Mounting and sub-assemblies 240 of the relay and accessories in the socket Signalling / protecting module type M... Electromagnetic relays Removing the relay from the socket with a retrainer / retractor clip Retainer / retractor clip Description plate Screw terminals plug-in socket Accessories retainer / retractor clips and description plates Type of plug-in socket GZT80, GZT92, GZM80, GZM92 GZS80, GZS92 GZ96 GZT2, GZT3, GZT4, GZM2, GZM3, GZM4 Type GZT80-0040 GZS-0040 ❶ MS16 GZT4-0040 Colour black black black black Type GZT80-0035 TR TR GZT4-0035 Colour white white white white Designed for relays RM84, RM85, RM85 inrush, RM85 105 °C sensitive, RM87, RM87 sensitive RM84, RM85, RM85 inrush, RM85 105 °C sensitive, RM87, RM87 sensitive RM96 1 C/O R2, R3, R4 Height of relay 15...16,5 mm 15...16,5 mm ❶ 15...16,5 mm 35,6 mm Retainer / retractor clips Description plates ❶ Relpol S.A. offers also retainer / retractor clip GZS-0025 designed for relays of the height 25...26 mm. www.relpol.com.pl Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 Signalling / protecting modules type M... Modules type M... 241 Layout Voltage Type of module ❶ 6/230 V DC M21P 6/230 V DC M21N 6/24 V DC 24/60 V DC 110/230 V DC M31R, M31G M32R, M32G M33R, M33G 6/24 V DC 24/60 V DC 110/230 V DC M41R, M41G M42R, M42G M43R, M43G 6/24 V AC 24/60 V AC 110/240 V AC M51 M52 M53 6/24 V AC/DC 24/60 V AC/DC 110/230 V AC/DC M61R, M61G M62R, M62G M63R, M63G 6/24 V AC/DC 24/60 V AC/DC 110/230 V AC/DC M91R, M91G M92R, M92G M93R, M93G It limits overvoltage on AC and DC coils. No indication. 24 V AC 130 V AC 230 V AC M71 M72 M73 Module R 110/230 V AC M103 Module D (polarization P) It limits overvoltage on DC coils. Module D (polarization N) It limits overvoltage on DC coils. Module LD (polarization P) It limits overvoltage on DC coils. Coil energizing indication. Module LD (polarization N) For sockets type: GZT80, GZT92, GZM80, GZM92, GZS80, GZS92, GZ96, It limits overvoltage on DC coils. Coil energizing indication. Module RC GZT2, GZT3, GZT4, GZM2, GZM3, GZM4 It protects against EMC disturbance. It limits overvoltage. Module L Coil energizing indication. Module LV It limits overvoltage on AC and DC coils. Coil energizing indication. Module V It limits overvoltage on AC coils. ❶ M...R - LED red colour M...G - LED green colour Modules type M... are parallely connected with relay coil. Polarity P: -A1/+A2. Polarity N: +A1/-A2. Additional features for industrial relays Type ❷ Description For industrial relays W mechanical indicator R15 2 C/O, R15 3 C/O, R2, R3, R4 T lockable front test button, orange colour AC coils, green colour - DC coils R15 2 C/O, R15 3 C/O, R2, R3, R4 L light indicator (LED diode), located inside the relay R15 2 C/O, R15 3 C/O, R15 4 C/O, RUC, R2, R3, R4, RY2 D surge suppresion element (diode) - only for DC coils R15 2 C/O, R15 3 C/O, R15 4 C/O, R2, R3, R4, RY2 V surge suppresion element (varistor) - only for AC coils R15 2 C/O, R15 3 C/O K test button without block function R15 4 C/O, RUC WT - mechanical indicator + lockable front test button Standard features for industrial relays: R15 2 C/O, R15 3 C/O, R2, R3, R4. ❷ Available combinations: WT, WTL, WTD, WTLD, WTV, WTLV - relays for plug-in sockets: R15 2 C/O, R15 3 C/O. WT, WTL, WTD, WTLD - relays for plug-in sockets: R2, R3, R4 K, L, D, KL, KD, KLD - relays for plug-in sockets R15 4 C/O. K, L, KL - relays RUC. Detailed information for individual relays: see Ordering codes - Additional features. Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 www.relpol.com.pl Plug-in sockets and accessories availability index 242 The relays not specified in the table are designed for other manners of mounting. Relays mounting options are specified in the table, page 244, 245. Plug-in sockets Type of relay Screw terminals Solder terminals For PCB mounting On panel mounting 35 mm rail mount acc. to PN-EN 60715 RM699BV, RSR30 ❶ – – – PI6W-1P RM84 – (EC50, PW80 ❷) (GD50 ❸) GZT80, GZM80 (GZS80 ❹) GZT80, GZM80 (GZS80 ❹) RM85 – (EC50, PW80 ❷) (GD50 ❸) GZT80, GZM80 (GZS80 ❹) GZT80, GZM80 (GZS80 ❹) RM85 inrush – (EC50, PW80 ❷) (GD50 ❸) GZT80, GZM80 (GZS80 ❹) GZT80, GZM80 (GZS80 ❹) RM85 105 °C sensitive – (EC50, PW80 ❷) (GD50 ❸) GZT80, GZM80 (GZS80 ❹) GZT80, GZM80 (GZS80 ❹) RM87N, RM87N sensitive – (EC35 ❷) (GD35 ❸) GZT92, GZM92 (GZS92 ❹) GZT92, GZM92 (GZS92 ❹) RM87L, RM87L sensitive – (EC50, PW80 ❷) (GD50 ❸) GZT80, GZM80 (GZS80 ❹) GZT80, GZM80 (GZS80 ❹) RM87P, RM87P sensitive – (EC50, PW80 ❷) (GD50 ❸) GZT80, GZM80 (GZS80 ❹) GZT80, GZM80 (GZS80 ❹) RM96 1 C/O – – GZ96 GZ96 R2 (SU4/2L ❺) (G4/2 ❻) SU4/2D ❻ GZT2, GZM2 GZT2, GZM2 R3 – – GZT3, GZM3 GZT3, GZM3 R4 (SU4L ❺) (G4 ❻) SU4D ❻ GZT4, GZM4 (GZ4 ❼), (GS4 ❼ ❽) GZT4, GZM4 (GZ4 ❼), (GS4 ❼ ❽) RY2 – – GZY2 ① GZY2 ① R2M G2M ② S2M ② GZ2 ③ GZ2 ③ Miniature relays Miniature industrial relays Industrial relays of small dimensions R15 2 C/O GOP8 ④ – (PZ8 ⑤) (GZ8 ⑥) GZS8, (GZP8 ⑦) (PZ8 ⑤) (GZU8 ⑥) GZS8, (GZP8 ⑦) R15 3 C/O GOP11 ④ – (PS11, PZ11 ⑤) (GZ11 ⑥) GZS11, (GZP11 ⑦) (PS11, PZ11 ⑤) (GZU11 ⑥) GZS11, (GZP11 ⑦) R15 4 C/O GOP14 ④ – GZ14, GZ14Z GZ14U RUC faston 4,8 x 0,5 – – GUC11 GUC11 – – GZT4, GZM4 GZT4, GZM4 Time relays T-R4 ❶ Solid state relays RSR30 type - see catalogue ”Solid state relays” and www.relpol.com.pl ❷ For EC50, PW80, EC35, EC32 sockets apply spring wire clips MH16-2 ❸ For GD50, GD35 sockets apply spring wire clips GD-0016 ❹ For GZS80, GZS92 sockets apply retainer / retractor clips GZS-0040 and description plates TR ❺ For SU4/2L, SU4L sockets apply spring wire clips G4 1053 or G4 1050 and spring clamps G4 1040 ❻ For SU4/2D, SU4D, G4/2, G4 sockets apply spring wire clips G4 1053 or G4 1050 ❼ For GZ4, GS4 sockets not applicable retainer / retractor clips GZT4-0040, description plates GZT4-0035, modules type M... and interconnection strip type ZGGZ4 ❽ For GS4 sockets apply spring wire clips GS4-0036 and description plates GS4-0035 ❾ Information on buttons (no latching) R4P-0001, R15-M404 and plugs R4W-0003, R15-M203 - see page 248. www.relpol.com.pl Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 Plug-in sockets and accessories availability index 243 Additional features Accessories Signalling / protecting modules Spring wire clips Retainer / retractor clips Description plates – – PI6W-1246 – interconnection strip type ZG20 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 (MH16-2 ❷), GZM80-0041 (GD-0016 ❸) GZT80-0040 (GZS-0040 ❹) GZT80-0035 (TR ❹) type M... interconnection strip type ZGGZ80 GZM80-0041 MS16 TR type M... interconnection strip type ZGGZ80 (G4 1053, G4 1050 ❺ ❻) G4 1052 GZT4-0040 GZT4-0035 type M... interconnection strip type ZGGZ4 test buttons, plugs ❾ G4 1052 GZT4-0040 GZT4-0035 type M... interconnection strip type ZGGZ4 test buttons, plugs ❾ (G4 1053, G4 1050 ❺ ❻) G4 1052, (GS4-0036 ❽) GZT4-0040 ❼ (GZT4-0035 ❼) (GS4-0035 ❽) type M... ❼ (interconnection strip type ZGGZ4 ❼) test buttons, plugs ❾ GZY 2000 ① – – – – (G4 1050 ②), (GZ2 1060 ③) – – – – (R159 1051 ④), (PZ11 0031 ⑤) (GZ 1050, GZU 1052 ⑥) (GZP-0054 ⑦) – GZP-0035 ⑦ – (test buttons, plugs ❾) (time module T(COM3) ⑦) (R159 1051 ④), (PZ11 0031 ⑤) (GZ 1050, GZU 1052 ⑥) (GZP-0054 ⑦) – GZP-0035 ⑦ – (test buttons, plugs ❾) (time module T(COM3) ⑦) (R15 0736 ④), GZ14 0737 – – – – MBA – – – – TR4-2000 – GZT4-0035 – interconnection strip type ZGGZ4 ① For GZY2 sockets apply spring wire clips GZY 2000 and spring clamps GZ2 1111 ② For G2M sockets apply spring wire clips G4 1050 and spring clamps G2M 1020 For S2M sockets apply spring wire clips G4 1050 ③ For GZ2 sockets apply spring wire clips GZ2 1060 and spring clamps GZ2 1111 ④ For GOP8, GOP11 sockets apply spring wire clips R159 1051 and spring clamps R15 5922 For GOP14 sockets apply spring wire clips R15 0736 and spring clamps R15 5922 ⑤ For PZ8, PS11, PZ11 sockets apply spring wire clips PZ11 0031 ⑥ For GZ8, GZ11 sockets apply spring wire clips GZ 1050 For GZU8, GZU11 sockets apply spring wire clips GZU 1052 ⑦ For GZP8, GZP11 sockets apply spring wire clips GZP-0054, description plates GZP-0035 and time modules T(COM3) Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 www.relpol.com.pl Relays mounting options 244 Type of relay Method of mounting For PCB mounting On panel mounting 35 mm rail mount acc. to PN-EN 60715 Cover with mounting flange - on panel mounting Flat insert connectors - faston Subminiature signal relays RSM850 direct – – – – – RSM850B direct – – – – – RSM822 direct – – – – – RSM832 direct – – – – – RSM954 direct – – – – – RSM957 direct – – – – – RM40 direct – – – – – RM50 direct – – – – – RM699BV, RSR30 ❶ direct – – with socket – – RM699H direct – – – – – RM84 direct with socket with socket with socket – – RM84 SMT direct – – – – – RM85 direct with socket with socket with socket – – RM85 ✪ direct – – – – – RM85 inrush direct with socket with socket with socket – – RM85 105 °C sensitive direct with socket with socket with socket – – RM85 SMT direct – – – – – RM85 faston direct – – – – 6,3 x 0,8 mm RM87N direct with socket with socket with socket – – RM87N sensitive direct with socket with socket with socket – – RM87L direct with socket with socket with socket – – RM87L sensitive direct with socket with socket with socket – – RM87P direct with socket with socket with socket – – RM87P sensitive direct with socket with socket with socket – – RM87N SMT direct – – – – – RM96 1 C/O direct – with socket with socket – – RM96 1 NO, 1 NC direct – – – – – RM83 direct – – – – – RM92 direct – – – – – RM94 direct – – – – – direct – – – – – Miniature relays Automotive relays RA2 Miniature industrial relays R2 direct with socket with socket with socket – – R3 – – with socket with socket – – R4 direct with socket with socket with socket – – RY2 – – with socket with socket on request 4,8 x 0,5 mm R2M direct with socket with socket with socket – – www.relpol.com.pl Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 Relays mounting options 245 Type of relay Method of mounting For PCB mounting On panel mounting 35 mm rail mount acc. to PN-EN 60715 Cover with mounting flange - on panel mounting Flat insert connectors - faston Industrial relays of small dimensions R15 2 C/O direct – with socket with socket – – R15 3 C/O direct – with socket with socket – – R15 4 C/O – – with socket ❷ with socket – – RUC faston 4,8 x 0,5 direct – with socket ❸ with socket ❸ on request 4,8 x 0,5 mm direct ❹ RUC faston 6,3 x 0,8 – – – direct ❹ on request 6,3 x 0,8 mm RG25 – – – direct – – R20 – – direct – standard 6,3 x 0,8 mm PI84 with socket GZT80 – – direct direct – – PI85 with socket GZT80 – – direct direct – – PI84 with socket GZM80 – – direct direct – – PI85 with socket GZM80 – – direct direct – – PIR2 with socket GZM2 – – direct direct – – PIR3 with socket GZM3 – – direct direct – – PIR4 with socket GZM4 – – direct direct – – PI6-1P – – – direct – – PI6-1T – – – direct – – PI6-OC – – – direct – – PIR6W-1P-... – – – direct – – PIR6W-1PS-...- ❺ – – – direct – – PIR6WB-1PS-...- ❺ – – – direct – – – – – direct – – MT-TUA-... – – – direct – – MT-TUB-... – – – direct – – MT-T..-.. – – – direct – – MT-TSD-... – – – direct – – TR4N 4 C/O – – – direct – – TR4N 1 C/O, 2 C/O – – – direct – – T-R4 – – with socket with socket – – PIR15...T ❻ – – direct direct – – Interface relays Installation relays MT-PI-... Time relays ✪ RM85 with increased contact gap ❶ Solid state relays RSR30 type - see catalogue ”Solid state relays” and www.relpol.com.pl ❷ Available socket to be mounted behind the assembly panel - GZ14Z. ❸ For RUC faston 4,8 x 0,5 with GUC11 socket max. switching voltages and coil voltages of relays are limited to 250 V AC/DC. ❹ Version with adaptor: (V) or (H). ❺ R - operational electromagnetic relay RM699BV type for PIR6W.-1PS-...-R. T/C/O - operational solid state relay RSR30 type for PIR6W.-1PS-...-T (C or O) - see catalogue ”Solid stete relays” and www.relpol.com.pl ❻ With time module T(COM3). Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 www.relpol.com.pl Plug-in sockets technical data 246 Plug-in socket Terminals type Insulation Insulation rated voltage Rated current (PN-EN 60664-1) Dielectric strength 50/60 Hz, 1 min. between coil and contacts pole - pole GZT80 for screw terminals 300 V AC 12 A 5000 V AC 3000 V AC GZM80 for screw terminals 300 V AC 12 A 5000 V AC 3000 V AC GZS80 for screw terminals 300 V AC 10 A 4000 V AC 2500 V AC EC50 for PCB 300 V AC 8A 6 kV (1,2 / 50 µs) 2000 V AC PW80 for PCB 250 V AC 8A 2000 V AC 2000 V AC GD50 for PCB 300 V AC 8A 2000 V AC 2000 V AC GZT92 for screw terminals 300 V AC 12 A 5000 V AC – GZM92 for screw terminals 300 V AC 12 A 5000 V AC – GZS92 for screw terminals 300 V AC 12 A 4000 V AC – EC35 for PCB 300 V AC 12 A 6 kV (1,2 / 50 µs) – GD35 for PCB 300 V AC 12 A 2000 V AC – GZ96 for screw terminals 300 V AC 12 A 4000 V AC – EC32 for PCB 300 V AC 12 A 6 kV (1,2 / 50 µs) – GZT2 for screw terminals 300 V AC 12 A 3000 V AC 3000 V AC GZM2 for screw terminals 300 V AC 12 A 4000 V AC 3000 V AC SU4/2D for PCB 250 V AC 12 A 2500 V AC 2500 V AC SU4/2L for solder terminals 250 V AC 12 A 2500 V AC 2500 V AC G4/2 for solder terminals 250 V AC 12 A 2500 V AC 2500 V AC GZT3 for screw terminals 300 V AC 10 A 3000 V AC 3000 V AC GZM3 for screw terminals 300 V AC 10 A 4000 V AC 3000 V AC GZT4 for screw terminals 300 V AC 6A 3000 V AC 3000 V AC GZM4 for screw terminals 300 V AC 6A 4000 V AC 3000 V AC GZ4 for screw terminals 300 V AC 7A 2500 V AC 2000 V AC GS4 for screw terminals 300 V AC 6A 2500 V AC 2000 V AC SU4D for PCB 250 V AC 6A 2500 V AC 2000 V AC SU4L for solder terminals 250 V AC 6A 2500 V AC 2000 V AC G4 for solder terminals 250 V AC 6A 2500 V AC 2000 V AC GZY2 for screw terminals 250 V AC 12 A 2000 V AC 2000 V AC GZ2 for screw terminals 250 V AC 7A 2000 V AC 2000 V AC S2M for PCB 250 V AC 5A 2000 V AC 2000 V AC G2M for solder terminals 250 V AC 5A 2000 V AC 2000 V AC PZ8 for screw terminals 250 V AC 10 A 2500 V AC 2500 V AC GZU8 for screw terminals 300 V AC 10 A 2500 V AC 2500 V AC GZ8 for screw terminals 300 V AC 10 A 2500V AC 2500 V AC GZS8 for screw terminals 300 V AC 10 A 2000 V AC 2000 V AC GZP8 for screw terminals 300 V AC 12 A 4000 V AC 2500 V AC GOP8 for solder terminals 250 V AC 10 A 2000 V AC 2000 V AC PS11 for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC PZ11 for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC GZU11 for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC GZ11 for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC GZS11 for screw terminals 300 V AC 10 A 2000 V AC 2000 V AC GZP11 for screw terminals 300 V AC 12 A 2500V AC 2000 V AC GOP11 for solder terminals 250 V AC 10 A 2000 V AC 2000 V AC GZ14U for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC GZ14 for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC GOP14 for solder terminals 250 V AC 10 A 2000 V AC 2000 V AC GZ14Z for screw terminals 250 V AC 10 A 2000 V AC 2000 V AC GUC11 for screw terminals 250 V AC 16 A 2000 V AC 2000 V AC PI6W-1P for screw terminals 250 V AC 6A 4000 V AC – ❶ Also relays RM85 inrush, RM85 105 °C sensitive www.relpol.com.pl ❷ Also versions RM87L sensitive, RM87P sensitive ❸ Also versions RM87N sensitive Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 Plug-in sockets technical data 247 General data Terminal capacity For relays Ambient temperature (operating) Protection category (PN-EN 60529) Maximum screw torgue 2 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 RM84, (RM85 ❶), (RM87L, RM87P ❷) 2 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 RM84, (RM85 ❶), (RM87L, RM87P ❷) 2 -40...+85 oC IP 20 0,5 Nm 2 x 2,5 mm RM84, (RM85 ❶), (RM87L, RM87P ❷) 2 -40...+85 oC – – – RM84, (RM85 ❶), (RM87L, RM87P ❷) 2 -40...+85 oC – – – RM84, (RM85 ❶), (RM87L, RM87P ❷) 2 -40...+85 oC – – – RM84, (RM85 ❶), (RM87L, RM87P ❷) 1 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 RM87N ❸ 1 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 RM87N ❸ 1 -40...+85 oC IP 20 0,5 Nm 2 x 2,5 mm2 RM87N ❸ 1 -40...+85 oC – – – RM87N ❸ 1 -40...+85 oC – – – RM87N ❸ 1 -40...+85 oC IP 20 0,5 Nm – RM96 1 C/O 1 -40...+85 oC – – – – 2 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 R2 2 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 R2 2 -40...+70 oC – – – 2 -40...+70 oC – 2 -40...+70 oC – 3 -40...+70 oC 3 Number of poles Maximum size of wires (multi-cable) 2 R2 – 2 x 0,75 mm 2 R2 – 2 x 0,75 mm2 R2 IP 20 0,7 Nm 2 x 2,5 mm2 R3 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 R3 4 -40...+70 oC IP 20 0,7 Nm 2 2 x 2,5 mm R4, T-R4 4 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 R4, T-R4 4 -40...+70 oC IP 20 0,7 Nm 2 x 1,5 mm2 R4 4 -40...+70 oC IP 20 0,7 Nm 2 x 1,5 mm R4 4 -40...+70 oC – – – R4 4 -40...+70 oC – – – R4 4 -40...+70 oC – – 2 x 0,75 mm2 R4 2 -40...+70 oC IP 00 0,7 Nm 2 x 2,5 mm RY2 2 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 R2M 2 -40...+70 oC – – – R2M 2 -40...+70 oC – – – 2 -40...+70 oC IP 20 2 -40...+70 oC IP 00 2 -40...+70 oC 2 2 R2M 0,7 Nm 2 2 x 2,5 mm R15 2 C/O 0,7 Nm 2 x 2,5 mm2 R15 2 C/O IP 00 0,7 Nm 2 x 2,5 mm2 R15 2 C/O 2 -40...+70 oC IP 00 1,0 Nm 2 2 x 2,5 mm R15 2 C/O 2 -40...+70 oC IP 20 0,5 Nm 2 x 2,5 mm2 R15 2 C/O 2 -40...+70 oC – – – R15 2 C/O 3 -40...+70 oC IP 20 0,7 Nm 2 x 2,5 mm2 R15 3 C/O 3 -40...+70 oC IP 20 0,7 Nm 2 2 x 2,5 mm R15 3 C/O 3 -40...+70 oC IP 00 0,7 Nm 2 x 2,5 mm2 R15 3 C/O 3 -40...+70 oC IP 00 0,7 Nm 2 x 2,5 mm2 R15 3 C/O 3 -40...+70 oC IP 00 1,0 Nm 2 x 2,5 mm2 R15 3 C/O 3 -40...+70 oC IP 20 0,5 Nm 2 x 2,5 mm2 R15 3 C/O 3 -40...+70 oC – – – R15 3 C/O 4 -40...+70 oC IP 00 0,7 Nm 2 x 2,5 mm2 R15 4 C/O oC 4 -40...+55 IP 00 0,7 Nm 2 x 2,5 mm R15 4 C/O 4 -40...+70 oC – – – R15 4 C/O 4 -40...+55 oC IP 00 0,7 Nm 2 x 2,5 mm2 R15 4 C/O 3 -40...+70 oC IP 00 0,7 Nm 2 x 2,5 mm2 1 oC IP 20 0,3 Nm 1 x 2,5 / 2 x 1,5 mm -40...+55 2 RUC 2 RM699BV, RSR30 ❹ ❹ Solid state relays RSR30 type - see catalogue ”Solid state relays” and www.relpol.com.pl Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900 www.relpol.com.pl Test buttons (no latching) and plugs 248 Test buttons are recommended for R2...WT, R3...WT, R4...WT, R15...WT 2 C/O, R15...WT 3 C/O relays - for applications that do not allow permanent contact latching. By manual operation (pressing the button) relay contacts can get switched for as long time as long the button is pressed. Contacts return to initial position as soon as pressure is released from the button. Those operations can be done while the coil is deenergized. Button R4P-0001 or R15-M404 can be easily inserted by the Customer after removal of button type T (see Fig. 2). Button type T can be removed with screwdriver as shown on Fig. 1. Fig. 1 Dimensions - test button R15-M404 for relays R15...WT 2 C/O, R15...WT 3 C/O 13,7 - 0,2 11,7 - 0,2 Dimensions - test button R4P-0001 for relays R2...WT, R3...WT, R4...WT Fig. 2 Ø 3,35 - 0,05 5,75 5,5 Ø 3,5 - 0,1 11,6 13,4 Types of buttons: R4P-0001-A - orange colour (AC coils) R4P-0001-D - green colour (DC coils) Types of buttons: R15-M404-A - orange colour (AC coils) R15-M404-D - green colour (DC coils) Plugs R4W-0003 or R15-M203 can substitute button type T if manual operation (latching and testing) is not allowed. Changing button type T for plug can be done by Customer themselves in the same way as changing button type T for button (no latching). Dimensions - plug R15-M203 for relays R15...WT 2 C/O, R15...WT 3 C/O 9,3 10,36 - 0,05 Dimensions - plug R4W-0003 for relays R2...WT, R3...WT, R4...WT Ø 3,40 - 0,12 Ø 3,50 - 0,03 R R 6,43-0,03 5,95-0,1 8 2, 7 2, R 17,23 ± 0,03 Types of plugs: R4W-0003-A - orange colour (AC coils) R4W-0003-D - green colour (DC coils) www.relpol.com.pl 5 2, 10,28 - 0,03 Types of plugs: R15-M203-A - orange colour (AC coils) R15-M203-D - green colour (DC coils) Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900