SINAMICS G150 - NEMA Type A - Data Sheet

SINAMICS Drives
SINAMICS G150 NEMA
Type A enclosed drive 150 – 800 HP
Introduction
This specification sheet provides a short overview of
the most important characteristics of the NEMA version
of SINAMICS G150 type A. For more comprehensive
information about the drive and options, as well as more
detailed technical data, refer to the SINAMICS G150
NEMA catalog D11.7.
The SINAMICS G150 type A enclosed drive is a stand-alone
variable speed enclosed drive ideal for all applications that
involve moving, conveying, pumping or compressing solids,
liquids or gases. In particular, this includes variable torque
applications such as pumps, fans, blowers, and compressors,
as well as constant torque applications such as mixers,
extruders and mills that do not require regeneration.
This compact and quiet drive uses IGBT power semi-conductors
and an innovative cooling concept. The control can be
operated in either Volts/Hertz, sensorless vector or closed
loop vector (with speed feedback encoder) control modes.
Standard features
The G150 type A enclosed drive is ready to install and run,
complete with all necessary accessories. It is offered with
a large variety of standard and custom input and output
options, such as contactors, across the line or solid state
bypass circuits, and output reactor.
SINAMICS G150 type A is delivered with the following
standard features:
• Basic NEMA 1 enclosure
• Circuit breaker disconnect (per NEC requirements for
motor branch circuit protection), mechanically
interlocked with the enclosure door
• Fuses as required for SCCR (short circuit current rating)
• Input line reactor
• Controller CU320-2 DP with integral PROFIBUS DP
communication port and Ethernet programming port
• Input/output module TM31, with digital and analog I/O
• Advanced Operator Panel AOP30 for easy start-up
and operation
• Windows-based start-up STARTER software –
common to all models of the SINAMICS drives family
• CE mark
June 2014
www.usa.siemens.com/drives
Product Specifications
Light Overload
High Overload
Output Base
(at 460V, (at 400V
load
or 575V, or 500V
current
60 Hz) 50Hz)
I L 1
HP kW
A
Supply voltage 380 V to 480 V 3 ph. AC
Output
(at 460V
(at 400V
or 575V,
or 500V,
60 Hz)
50Hz)
HP
kW
Base
load
current
IH 1
A
Rated
Rated Output
input
current current 2
IN 1
A
A
SINAMICS G150
NEMA Type A
Enclosed Drive
Order No.
150
110
205
125
90
178
210 239
6SL3710-1GE32-1AU3
200
132
250
150
110
233
260 294
6SL3710-1GE32-6AU3
250
160
302
200
132
277
310 348
6SL3710-1GE33-1AU3
300
200
370
250
160
340
380 405
6SL3710-1GE33-8AU3
400
250
477
350
200
438
490 519
6SL3710-1GE35-0AU3
500
315
590
400
250
460
605 639
6SL3710-1GE36-1AU3
600
400
725
500
315
570
745 785
6SL3710-1GE37-5AU3
700
450
820
600
400
700
840 883
6SL3710-1GE38-4AU3
800
560
960
700
450
860
9851034
6SL3710-1GE41-0AU3
Supply voltage 500 V to 600 V 3 ph. AC
150
110
171
150
90
157
175 201
6SL3710-1GF31-8AU3
200
132
208
200
110
192
215 234
6SL3710-1GF32-2AU3
250
160
250
250
132
233
260 280
6SL3710-1GF32-6AU3
300
200
320
300
160
280
330 353
6SL3710-1GF33-3AU3
400
250
400
350
200
367
410 436
6SL3710-1GF34-1AU3
450
315
452
450
250
416
465 493
6SL3710-1GF34-7AU3
600
400
560
500
315
514
575 608
6SL3710-1GF35-8AU3
700
500
710
600
450
657
735 774
6SL3710-1GF37-4AU3
800
560
790
700
500
724
810 852
6SL3710-1GF38-1AU3
1
For a NEMA 12 (ventilated) enclosure (option M54), current values must be reduced to 95% of the values in this table.
2 The input current is based on the rated output current and includes 10A to power optional auxiliary circuits in the drive (such as L17, L50, N70).
Note: HP ratings are based on rated current, and provided as a guide only, for standard 2, 4 or 6 pole motors. Select drive based on motor FLA and overloads.
Options
Option Code Description
Enclosure Options
M06 Base (plinth) 4” (100mm)
M07
M23
M39
M43
M54
M78
M90
Y09
Base (plinth) 8” (200mm)
Enclosure NEMA 1 filtered
Mechanical door interlock (slam latch)
[for doors without c/b operator]
Enclosure IP43
Enclosure NEMA 12 (ventilated)
[Requires current derate to 95%]
Motor side top cable exit
Lifting beam/eye bolts
[Recommended: Required to lift the drive off pallet]
Special enclosure paint color (specify color)
Power Options
L08
Motor reactor
L10
L13
L22
L61
L62
Output dV/dt-Filter with VPL [Requires add-on options cabinet]
Input contactor
Without input line reactor
Braking unit 100 kW (for 150 HP and 200 HP only)
Braking unit 200 kW (for 250 HP to 800 HP only)
Miscellaneous Options
L17
Feeder for external auxiliaries 460V 3ph. AC, max. 10 A
L50
L55
U90
U91
Enclosure light with power outlet 120 V, 1 ph AC, 5 A
Enclosure space heater
UL listing per UL508A
[Requires M23, M43 or M54]
cUL listing per UL508A
[Requires M23, M43 or M54 & T58]
Testing
F03
F71
F75
F77
F97
Visual inspection by customer
Witnessed function test without motor
Witnessed function test with test-bay motor, no load
Witnessed test incl. high-voltage and isulation test
Witnessed customer specific test (on request)
Please consult factory for additional engineered options, for example:
Pushbuttons, control switches and indicator lights
Motor space heater connection
Option
Code Description
Bypass Options
L29
L30
3 contactor bypass [Requires add-on options cabinet]
Soft start bypass [Requires add-on options cabinet]
Control Options
G20
G22
G27
G33 G51 G52
G61 G65 G66 K01 K50 K51 K52 K82 K87 K88 K95 L87
L96 N55 N57
N59
N60
N70
Communication board CBC10 (CAN-open)
Modbus RTU communication
MODBUS TCP/IP communication
CBE20 for SINAMICS link or PROFINET or EtherNet/IP
TM150 Terminal Module for RTD monitoring
Qty. 2 of TM150 Terminal Module for RTD monitoring
Additional TM31 terminal module for digital and analog I/O
TM31 I/O wired to customer terminal strip
2nd TM31 (opt. G61) I/O wired to customer terminal strip
Safety license (for 1 axis)
SMC30 sensor module for speed feedback
VSM10 voltage sensing module
Additional SMC30 sensor module
Terminal interface for Safety Integrated functions STO and SS1
TM54F Terminal Module (requires option K01)
Safe Brake Adapter SBA, 230 V AC (not UL listed)
Control unit CU320-2 PN (PROFINET)
Insulation Monitor for ungrounded supplies
Input surge protective device
ALL STOP (mushroom pushbutton), coast to stop
Emergency Stop category 0, 120V or 24V, coast to stop
Emergency Stop category 1, 120V, controlled ramp down
Emergency Stop category1, 24V, controlled ramp down
Control power supply 120V, 5A
Documentation and Languages
D02
D04
D14
D58
T58
Customer drawings in dxf format
Customer documentation in paper format, one set
Advance copy of customer documentation (pdf)
Documentation English/French
Nameplate English/French
Bypass – Automatic or Synchronized
Output sinusoidal filter or contactor(s)
Design Data
10 ” /
250 mm
Spacing to ceiling if rear
is mo un ted against wall
AIR OUT
Add-on Output
Opions Cabinet
SINAMICS
79” / 2000 mm
94.5” / 2400 mm
Tophat
AIR IN
4” / 100 mm
Op
tio n M06
Option
M06
Option M07
8” / 200 mm
23.6” / 600 mm
SIDE VIEW
WN
Wo
FRONT VIEW
G150 type A on pallet,
with transport beams
(tophats removed)
Note:
•The drawing shows the SINAMICS G150 type A enclosed drive with louvers (option M23, M43 or M54).
• For transport reasons, the tophats are delivered separately and must be fitted on site.
• To assure proper air circulation through the drive, please allow a minimum space of 10” (250mm) between drive tophat and ceiling when mounted against
a wall.
• All dimensions are nominal for sheet steel enclosure, tolerance 0.5” (12 mm), excluding protruding components. Please refer to order drawings for exact details.
SINAMICS G150
Output
Noise
Cooling HeatWeight Nominal
Nominal
NEMA Type A
(Light level LpA
air flow
loss approx. Width
Width
Enclosed drive
Overload) (1m) at demand
(standard Drive
Options
(at 460V, or 50/60 Hz
enclosure Enclosure
Cabinet
575, 60 Hz)w/o options) WN (dV/dt Filt. L10)
WO
Model No.
HP
dB(A)
cfm
kW lb
kg
inch
inch inch mm
Supply voltage 380 V to 480 V 3 ph. AC
6SL3710-1GE32-1AU3 150
67 / 68 360 2.9 950 430 39.4 1000 23.6
600
6SL3710-1GE32-6AU3 200
69 / 73 487 3.8 950 430 39.4 1000 23.6
600
6SL3710-1GE33-1AU3 250
69 / 73 763 4.41250 570 39.4 1000 23.6
600
6SL3710-1GE33-8AU3 300
69 / 73 763 5.31250 570 39.4 1000 23.6
600
6SL3710-1GE35-0AU3 400
69 / 73 763 6.41250 570 39.4 1000 23.6
600
6SL3710-1GE36-1AU3 500
70 / 731653 8.22000 900 47.2 1200 15.8
400
6SL3710-1GE37-5AU3 600
70 / 731653 9.62000 900 47.2 1200 15.8
400
6SL3710-1GE38-4AU3 700
70 / 73165310.12000 900 47.2 1200 15.8
400
6SL3710-1GE41-0AU3 800
72 / 75313614.4 3100 1400 63.0 1600 15.8
400
Supply voltage 500 V to 600 V 3 ph. AC
6SL3710-1GF31-8AU3 150
69 / 73 763 3.81200 550 39.4 1000 23.6
600
6SL3710-1GF32-2AU3 200
69 / 73 763 4.21200 550 39.4 1000 23.6
600
6SL3710-1GF32-6AU3 250
69 / 73 763 5.01200 550 39.4 1000 23.6
600
6SL3710-1GF33-3AU3 300
69 / 73 763 6.11200 550 39.4 1000 23.6
600
6SL3710-1GF34-1AU3 400
72 / 751653 8.1 1700 780 47.2 1200 15.8
400
6SL3710-1GF34-7AU3 450
72 / 751653 7.81700 780 47.2 1200 15.8
400
6SL3710-1GF35-8AU3 600
72 / 751653 8.71700 780 47.2 1200 15.8
400
6SL3710-1GF37-4AU3 700
72 / 75313612.731001360 63.0 1600 15.8
400
6SL3710-1GF38-1AU3 800
72 / 75313614.131001400 63.0 1600 15.8
400
Nominal
Width
Options
Cabinet
(Bypass L29)
WO
inch mm
Nominal
Width
Options
Cabinet
(SS Bypass L30)
WO
inch
mm
23.6 600
23.6 600
23.6 600
23.6 600
23.6 600
23.6 600
23.6 600
39.41000
39.41000
23.6 600
23.6 600
23.6 600
23.6 600
31.5 800
39.41000
39.41000
70.91800
70.91800
23.6 600
23.6 600
23.6 600
23.6 600
23.6 600
23.6 600
23.6 600
39.41000
39.41000
23.6 600
23.6 600
23.6 600
23.6 600
31.5 800
31.5 800
39.41000
39.41000
70.91800
Technical Data
Electrical data
Supply voltages and output ranges
Supply systems
Line frequency
Output frequency
Power factor fundamental / total
Converter efficiency
Short circuit current rating
Control method
Fixed speeds
Skipped frequency ranges
Braking operation
Mechanical data
Type of enclosure
Type of cooling
Noise level LpA (1 m)
Environmental protection
Compliance with standards
UL listing
Ambient conditions
Ambient temperature
Relative humidity (non-condensing)
Installation altitude
380 V to 480 V 3 ph AC, ±10% (-15% < 1 min) 150 to 800 HP
500 V to 600 V 3 ph AC, ±10% (-15% < 1 min) 150 to 800 HP
Grounded (TN/TT) supplies or ungrounded (IT) supplies
47 Hz to 63 Hz
0 Hz to 300 Hz
> 0.98 / 0.93 to 0.96
> 98%
SCCR per UL508A at 480V, all HP: 65kA; at 600V to 400HP: 25kA, 450HP: 30 or 35kA, 600HP - 800HP: 35kA
Vector control (sensorless and closed loop) or V/Hz control
15 fixed speeds plus 1 minimum speed, programmable (in the default setting 3 fixed setpoints plus 1 minimum speed can be selected via digital inputs/ PROFIBUS)
4, programmable
optional via braking unit
NEMA1 (optionally NEMA 1 filtered or NEMA12 ventilated) Color RAL 7035 light grey
Forced air ventilation
< 75 dB at 60 Hz line frequency
Nickel plated busbars, varnish coated electronic boards
Optional listing per UL508A
Operation
Storage
Transport
32°F to 104°F (0 °C to +40 °C)
-13°F (-25 °C) to 131°F (+55 °C)
-13°F (-25 °C) to 158°F (+70 °C)
Up to +122°F/+50°C with derating Above -40°F (-40 °C) for 24 hours
5% to 95%
5% to 95%
5% to 95% at 40 °C
corresponds to 3K3 to IEC 60721-3-3
corresponds to 1K4 to IEC 60721-3-1 corresponds to 2K3 to IEC 60721-3-2
Up to 6,600 ft (2000 m) above sea level without reduction in performance, > 6,600 ft see derating data
Engineering Information
Overload ratings
The SINAMICS G150 drive may be operated
with both variable torque and constant
torque loads at either light or high overload duties. The criterion for overload
is that the drive is operated with its
base load current before and after the
overload occurs.
Light overload duty is based on 110% base
load current for 60 sec or 150% for 10 sec,
repeated every 300 sec.
Motor and drive sizing
Service Factor must be considered for
motors operating at Service Factors
beyond 1.0. Please consult factory for
assistance sizing the drive.
For motors with ratings larger than
the drive, please consult factory as
nuisance tripping may occur if drive is
not properly sized.
In sensorless vector control, the rated
motor current (FLA) must be at least Z⁄v
of the rated drive output current. With
lower motor currents, operation is
possible in Volts/Hz control mode only.
Advanced operator panel (AOP30)
Light overload
High overload duty is based on 150% base
load current for 60 sec or 160% for 10 sec,
repeated every 300 sec.
Siemens Industry, Inc.
Drive Technologies
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
[email protected]
www.usa.siemens.com/drives
Subject to change without prior notice.
Order No. DRBR-G150A-0614
Printed in USA
©2014 Siemens Industry, Inc.
The easy-to-use advanced operator panel is
common to all SINAMICS enclosed drives.
The AOP30 is mounted in the enclosure
door of the G150 drive, and is used for
start-up/commissioning or operation and
troubleshooting of the drive.
During the first start-up of the drive, the
user will automatically be guided through
the initial start-up procedure that allows
a very simple and quick commissioning
process. Parameters are arranged
according to function groups which
makes it easy to find and select them.
The AOP30 features a graphical LCD with
backlighting for plain text and bar graph
display of process variables:
• LEDs for display of operational status
• Numeric keypad and drive specific hard and soft function keys
• Access control to inhibit changing
of parameters
• Help functions with description of causes and remedies for faults and alarms
• Alarm and fault status in plain text
• Configurable operating display allows
up to 3 variables displayed in bar graph
format, with associated numerical values
The information provided in this brochure contains merely
general descriptions or characteristics of performance
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
terms of contract.