SINAMICS G150 - NEMA Type C - Data Sheet

SINAMICS Drives
SINAMICS G150 NEMA
Type C enclosed chassis 150 – 800 HP
Introduction
This specification sheet provides a short overview of
the most important characteristics of the NEMA version
of SINAMICS G150 type C. For more comprehensive
information about the drive and options, as well as more
detailed technical data, refer to the SINAMICS G150
NEMA catalog D11.7.
The SINAMICS G150 type C enclosed chassis is a standalone variable speed enclosed drive ideal for all applications
that involve moving, conveying, pumping or compressing
solids, liquids or gases. In particular, this includes variable
torque applications such as pumps, fans, blowers, and
compressors, as well as constant torque applications such as
mixers, extruders and mills that do not require regeneration.
This compact and quiet drive uses IGBT power semi-conductors
and an innovative cooling concept. The control can be
operated in either Volts/Hertz, sensorless vector or closed
loop vector (with speed feedback encoder) control modes. Standard features
The G150 type C enclosed chassis is a drive in a very compact
enclosure, for use with external disconnect and circuit
protection (for example in an existing MCC). It is offered
with a limited range of standard options, such as enclosure
type, input line reactor or speed encoder feedback module.
SINAMICS G150 type C is delivered with the following
standard features:
• Basic NEMA 1 enclosure
• Controller CU320-2 DP with integral PROFIBUS DP
communications port and Ethernet programming port
• Input/output module TM31, with digital and analog I/O
• Advanced Operator Panel AOP30 for easy start-up
and operation
• Windows-based start-up STARTER software – common to all models of the SINAMICS drives family
• CE mark
June 2014
www.usa.siemens.com/drives
Product Specifications
Light Overload
High Overload
Output
(at 460V
(at 400V
or 575V,
or 500V,
60 Hz
50Hz)
HP
kWA
Base
load
current
IH 1
A
Rated
Rated Output
input
current current 2
IN 1
A
Order No.
125
90
150110
200132
250160
350200
400250
500315
600400
700450
178
233
277
340
438
460
570
700
860
210 229
260 284
310 338
380 395
490 509
605 629
745 775
840 873
9851024
6SL3710-1GE32-1CU3
6SL3710-1GE32-6CU3
6SL3710-1GE33-1CU3
6SL3710-1GE33-8CU3
6SL3710-1GE35-0CU3
6SL3710-1GE36-1CU3
6SL3710-1GE37-5CU3
6SL3710-1GE38-4CU3
6SL3710-1GE41-0CU3
150 90
200
110
250132
300
160
350200
450250
500315
600450
700500
157
192
233
280
367
416
514
657
724
175
215
260
330
410
465
575
735
810
6SL3710-1GF31-8CU3
6SL3710-1GF32-2CU3
6SL3710-1GF32-6CU3
6SL3710-1GF33-3CU3
6SL3710-1GF34-1CU3
6SL3710-1GF34-7CU3
6SL3710-1GF35-8CU3
6SL3710-1GF37-4CU3
6SL3710-1GF38-1CU3
Output Base
460V, (at 400V
load
or 575V, or 500V
current
60 Hz) 50Hz)
I L 1
HP kW
A
Supply voltage 380 V to 480 V 3 ph. AC
150
200
250
300
400
500
600
700
800
110
132
160
200
250
315
400
450
560
205
250
302
370
477
590
725
820
960
SINAMICS G150
NEMA Type C
Enclosed Chassis
Supply voltage 500 V to 600 V 3 ph. AC
150
200
250
300
400
450
600
700
800
110
132
160
200
250
315
400
500
560
171
208
250
320
400
452
560
710
790
191
224
270
343
426
483
598
764
842
For a NEMA 12 (ventilated) enclosure (option M54), current values must be reduced to 95% of the values in this table.
The input current is based on the rated output current.
Note: HP ratings are based on rated current, and provided as a guide only, for standard 2, 4 or 6 pole motors. Select drive based on motor FLA and overloads.
1
2
Options
Option Code Description
Enclosure Options
Option
Code Description
M06
M07
M23
M43
M54
M90
Y09
L55
U90
U91
Base (plinth) 4” (100mm)
Base (plinth) 8” (200mm)
Enclosure NEMA 1 filtered
Enclosure IP43
Enclosure NEMA 12 (ventilated)
[Requires current derate to 95%]
Lifting beam/eye bolts
[Recommended: Required to lift the drive off pallet]
Special enclosure paint color (specify color)
Power Options
L23
Input line reactor
Control Options
G20 G33 G51
K01*
K50 K95 CBC10 communication board CANopen
CBE20 for SINAMICS link or PROFINET or EtherNet/IP
TM150 Terminal Module for RTD monitoring
Safety license (for 1 axis)
SMC30 sensor module for speed feedback
Control unit CU320-2 PN (PROFINET)
Miscellaneous Options
Enclosure space heater
UL listing per UL508A
cUL listing per UL508A
[Requires M23, M43 or M54]
[Requires M23, M43 or M54 & T58] Documentation and Languages
D02
D04
D14
D58
T58
Customer drawings in dxf format
Customer documentation in paper format, one set
Advance copy of customer documentation (pdf)
Documentation English/French
Nameplate English/French
For additional languages, please consult factory
Testing
F03
F71
F75
F77
F97
Visual inspection by customer
Witnessed function test without motor
Witnessed function test with test-bay motor, no load
Witnessed test incl. high-voltage and isulation test
Witnessed customer specific test (on request)
* Integrated Safety functionality on SINAMICS G150 type C:
• Basic and extended safety functions can be controlled only using PROFISAFE on PROFIBUS or PROFINET bus communications (fail safe inputs or outputs are not available)
• Only encoderless implementation of safety functions is possible, with associated restrictions (only with induction motors, no optimized pulse patterns,
no sweep frequency generation, no fine adjustment of pulse frequency, and only for applications with low dynamic requirements i.e. acceleration or
deceleration ramp time >1 second)
Design Data
Spacing to ceiling if rear
is mo un ted against wall
10 ” /
250 mm
AIR OUT
SINAMICS
79” / 2000 mm
94.5” / 2400 mm
Tophat
AIR IN
4” / 100 mm
Option M06
Option M07
8” / 200 mm
23.6” / 600 mm
WN
SIDE VIEW
FRONT VIEW
G150 type C with
transport eye bolts
(tophat removed)
Note:
•The drawing shows the SINAMICS G150 type C enclosed chassis with louvers (option M23, M43 or M54).
• For transport reasons, the tophat is delivered separately and must be fitted on site.
• To assure proper air circulation through the drive, please allow a minimum space of 10” (250mm) between drive tophat and ceiling when mounted against
a wall.
• All dimensions are nominal for sheet steel enclosure, tolerance 0.5” (12 mm), excluding protruding components. Please refer to order drawings for exact details.
SINAMICS G150
NEMA Type C
Enclosed chassis
Output
Noise
Cooling Heat
Weight approx.
Nominal Width
(Light level LpA
air flow
loss (standard enclosure)
Drive Enclosure
Overload) (1m) at demand
w/o options)
WN
(at 460V, or 50/60 Hz
575, 60 Hz) HP
dB(A)
cfm
kW lb
kg
inch
inch
Model No.
Supply voltage 380 V to 480 V 3 ph. AC
6SL3710-1GE32-1CU3
150
6SL3710-1GE32-6CU3
200
6SL3710-1GE33-1CU3
250
6SL3710-1GE33-8CU3
300
6SL3710-1GE35-0CU3
400
6SL3710-1GE36-1CU3
500
6SL3710-1GE37-5CU3
600
6SL3710-1GE38-4CU3
700
6SL3710-1GE41-0CU3
800
Supply voltage 500 V to 600 V 3 ph. AC
6SL3710-1GF31-8CU3
150
6SL3710-1GF32-2CU3
200
6SL3710-1GF32-6CU3
250
6SL3710-1GF33-3CU3
300
6SL3710-1GF34-1CU3
400
6SL3710-1GF34-7CU3
450
6SL3710-1GF35-8CU3
600
6SL3710-1GF37-4CU3
700
6SL3710-1GF38-1CU3
800
67 / 68
360 2.9
480 220
69 / 73 487 3.8 480 220
69 / 73 763 4.4 640 290
69 / 73 763 5.3 640 290
69 / 73
763 6.4
640 290
70 / 731653 8.2
1400 640
70 / 731653 9.6
1400 640
70 / 73
1653 10.1
1400 640
72 / 75
3136 14.4
22501020
15.8 400
15.8 400
15.8 400
15.8 400
15.8 400
23.6 600
23.6 600
23.6 600
39.41000
69 / 73
763 3.8
640 290
69 / 73 763 4.2 640 290
69 / 73 763 5.0 640 290
69 / 73 763 6.1
640 290
72 / 751653 8.11400 640
72 / 751653 7.81400 640
72 / 751653 8.71400 640
72 / 75
3136 12.72150 980
72 / 75
3136 14.122501020
15.8 400
15.8 400
15.8 400
15.8 400
23.6 600
23.6 600
23.6 600
39.4
1000
39.4
1000
Technical Data
Electrical data
Supply voltages and output ranges
Supply systems
Line frequency
Output frequency
Power factor fundamental / total
Converter efficiency
Short circuit current rating
Control method
Fixed speeds
Skipped frequency ranges
Mechanical data
Type of enclosure
Type of cooling
Noise level LpA (1 m)
Environmental protection
Compliance with standards
UL listing
Ambient conditions
Ambient temperature
Relative humidity (non-condensing)
Installation altitude
380 V to 480 V 3 ph AC, ±10% (-15% < 1 min) 150 to 800 HP
500 V to 600 V 3 ph AC, ±10% (-15% < 1 min) 150 to 800 HP
Grounded (TN/TT) supplies or ungrounded (IT) supplies
47 Hz to 63 Hz
0 Hz to 300 Hz
> 0.98 / 0.93 to 0.96
> 98%
SCCR per UL508A at 480V 65kA, at 600V 35kA, when used with recognized AC input line fuses as specified in the user
manual and listed circuit breakers
Vector control (sensorless and closed loop) or V/Hz control
15 fixed speeds plus 1 minimum speed, programmable (in the default setting 3 fixed setpoints plus 1 minimum speed can be selected via digital inputs/ PROFIBUS)
4, programmable
NEMA1 (optionally NEMA 1 filtered or NEMA12 ventilated) Color RAL 7035 light grey
Forced air ventilation
< 75 dB at 60 Hz line frequency
Nickel plated busbars, varnish coated electronic boards
Optional listing per UL508A
Operation
Storage
Transport
32°F to 104°F (0 °C to +40 °C)
-13°F (-25 °C) to 131°F (+55 °C)
-13°F (-25 °C) to 158°F (+70 °C)
Up to +122°F/+50°C with derating Above -40°F (-40 °C) for 24 hours
5% to 95%
5% to 95%
5% to 95% at 40 °C
corresponds to 3K3 to IEC 60721-3-3
corresponds to 1K4 to IEC 60721-3-1 corresponds to 2K3 to IEC 60721-3-2
Up to 6,600 ft (2000 m) above sea level without reduction in performance, > 6,600 ft see derating data
Engineering Information
Overload ratings
The SINAMICS G150 drive may be operated
with both variable torque and constant
torque loads at either light or high overload duties. The criterion for overload
is that the drive is operated with its
base load current before and after the
overload occurs.
Light overload duty is based on 110% base
load current for 60 sec or 150% for 10 sec,
repeated every 300 sec.
Motor and drive sizing
Service Factor must be considered for
motors operating at Service Factors
beyond 1.0. Please consult factory for
assistance sizing the drive.
For motors with ratings larger than
the drive, please consult factory as
nuisance tripping may occur if drive is
not properly sized.
In sensorless vector control, the rated
motor current (FLA) must be at least Z⁄v
of the rated drive output current. With
lower motor currents, operation is
possible in Volts/Hz control mode only.
Advanced operator panel (AOP30)
Light overload
High overload duty is based on 150% base
load current for 60 sec or 160% for 10 sec,
repeated every 300 sec.
Siemens Industry, Inc.
Drive Technologies
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
[email protected]
www.usa.siemens.com/drives
Subject to change without prior notice.
Order No. DRBR-G150C-0614
Printed in USA
©2014 Siemens Industry, Inc.
The easy-to-use advanced operator panel is
common to all SINAMICS enclosed drives.
The AOP30 is mounted in the enclosure
door of the G150 drive, and is used for
start-up/commissioning or operation and
troubleshooting of the drive.
During the first start-up of the drive, the
user will automatically be guided through
the initial start-up procedure that allows
a very simple and quick commissioning
process. Parameters are arranged
according to function groups which
makes it easy to find and select them.
The AOP30 features a graphical LCD with
backlighting for plain text and bar graph
display of process variables:
• LEDs for display of operational status
• Numeric keypad and drive specific hard and soft function keys
• Access control to inhibit changing of
parameters
• Help functions with description of causes and remedies for faults and alarms
• Alarm and fault status in plain text
• Configurable operating display allows
up to 3 variables displayed in bar graph
format, with associated numerical values
The information provided in this brochure contains merely
general descriptions or characteristics of performance
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
terms of contract.
All product designations may be trademarks or product
names of Siemens AG or supplier companies whose use by
third parties for their own purposes could violate the rights
of the owners.