIAL FUNCTION
NOTE
COOLING
86%
89%
89%
90%
90%
110 ~ 135% Follow to output set up point
Protection type : Shut down o/p voltage, re-power on to recover
>100 / measure by heat sink, near transformer
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +65 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.04% / (0 ~ 50 )
10 ~ 200Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, OP/FG:100M Ohms / 500VDC / 25
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) class A
Compliance to EN61000-3-2,3
HARMONIC CURRENT
EMS IMMUNITY
POWER GOOD SIGNAL
OTHERS
85%
84%
105 ~ 140% rated output power
Note. 4
Protection type : Current limiting, delay shut down o/p voltage, re-power on to recover
PROTECTION OVER VOLTAGE
EMC
82%
EFFICIENCY (Typ.)
OVERLOAD
SAFETY &
260 ~ 370VDC see the derating curve
/ 70% RH
Compliance to EN61000-4-2,3,4,5,6,8,11, light industry level, criteria A
Open collector of NPN transistor
DC Voltage Adj., remote sensing, remote control, parallel operation(refer to control terminal instruction manual)
MTBF
By fan, >20% load or >50 fan on
37.4K hrs min. MIL-HDBK-217F(25
DIMENSION
290*120*132mm (L*W*H)
PACKING
5kg; 4pcs /21kg /CARTON
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Current limiting 3 times(1.5s,3.0s,5.0s)Then intelligent auto recovery before shut down
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name: SCP-1K2-SPEC 2008-05-06
SCP-1K2
900~1200W Parallel (N+1) With PFC Function
Mechanical Specification
series
Unit:mm
290
200
200
120
1 2 3
TB1
#6-32-4
M3(NUT) 3H-4
1 2 3 4 5 6 7 8
Vadj
103
132.5
AC INPUT
LED
NEG-
POS+
LED
30
26.5
251
Air flow
direction
89
M3(NUT) 3H-4
Terminal Pin No. Assignment
Pin No.
1
2
3
Control terminal Pin No. Assignment (TB1) : Dinkle 51HDBC-O8P or equivalent
Assignment
AC/L
AC/N
FG
Pin No.
1
2
3
4
Assignment
VS+
VSVCI
VCO
Pin No.
5
6
7
8
Assignment
Mating With
PG
PAR
Dinkle 51SDB-O8P
or equivalent
GND
INH
Derating Curve
Ta=25
1800
OUTPUT POWER (W)
100
LOAD (%)
80
60
40
20
-20
1600
1400
1200
1100
1000
800
600
-10
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70
90
110
130
150 160
180
200
220
240
260
INPUT VOLTAGE (VAC) 60Hz
File Name: SCP-1K2-SPEC 2008-05-06
SCP-1K2
900~1200W Parallel (N+1) With PFC Function
series
Control terminal instruction manual
LOAD
VS+
VSVCI
VCO
PG
PAR
GND
INH
VS+
VSVCI
VCO
PG
PAR
GND
INH
USING INTERNAL VOLTAGE CONTROL
LOAD
LOAD
LOAD
VS+
VSVCI
VCO
PG
PAR
GND
INH
VS+
VSVCI
VCO
PG
PAR
GND
INH
ON/OFF SWITCH
ON/OFF CONTROL BY TRANSISTOR
ON/OFF CONTROL BY SWITCH
REMOTE SENSING
H:ON
L:OFF
Vout
GOOD
FAIL
: LED OFF
: LED ON
O.V.P. 120% (Typ.)
120
100
VS+
VSVCI
VCO
PG
PAR
GND
INH
40V / 0.5A MAX.
POWER GOOD SIGNAL
VS+
VSVCI
VCO
PG
PAR
GND
INH
OUTPUT VOLTAGE (%)
LOAD
LOAD
DC 1-5V
80
Non-Linear
60
40
20
1
OUTPUT VOLTAGE ADJUST WITH DC 1-5V
2
3
4
5
6
EXTERNAL VOLTAGE (DC)
LOAD
VS+
VSVCI
VCO
PG
PAR
GND
INH
VS+
VSVCI
VCO
PG
PAR
GND
INH
VS+
VSVCI
VCO
PG
PAR
GND
INH
PARALLEL OPERATION WITH REMOTE SENSING
V
LOAD
VS+
VSVCI
VCO
PG
PAR
GND
INH
VS+
VSVCI
VCO
PG
PAR
GND
INH
VS+
VSVCI
VCO
PG
PAR
GND
INH
PARALLEL OPERATION WITHOUT REMOTE SENSING
File Name: SCP-1K2-SPEC 2008-05-06