Smart Product Brochure

© Siemens AG 2012
Brochure
Edition
10/2012
SITOP smart
The high-performance standard power
supply for 1 and 3-phase networks
SITOP smart is the high-performance standard power
supply for automated machinery and plants with 24 V or
12 V DC electronics. Thanks to its high overload capability, even loads with high power demand can be connected
without difficulty. The 24 V power supplies can continuously manage 120% of the rated power. Thanks to their
slim design and seamless installation next to laterally
mounting devices, the power supplies require little space
on the DIN rail. The high degree of efficiency ensures low
energy consumption and minimal heat loss in the control
cabinet.
The flexible input voltage ranges allow problem-free
connection to 1 and 3-phase networks around the world.
Comprehensive certifications also facilitate universal
usage, e.g in hazardous areas.
To further increase the availability, the reliable power
supplies can be combined with DC UPS, redundancy and
selectivity modules.
The benefits at a glance
• Minimum mounting space required due to slim
design, no lateral installation clearances required
• "Extra Power" with 1.5 times the rated current for
5 s/min for brief overloads
• Can be continuously used with 120% of the
rated power at up to 45 °C ambient temperature
(24 V versions)
• Signaling contact for "output voltage OK" for easy
integration in the plant monitoring system
• Low energy consumption and minimal heat dissipation inside the control cabinet due to the high
degree of efficiency
• PSU100S:
automatic range switchover 120/230 V AC
PSU300S:
Wide-range input 400 – 500 V 3 AC
• Adjustable output voltage for compensating
voltage drops
• Wide temperature range from -10 to +70 °C
• Numerous certifications for all standard applications worldwide
Answers for industry.
© Siemens AG 2012
Technical specifications 1)
SITOP PSU100S, 1-phase
Output voltage/current
12 V/7 A
12 V/14 A
24 V/2.5 A
24 V/5 A
24 V/10 A
Order No.2)
6EP1 322-2BA00
6EP1 323-2BA00
6EP1 332-2BA20
6EP1 333-2BA20
6EP1 334-2BA20
Input voltage
– Rated value 120/230 V AC
– Range 85 ... 132/170 ... 264 V AC, automatic range switchover
Line frequency
– Rated value 50/60 Hz
Mains buffering
20 ms (at 93/187 V AC)
Input current
– Rated value at 120 V/230 V AC 1.73 A/0.99 A
– Inrush current (25 °C) < 45 A
– Recommended MCB From 6 A,
C characteristic
3.24 A/1.41 A
1.25 A/0.74 A
2.34 A/1.36 A
4.49 A/1.91 A
< 60 A
< 33 A
< 40 A
< 60 A
From 10 A,
C characteristic
From 3 A,
C characteristic
From 6 A,
C characteristic
From 10 A,
C characteristic
5A
6A
from +60 °C (3%/K)
10 A
12 A
from +60 °C (3%/K)
85%
88%
90%
not applicable
Yes
Output voltage
– Rated value 12 V DC
– Tolerance ± 3%
– Adjustment range 11.5 … 15.5 V DC
24 V DC
± 3%
22.8 … 28 V DC
Output current
– Rated value 7 A
– Continuously up to +45 °C 7 A
– Derating from +55 °C (5%/K)
14 A
14 A
from +55 °C (5%/K)
Overload response
Extra Power: 1.5 x rated output current for 5 s/min
Switching in parallel
Yes
Efficiency at rated value, approx. 84%
87%
Short-circuit protection
Constant current characteristic
Radio interference suppression
(EN 55022)
Class B
Radio interference suppression
(EN 61000-3-2)
Yes
Degree of protection EN 60529
IP20
Ambient temperature
-10 … +70 °C
Dimensions (W x H x D) in mm
50 x 125 x 125
70 x 125 x 125
32.5 x 125 x 125
50 x 125 x 125
70 x 125 x 125
Weight, approx.
0.5 kg
0.8 kg
0.32 kg
0.5 kg
0.8 kg
Approvals
CE, cULus, ATEX; available soon: GL, and cCSAus Class1 Div 2
SITOP add-on modules –
customized all-round protection
Optional add-on modules intercept individual interference
factors such as mains and voltage
fluctuations and allow operation
in regions with unreliable quality
of supply. Fault-related overload
in the output circuit is selectively
disconnected so that the supply to
the other loads is maintained.
Configuration with SITOP smart and add-on modules
PSU100S
power
supply
PSE202U
redundancy
module
24 V DC
2
2.5 A
3A
from +60 °C (3%/K)
SITOP smart
PSU100S
power
supply
UPS500S
uninterruptible
power supply
PSE200U
selectivity module
PLC, HMI
Actuators
Sensors
...
24 V DC, buffered
© Siemens AG 2012
SITOP PSU300S, 3-phase
24 V/20 A
24 V/10 A
24 V/20 A
24 V/40 A
6EP1 336-2BA10
6EP1 434-2BA10
6EP1 436-2BA10
6EP1 437-2BA20
120/230 V AC
85 ... 132/170 ... 264 V AC,
autom. range switchover
400 – 500 V 3 AC
340 … 550 V 3AC
– Rated value
– Range
50/60 Hz
50/60 Hz
– Rated value
20 ms (at 93/187 V)
> 6 ms (at 400 V)
7.5 A/3.5 A
0.7 – 0.5 A
1.2 – 1.0 A
1.7 – 1.5 A
Input current
– Rated value at 120 V/230 V AC
< 11 A
< 36 A
< 36 A
< 60 A
– Inrush current (25 °C)
From 10 A, characteristic C
or 3RV2411-1JA10 (120 V)
or 3RV2411-1FA10 (230 V)
From 6 to 16 A
charact. C, 3-ph. coupled
or 3RV2 011-1DA10
or 3RV2 711-1DD10
From 6 to 16 A
charact. C, 3-ph. coupled
or 3RV2 011-1DA10
or 3RV2 711-1DD10
From 10 to 16 A
charact. C, 3-ph. coupled
or 3RV2 011-1DA10
or 3RV2 711-1DD10
– Required line protection
(PSU300S)
Recommended MCB
(PSU100S)
Output voltage/current
Order No.2)
– Rated value
– Output voltage
– Tolerance
– Adjustment range
10 A
12 A
–
20 A
24 A
from + 60°C (5%/ K)
– Rated value
– Output current
– Continuously up to +45 °C
– Derating
40 A
48 A
from + 60°C (2.5%/ K)
Extra Power: 1.5 x rated output current for 5 s/min, 120% continuously up to 45 °C
Overload response
Yes
90%
Line frequency
Mains buffering
24 V DC
± 3%
24 … 28 V DC
10 A
24 A
from + 60 °C (5%/ K)
Input voltage
Switching in parallel
91%
91%
91.5%
At rated value approx.
Yes, electronic shutdown and automatic restart
Efficiency
Short-circuit protection
Radio interference suppression
(EN 55022)
Class B
Yes
Radio interference suppression
(EN 61000-3-2)
IP20
Degree of protection EN 60529
-10 … +70 °C
115 x 145 x 150
Ambient temperature
90 x 145 x 150
90 x 145 x 150
150 x 145 x 150
1.6 kg
2.6 kg
2.6 kg
3.7 kg
CE, cULus, ATEX, cCSAus
Class1 Div 2, GL
CE, cULus, ATEX, cCSAus Class1 Div 2, GL
Dimensions (W x H x D) in mm
Weight, approx.
Approvals
1) Technical data apply with rated input voltage and +25 °C ambient temperature (if not specified otherwise).
2) You can find up-to-date ordering data as well as our terms of sale and delivery on the Internet.
Everything for project planning
85
55
150
35
149
145
Additional information such as 3D data, circuit diagram
macros, certificates, and operating instructions are
available at the click of a mouse. The project data can be
downloaded in the formats DXF, STEP, and EPLAN and
used directly for your configuration. They are also available via the CAx Download Manager and can be individually selected there as required and called up as a download.
7,8
7,1
157,1
3D
SITOP smart
3
© Siemens AG 2012
Further information
More information on SITOP smart
www.siemens.com/sitop-smart
Information material for download:
www.siemens.com/sitop-infomaterial
The SITOP Selection Tool for selecting the appropriate power
supply:
www.siemens.com/sitop-selection-tool
Operating instructions for downloading:
www.siemens.com/sitop/manuals
CAx data (2D, 3D, circuit diagram macro) as download:
www.siemens.com/sitop-cax
Industry Mall for electronic ordering:
www.siemens.com/industrymall
SITOP contact:
www.siemens.com/automation/partner
Siemens AG
Industry Sector
Industry Automation
Postfach 48 48
90026 NÜRNBERG
GERMANY
www.siemens.com/sitop
Subject to change without prior notice
Order No.: 6ZB5341-0AD02-0AA2
MP.R1.SC.0000.77.3.02 / Dispo 10001
BR 1012 3. ROT 4 En
Printed in Germany
© Siemens AG 2012
The information provided in this brochure contains descriptions or
characteristics of performance which in case of actual use do not
always apply as described or which may change as a result of further
development of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the terms of
contract.
All product designations may be trademarks or product names of